DynaGen
TM
ES52 - EN
User Manual
7
9M02-9253-A001-EN
Revision A
3
Wiring Installation Guidelines
WARNING
THE CONTROLLER DOES NOT GENERATE A WARNING PRIOR TO
AUTOMATIC
ENGINE
START. DO NOT WORK ON THE ENGINE WHILE POWER IS APPLIED TO THE UNIT. IT IS
HIGHLY RECOMMENDED THAT WARNING SIGNS BE PLACED ON THE ENGINE EQUIPMENT
INDICATING THE ABOVE.
Following these instructions will help avoid common installation problems during wiring and setup:
•
Battery must be disconnected before any wiring connections are made
•
Wire length from the engine to the controller should not exceed 6 m (20 ft)
3.1 Wire Sizing
Wiring size and type should be as specified below.
Use stranded wire
,
since solid wire tends to crack, break
and loosen over time.
Terminal
Wire Size
Current (max)
Function
CON 1
18
100 mA
Speed signal connection via onboard connector
1
18
100 mA
LED Test Switch
2
18
7 mA
Oil Pressure Switch
3
18
7 mA
High Temperature Switch
4
18
7 mA
Auxiliary Input Switch
5
14
10 A
Starter Solenoid/Pilot Relay
6
12
20 A
Battery Negative (-)
7
12
20 A
Auto Switch
8
12
20 A
RSC1 (Remote Start Contact Connection)
9
12
20 A
RSC2 (Remote Start Contact Connection)
10
12
20 A
Start/Stop Connection
11
14
10 A
Fuel Solenoid/Pilot Relay
12
18
300 mA
Timer Output
13 to 18
18
300 mA
Annunciation Outputs
19
18
300 mA
Warm up Output
20
18
300 mA
Annunciator Common Ground Only
(DO NOT use this as main ground connection)
!