Evacuating

- This air conditioner can be installed up to the connecting pipe length and height difference in the following table.

Air Purge

With respect to the preservation of terrestrial environment, adopt
“Vacuum pump” for air purge (Evacuate air in the connecting pipes)
when installing the unit.

• Do not discharge the refrigerant gas to the atmosphere to

preserve the terrestrial environment.

• Use a vacuum pump to discharge the air (nitrogen, etc.) remained

in the set. If the air remains, the capacity may decrease.

For the vacuum pump, be sure to use one with backflow preventer
so that the oil in the pump does not backflow into the pipe of the air
conditioner when the pump stops.
(If oil in the vacuum pump is put in an air conditioner including
R410A, it may cause trouble on the refrigeration cycle.)

Table VIII: Air Purge

Capacity rank

Max. connecting

Height difference (m)

Hexagonal

pipe length (m)

  Outdoor unit higher than indoor unit   Outdoor unit lower than indoor unit

w

rench size

38 VYX 050

30

30

15

4 mm

38 VYX 080

50

30

15

Vacuum pump

• As shown in the right figure, connect the charge hose after the

manifold valves are closed completely.

• Attach the connecting port of the charge hose with a projection to

push the valve core (setting pin) to the charge port of the set.

• Open handle Low fully.
• Turn ON the vacuum pump.

(*1)

• Loosen the flare nut of the packed valve (Gas side) a little to

check the air passes through.

(*2)

• Tighten the flare nut again.
• Execute vacuuming until the compound pressure gauge indicates

–101kPa (–76cmHg). 

(*1)

• Close handle Low completely.
• Turn OFF the vacuum pump.
• Leave the vacuum pump as it is for 1 or 2 minutes, and check the

indicator of the compound pressure gauge does not return.

• Open fully the valve stem or the valve handle. (First, at liquid side,

then gas side)

• Disconnect the charge hose from the charge port.
• Tighten valve and caps of the charge port surely.

*1. Use the vacuum pump, vacuum pump adapters, and gauge manifold referring to the manuals attached to each tool before using them. For the vacuum

pump, check oil is filled up to the specified line of the oil gauge.

*2. While the air is purged, check again that the connecting port of charge hose, which has a projection to push the valve core, is firmly connected to the

charge port.

 Compound pressure gauge

 Pressure gauge

 Manifold valve

 Handle Hi (Keep fully closed)

 

Charge hose (For R410A only)

 Vacuum pump adapter for counter-flow prevention

(For R410A only)

 

Charge hose (For R410A only)

 

Close

38VYX050

38VYX080

Open

Handle position

 

 Packed valve (Gas side)

 

Vacuum pump

 

Service port (Valve core (Setting pin))

 

Handle Lo

 

-101kPa (-76cmHg)

 

Valve unit

 

Flare nut

 

Stopper

 

Charge cap

 

Valve rod

 

Charge port

 

Push in handle.

Handle

Pull out the handle and using cutting
pliers, etc. turn it counterclockwise
by 90˚. (Open fully)

 

Flexible charge pipe

(only for R410A)

Vacuum pump adapter for

counter-flow prevention

(only for R410A)

Flexible charge pipe

(only for R410A)

A

opened

fully

closed

completely

Содержание XPOWER 38VYX050

Страница 1: ...38VYX050 38VYX080 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 INSTALLATION MANUAL...

Страница 2: ...refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top R 410A systems should be...

Страница 3: ...other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may cau...

Страница 4: ...add refrigerant at installation site 1 from 20 m to 30 m 38VYX 050 Add 20 g of refrigerant for every meter of pipe beyond 20 m 2 from 20 m to 50 m 38VYX 080 Add 40 g of refrigerant for every meter of...

Страница 5: ...round the outdoor unit A place where the operation noise and discharged air are not given to your neighbors A place that is not exposed to a strong wind A place that does not block a passage When the...

Страница 6: ...your fingers Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure As shown in the figure use two spanners to unscrew or tighten the valve flare nut at gas side If u...

Страница 7: ...e lower than the height of the outdoor unit The height of the obstacle should be lower than the height of the outdoor unit 150 or more 300 or more 300 or more 300 or more 200 or more 150 or more 500 o...

Страница 8: ...or more Open the upper side and both right and left sides The height of obstacle at both front and rear side should be lower than the height of the outdoor unit Serial installation at front and rear...

Страница 9: ...nd also seal the screws securely with silicone material etc so that water does not drop down Some conditions may cause dewing or dripping of water Drain nipple Table VI Optional Installation Parts loc...

Страница 10: ...ed valve Gas side a little to check the air passes through 2 Tighten the flare nut again Execute vacuuming until the compound pressure gauge indicates 101kPa 76cmHg 1 Close handle Low completely Turn...

Страница 11: ...g disconnect electrical connections before refrigerant connections IMPORTANT Make ground connection prior to any other electrical connections Power cable and connecting cable The installation fuse 25A...

Страница 12: ...ashing Discharge temp error hot gas is too high Off EEPROM error On Communication error between IPDU No abnormal stop G Tr short circuit protection Detect circuit error Current sensor error Comp lock...

Страница 13: ...other refrigerant from being charged each port diameter is changed In order to increase pressure resisting strength Charge hose x hose materials and port size are changed to 1 2 UNF 20 threads per in...

Страница 14: ...050 080 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2003 Supersedes July 2003 Printed in J...

Отзывы: