
43
MINIMUM HEATING ENTERING AIR TEMPERATURE
When operating on first stage heating, the minimum temperature
of air entering the dimpled heat exchanger is 50°F (10°C) con-
tinuous and 45°F (7°C) intermittent for standard heat exchangers
and 40°F (4°C) continuous and 35°F (2°C) intermittent for stain-
less steel heat exchangers. To operate at lower return or mixed
air temperatures, a field-supplied outdoor-air thermostat must be
used to initiate both stages of heat when the temperature is below
the minimum required temperature to ensure full fire operation.
Wire the outdoor-air thermostat (OALT) (part no. HH22AG106)
in series with the second stage gas valve. See Fig. 53. Set the
outdoor-air thermostat at 35°F (2°C) for stainless steel heat ex-
changers or 45°F (7°C) for standard heat exchangers. This tem-
perature setting will bring on the second stage of heat whenever
the ambient temperature is below the thermostat setpoint. Indoor
comfort can be compromised when heating is initiated using low
entering air temperatures with insufficient heating temperature
rise.
Fig. 53 — OATL Connections
TROUBLESHOOTING HEATING SYSTEM
Refer to Tables 18 and 19 for additional troubleshooting topics.
CTB
Thermo
s
t
a
t
TH1
TH2
W1
W1
OALT
Table 18 — Heating Service Troubleshooting
PROBLEM
CAUSE
REMEDY
Burners will
not ignite
Misaligned spark electrodes.
Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners.
Check gas line for air, purge as necessary. After purging gas line of air, allow
gas to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
Water in gas line.
Drain water and install drip leg to trap water.
No power to furnace.
Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.
Check transformer. Transformers with internal overcurrent protection require a
cool down period before resetting.
Miswired or loose connections.
Check all wiring and wire nut connections.
Burned-out heat anticipator in thermostat. Replace thermostat.
Broken thermostat wires.
Run continuity check. Replace wires, if necessary.
Inadequate heating
Dirty air filter.
Clean or replace filter as necessary.
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input. If too low, increase
manifold pressure, or replace with correct orifices.
Unit undersized for application.
Replace with proper unit or add additional unit.
Restricted airflow.
Clean filter, replace filter, or remove any restrictions.
Blower speed too low.
Use high speed tap, increase fan speed, or install optional blower, as suitable
for individual units.
Limit switch cycles main burners.
Check rotation of blower, thermostat heat anticipator settings, and temperature
rise of unit. Adjust as needed.
Too much outdoor air.
Adjust minimum position.
Check economizer operation.
Poor Flame
Characteristics.
Incomplete combustion (lack of
combustion air) results in: Aldehyde odors,
CO, sooting flame, or floating flame.
Check all screws around flue outlets and burner compartment. Tighten as
necessary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners Will Not
Turn Off.
Unit is locked into Heating mode for a one
minute minimum.
Wait until mandatory one-minute time period has elapsed or reset power to
unit.
Содержание WeatherMaster Puron 48HC D17
Страница 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Страница 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Страница 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Страница 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Страница 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Страница 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Страница 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Страница 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Страница 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Страница 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Страница 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Страница 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Страница 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Страница 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Страница 97: ......