GB - 8

38VYX050/38VYX080 

• When there is a possibility of freezing of drain at the cold district

or a snowfall area, be careful for drainage ability of drain.
The drainage ability increases when a knockout hole on the base
plate is opened. (Open the knockout hole to outside using a
screwdriver, etc.)

Table VII: Piping connection

Capacity rank

Liquid piping

Gas piping

Outer diameter

Thickness

Outer diameter

Thickness

38 VYX 050

ø 6,4

0,8

ø 12,7

0,8

38 VYX 080

ø 9,52

0,8

ø 15,87

1,0

• In case of draining through the drain hose, attach the following

drain nipple and the waterproof rubber cap, and use the drain
hose (Inner diam.: 16mm) sold on the market.
And also seal the screws securely with silicone material, etc. so
that water does not drop down. Some conditions may cause
dewing or dripping of water.

 Drain nipple

Table VI: Optional Installation Parts

(local procure)

CAUTION:
IMPORTANT FOR POINTS BELOW FOR PIPING WORK

1. Keep dust and moisture away from inside the connecting

pipes.

2. Tightly connect the connection between pipes and the unit.
3. Evacuate the air in the connecting pipes using VACUUM

PUMP.

4. Check gas leak at connected points.

 

Installation

 Waterproof rubber cap

Knockout hole

Waterproof rubber cap

Drain nipple

Open

38 VYX 080

Parts name

Q’ty

Refrigerant piping

A

Liquid side: ø 6,35 mm o ø 9,52 mm

Each one

Gas side: ø 12,7 mm o ø 15,9 mm

B

Pipe insulating material

1

(polyethylene foam, 6 mm thick)

C

Putty, PVC tapes

Each one

A

 

Waterproof rubber
cap

Base plate

Drain nipple

38 VYX 050

Содержание XPOWER 38VYX050

Страница 1: ...38VYX050 38VYX080 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 INSTALLATION MANUAL...

Страница 2: ...refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top R 410A systems should be...

Страница 3: ...other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may cau...

Страница 4: ...add refrigerant at installation site 1 from 20 m to 30 m 38VYX 050 Add 20 g of refrigerant for every meter of pipe beyond 20 m 2 from 20 m to 50 m 38VYX 080 Add 40 g of refrigerant for every meter of...

Страница 5: ...round the outdoor unit A place where the operation noise and discharged air are not given to your neighbors A place that is not exposed to a strong wind A place that does not block a passage When the...

Страница 6: ...your fingers Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure As shown in the figure use two spanners to unscrew or tighten the valve flare nut at gas side If u...

Страница 7: ...e lower than the height of the outdoor unit The height of the obstacle should be lower than the height of the outdoor unit 150 or more 300 or more 300 or more 300 or more 200 or more 150 or more 500 o...

Страница 8: ...or more Open the upper side and both right and left sides The height of obstacle at both front and rear side should be lower than the height of the outdoor unit Serial installation at front and rear...

Страница 9: ...nd also seal the screws securely with silicone material etc so that water does not drop down Some conditions may cause dewing or dripping of water Drain nipple Table VI Optional Installation Parts loc...

Страница 10: ...ed valve Gas side a little to check the air passes through 2 Tighten the flare nut again Execute vacuuming until the compound pressure gauge indicates 101kPa 76cmHg 1 Close handle Low completely Turn...

Страница 11: ...g disconnect electrical connections before refrigerant connections IMPORTANT Make ground connection prior to any other electrical connections Power cable and connecting cable The installation fuse 25A...

Страница 12: ...ashing Discharge temp error hot gas is too high Off EEPROM error On Communication error between IPDU No abnormal stop G Tr short circuit protection Detect circuit error Current sensor error Comp lock...

Страница 13: ...other refrigerant from being charged each port diameter is changed In order to increase pressure resisting strength Charge hose x hose materials and port size are changed to 1 2 UNF 20 threads per in...

Страница 14: ...050 080 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2003 Supersedes July 2003 Printed in J...

Отзывы: