DynaGen
TM
ES52 - EN
User Manual
22
9M02-9253-A001-EN
Revision A
Trouble
Possible Cause
Suggested Action
Engine starts but shuts
down after
Oil Bypass
period due to low oil/high
temperature/auxiliary input
Oil/temp/aux input wiring
improperly connected
Check wiring for proper connections
Engine starts but Running
LED does not illuminate
Improper speed range setting
Check to ensure that controller is set to
proper speed range (using DIP switches
4 and 5)
Fault (short or overload) on
one of the annunciator
outputs
Check for fault; once fault is corrected,
then operation resumes
Crank disconnect pot set too
high
Decrease crank disconnect pot setting
Annunciation output not
working
Fault (short or overload) on
one of the annunciator
outputs
Check for fault; once fault is corrected,
then annunciation operation resumes
Timer LED and timer output
do not activate
Timer pot set to zero
Increase timer pot setting (turn pot
clockwise)
Timer LED works OK but
timer output does not
activate
Fault (short or overload) on
timer output
Check for fault; once fault is corrected,
then output operation resumes
Flashing Over-speed LED
(indicates loss of speed
signal)
Speed signal improperly
connected, missing, or
damaged
Check speed signal wiring; replace
damaged speed signal source
Crank output damaged, not
working
Check wiring and replace controller
Starter or starter solenoid
damaged
Replace/repair damaged starter or starter
solenoid
Engine stalled
Check fueling
Flashing Over-speed using
generator output during
cranking
Not enough residual voltage
during cranking
Set DIP switch 9 to OFF
Alternating flashing of Over-
speed and Over-crank
Crank disconnect set too high
Check crank disconnect
Wrong speed range
Check speed range
Flashing Run LED and solid
Oil LED
Oil switch not closed as it
should be
Check oil switch wiring
Turn DIP switch 6 OFF to disable oil
verification