
10
9. Interior and exterior finned areas must be thoroughly
cleaned.
10. Finned surfaces should remain wet with cleaning solution
for 10 minutes.
11. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10 minute saturation
is achieved.
12. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray noz-
zle. Protect fins from damage from the spray nozzle.
Evaporator Coil Metering Devices
The metering devices are multiple fixed-bore devices (Acu-
trol™) sweated into the horizontal outlet tubes from the liquid
header, located at the entrance to each evaporator coil circuit
path. The metering devices are non-adjustable. Service re-
quires replacing the entire liquid header assembly.
To check for possible blockage of one or more of these meter-
ing devices, disconnect the supply fan contactor (IFC) coil,
then start the compressor and observe the frosting pattern on
the face of the evaporator coil.
A frost pattern should develop uniformly across the face of the
coil starting at each horizontal header tube. Failure to develop
frost at an outlet tube can indicate a plugged or a missing orifice.
Refrigerant System Pressure Access Ports
There are two access ports in the system - on the suction tube
near the compressor and on the discharge tube near the com-
pressor. These are brass fittings with black plastic caps. The
hose connection fittings are standard
1
/
4
-in. SAE male flare
couplings.
The brass fittings are two-piece High Flow valves, with a re-
ceptacle base brazed to the tubing and an integral spring-closed
check valve core screwed into the base. See Fig. 14. This
schrader valve is permanently assembled into the core body
and cannot be serviced separately; replace the entire core body
if necessary. Service tools are available from RCD (P920-
0010) that allow the replacement of the schrader valve core
without having to recover the entire system refrigerant charge.
Apply compressor refrigerant oil to the schrader valve core’s
bottom O-ring. Install the fitting body with 96 ± 10 in.-lb
(10.85 ± 1.13Nm) of torque; do not over-tighten.
NOTE: The High Flow valve has a black plastic cap with a rubber
o-ring located inside the cap. This rubber o-ring must be in place
in the cap to prevent refrigerant leaks.
EXAMPLE:
Model 48HC*D28
Circuit A (from Fig. 15):
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . 85°F (29°C)
Suction Pressure. . . . . . . . . . . . . . . . . . . . . .125 psig (860 kPa)
Suction Temperature should be . . . . . . . . . . . . . . . 63°F (17°C)
Circuit B (from Fig. 15):
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . 85°F (29°C)
Suction Pressure. . . . . . . . . . . . . . . . . . . . . .120 psig (830 kPa)
Suction Temperature should be . . . . . . . . . . . . . . . 58°F (14°C)
Fig. 14 — CoreMax
1
Access Port Assembly
1. CoreMax is a registered trademark of Fastest, Inc.
5/
8
” HEX
0.47
3
0°
0.596
1/2-20 UNF RH
1/2
” HEX
45°
WA
S
HER
O-RING
7/16-20 UNF RH
DEPRE
SS
OR PER AHRI 720
+.01/-.0
3
5
FROM FACE OF BODY
Thi
s
su
rf
a
ce provide
s
a
met
a
l to met
a
l
s
e
a
l when
torq
u
ed into the
s
e
a
t. Appropri
a
te h
a
ndling i
s
req
u
ired to not
s
cr
a
tch or dent the
su
rf
a
ce.
S
EAT
CORE
(P
a
rt No. EC
3
9EZ067)
Содержание WeatherMaster Puron 48HC D17
Страница 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Страница 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Страница 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Страница 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Страница 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Страница 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Страница 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Страница 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Страница 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Страница 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Страница 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Страница 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Страница 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Страница 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Страница 97: ......