DynaGen
TM
ES52 - EN
User Manual
10
9M02-9253-A001-EN
Revision A
Terminal #
Description
10
Start/Stop
when +12/24 VDC is applied, the controller is powered and proceeds to start
the engine. The power for the
crank output
and
fuel output
is obtained from this
terminal. If the 20A fuse is blown, then the ES52 will not start.
11
Fuel output
provides
10A
maximum. Fuel output closes to +12/24 VDC when start signal
is actuated, and it opens when either an engine failure is detected or when the stop signal
is applied.
12
Timer output
has one of four possible functions (Glow Plug,
Smart Choke
, Air-Gate or
Slow). This output closes to +12/24 VDC when activated.
13
Low oil pressure output
closes to +12/24 VDC when the engine shuts down due to a
low oil pressure condition. Flashing Low Oil output indicates an Auxiliary Input failure.
14
High temperature output
closes to +12/24 VDC when the engine shuts down due to a
high temperature condition.
15
Over-crank output
closes to+12/24 VDC when the engine shuts down due to an Over-
crank failure.
16
Over-speed output
closes to +12/24 VDC on an Over-speed failure and is open
otherwise. Flashing output indicates Loss of Speed Signal.
17
Engine running output
closes to +12/24 VDC when the engine speed is greater than the
crank disconnect setting, and it opens when the engine stops. Flashing output indicates
Crank Rest period.
18
Engine failure output
activates on any failure (closes to +12/24 VDC when activated).
19
Warm up output
turns on after the controller has been running for
2 minutes
and
10
seconds.
Output turns on immediately if battery voltage is applied to Start/Stop (terminal
10) and the speed is greater than the crank disconnect pot setting when the controller is
not cranking.
Note: Pins 12 to 19
The maximum rating of each output depends on how many outputs are on simultaneously on pins 12
to 19. Do not exceed these values:
1 on = 300 mA, 2 on = 230 mA, 3 on = 160 mA, 4 on = 123 mA, 5 on = 91 mA, 6 on = 80 mA,
7 on = 66 mA, 8 on = 52 mA
Good practice is to use 50% of the maximum rating.
20
Common ground
for annunciation outputs only.
DO NOT USE AS MAIN GROUND TO
CONTROLLER UNIT.