38VYX050/38VYX080 

GB - 10

All field electrical connections are the responsibility of the
installer.

WARNING:
• Wrong wiring may cause a burn-out to some electrical parts.
• Be sure to use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator

of power and inter-connecting cables when peeling them.

• Be sure to comply with local regulations of the cable from outdoor

unit to indoor unit.
(wire size and cabling method etc.)

• Use the power and Inter-connecting cables with specified

thickness, specified type and protective devices required.

38VYX050
How to remove the cover

1. Remove  screws of the valve cover.
2. Pull the valve cover downward to remove it.

1. Connect the connecting cable to the terminal as identified with

their respective numbers on the terminal block of indoor and
outdoor unit.

Evacuating

• Open the valve stem or the handle until it strikes the stopper.

It is unnecessary to apply further force.

• Securely tighten the cap with a torque wrench.

• Cap tightening torque

ø 6,35

14 a 18 N•m (1,4 a 1,8 kgf•m)

Valve

ø 9,52

33 a 42 N•m (3,3 a 4,2 kgf•m)

size

ø 12,70

33 a 42 N•m (3,3 a 4,2 kgf•m)

ø 15,87

20 a 25 N•m (2,0 a 2,5 kgf•m)

Service connection

14 a 18 N•m (1,4 a 1,8 kgf•m)

Electrical connections

• Make refrigerant connections before electrical

connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.

IMPORTANT:
Make ground connection prior to any other electrical
connections.

Power cable and connecting cable

• The installation fuse (25A D type 

) must be used for the

power supply line of this air conditioner.

• Incorrect/incomplete wiring might cause an electrical fire or

smoke.

• Prepare the exclusive power supply for the air conditioner.

•  Ensure that mains supply connection is made through a switch

that disconnects all poles, with contact gap of a least 3 mm.

• The indoor - outdoor unit interconnecting wires must be A07 RN-F

type (245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.

• The mains supply connecting cable for 38VYX units, must be H07

RN-F type (245 IEC 57) or higher, with synthetic rubber insulation
with Neoprene coating, according to EN 60335-2-40 codes.
Refer to the indoor unit installation manual for sizing of the
power supply wires.

2. For inter connecting cable, do not use a wire jointed to another

on the way.
Use wires long enough to cover the entire length.

Connecting
cable

Power cable

Ground
connector

(mm)

10

30

1 2 3

10

10

L N

30

40

Valve handling precautions

Connecting

cable

Power cable

1 2 3 L N

Terminal block

 Piping cover

 Cord clamp

 Indoor/outdoor

connecting cables

 Power cable

 

Valve cover

 Model

38VYX050

38VYX080

Power supply

220

÷

240 V

Single phase

 50 Hz

Maximum running current

12 A

15A

Installation

25 A (type D 

)

fuse rating

Power cable

H07 RN-F (245 IEC 57)

2,5 mm

2

Содержание XPOWER 38VYX050

Страница 1: ...38VYX050 38VYX080 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 INSTALLATION MANUAL...

Страница 2: ...refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top R 410A systems should be...

Страница 3: ...other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may cau...

Страница 4: ...add refrigerant at installation site 1 from 20 m to 30 m 38VYX 050 Add 20 g of refrigerant for every meter of pipe beyond 20 m 2 from 20 m to 50 m 38VYX 080 Add 40 g of refrigerant for every meter of...

Страница 5: ...round the outdoor unit A place where the operation noise and discharged air are not given to your neighbors A place that is not exposed to a strong wind A place that does not block a passage When the...

Страница 6: ...your fingers Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure As shown in the figure use two spanners to unscrew or tighten the valve flare nut at gas side If u...

Страница 7: ...e lower than the height of the outdoor unit The height of the obstacle should be lower than the height of the outdoor unit 150 or more 300 or more 300 or more 300 or more 200 or more 150 or more 500 o...

Страница 8: ...or more Open the upper side and both right and left sides The height of obstacle at both front and rear side should be lower than the height of the outdoor unit Serial installation at front and rear...

Страница 9: ...nd also seal the screws securely with silicone material etc so that water does not drop down Some conditions may cause dewing or dripping of water Drain nipple Table VI Optional Installation Parts loc...

Страница 10: ...ed valve Gas side a little to check the air passes through 2 Tighten the flare nut again Execute vacuuming until the compound pressure gauge indicates 101kPa 76cmHg 1 Close handle Low completely Turn...

Страница 11: ...g disconnect electrical connections before refrigerant connections IMPORTANT Make ground connection prior to any other electrical connections Power cable and connecting cable The installation fuse 25A...

Страница 12: ...ashing Discharge temp error hot gas is too high Off EEPROM error On Communication error between IPDU No abnormal stop G Tr short circuit protection Detect circuit error Current sensor error Comp lock...

Страница 13: ...other refrigerant from being charged each port diameter is changed In order to increase pressure resisting strength Charge hose x hose materials and port size are changed to 1 2 UNF 20 threads per in...

Страница 14: ...050 080 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2003 Supersedes July 2003 Printed in J...

Отзывы: