
30
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Locations
Supply Air —
The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 46. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift--off filter panel.
SMOKE DETECTOR
SENSOR
C08245
Fig. 46 -- Typical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer —
The sampling tube is
located across the return air opening on the unit base pan.
See Fig. 47. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected by tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation.)
*RA detector must be moved from shipping
position to operating position by installer
RETURN AIR DETECTOR
SAMPLING TUBE
RETURN AIR
DETECTOR MODULE
(Shipping position
shown)*
CONTROLLER
MODULE
C07307
Fig. 47 -- Typical Return Air Detector Location
Return Air with Economizer —
The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit base pan. See Fig. 48. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat--mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor” for installation
steps.)
Return Air
Sampling Tube
C08129
Fig. 48 -- Return Air Sampling Tube Location
Содержание WeatherMaster 50HCQA04
Страница 16: ...16 C160018 Fig 21 Cooling Charging Charts 50HCQA06 C160019 Fig 22 Cooling Charging Charts 50HCQA07 ...
Страница 17: ...17 C160020 Fig 23 Cooling Charging Charts 50HCQD08 C160021 Fig 24 Cooling Charging Charts 50HCQD09 ...
Страница 38: ...38 C10818 Fig 56 RTU OPEN Control Module ...
Страница 78: ...78 APPENDIX V WIRING DIAGRAMS C150427 Fig 58 50HCQA04 A05 Control Wiring Diagram 575 3 60 ...
Страница 80: ...80 APPENDIX V WIRING DIAGRAMS C160013 Fig 60 50HCQ 06 Control Wiring Diagram 575 3 60 ...
Страница 84: ...84 APPENDIX V WIRING DIAGRAMS C150243 Fig 64 50HCQ 04 05 06 Power Wiring Diagram 208 230 1 60 ...
Страница 85: ...85 APPENDIX V WIRING DIAGRAMS C12347 Fig 65 50HCQ 04 05 06 Power Wiring Diagram 208 230 3 60 ...
Страница 86: ...86 APPENDIX V WIRING DIAGRAMS C12353 Fig 66 50HCQ 04 05 06 Power Wiring Diagram 460 3 60 ...
Страница 87: ...87 APPENDIX V WIRING DIAGRAMS C12354 Fig 67 50HCQ 04 05 06 Power Wiring Diagram 575 3 60 ...
Страница 88: ...88 APPENDIX V WIRING DIAGRAMS C160015 Fig 68 50HCQ 07 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 89: ...89 APPENDIX V WIRING DIAGRAMS C12348 Fig 69 50HCQ 09 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 90: ...90 APPENDIX V WIRING DIAGRAMS C12349 Fig 70 50HCQ 12 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 91: ...91 APPENDIX V WIRING DIAGRAMS C12356 Fig 71 50HCQ 12 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 92: ...92 APPENDIX V WIRING DIAGRAMS C150432 Fig 72 50HCQ PremierLink Control Diagram ...
Страница 93: ...93 APPENDIX V WIRING DIAGRAMS C12359 Fig 73 50HCQ RTU Open Control Diagram ...