27
Table 10 – Heater Model Number
Bare Heater Model Number
C
R
H
E
A
T
E
R
0
0
1
A
0
0
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
C
R
H
E
A
T
E
R
1
0
1
A
0
0
Single Point Boxes and Supplementary Fuses —
When
the unit MOCP device value exceeds 60A, unit--mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 38.
ALLIEDPA
MO
DELNO.
ERI
ALNO.
CO
RP.
11
13
21
23
OD
22.2
3
1
23
ISTED
AIR
NDITIONING
UIP
ACCESS
346N.
P/ N
2--5610
--4 REV
111
3
212
3
SINGLE
POINT
BOX
HINGED
COVER
FIELD POWER
CONNECTIONS
C11490
Fig. 38 -- Typical Single Point Installation
On 50HCQ units, all fuses are 60A. Single point boxes
containing fuses for 208/230V applications use UL Class
RK5 250V fuses (Bussmann FRNR 60 or Shawmut TR
60R). Single point boxes for 460V and 575V applications
use UL Class T 600V fuses (Bussmann JJS 60 or
Shawmut A6T 60). (Note that all heaters are qualified for
use with a 60A fuse, regardless of actual heater ampacity,
so only 60A fuses are necessary.)
On 07 -- 09 size units, unit heater applications not
requiring supplemental fuses require a special Single
Point Box without any fuses. Connect power supply
conductors to heater conductors and field--supplied base
unit power tap leads (see text below re: “Completing
Heater Installation”) inside the empty Single Point Box
using UL--approved connectors.
Safety Devices —
Electric heater applications use a
combination of line--break/auto--reset limit switches and a
pilot--circuit/manual reset limit switch to protect the unit
against over--temperature situations.
Line--break/auto--reset limit switches are mounted on the
base plate of each heater module. See Fig. 39. These are
accessed through the indoor access panel. Remove the
switch by removing two screws into the base plate and
extracting the existing switch.
Pilot--circuit/manual reset limit switch is located in the
side plate of the indoor (supply) fan housing. See Fig. 36
and Fig 39.
Completing Heater Installation
Field Power Connections —
Tap conductors must be
installed between the base unit’s field power connection
lugs and the Single Point Box (with or without fuses). See
Fig. 38. Refer to unit wiring schematic. Use copper wire
only. For connection using the single point box without
fuses, connect the field power supply conductors to the
heater power leads and the field--supplied tap conductors
inside the Single Point Box. Use UL approved pressure
connectors (field--supplied) for these splice joints.
ALLIEDPA
MODELNO.
ERIALNO.
CO
RP.
11
13
21
23
OD
22.2
3
1
23
ISTED
AIR
NDITIONING
UIP
ACCESS
346N.
P/ N2-- 5610
--4 REV
PILOT---CIRCUIT/MANUAL
RESET LIMIT SWITCH
LINE---BREAK
LIMIT SWITCHES
C11489
Fig. 39 -- Typical Location of Heater Limit Switches
(3--phase heater shown)
Содержание WeatherMaster 50HCQA04
Страница 16: ...16 C160018 Fig 21 Cooling Charging Charts 50HCQA06 C160019 Fig 22 Cooling Charging Charts 50HCQA07 ...
Страница 17: ...17 C160020 Fig 23 Cooling Charging Charts 50HCQD08 C160021 Fig 24 Cooling Charging Charts 50HCQD09 ...
Страница 38: ...38 C10818 Fig 56 RTU OPEN Control Module ...
Страница 78: ...78 APPENDIX V WIRING DIAGRAMS C150427 Fig 58 50HCQA04 A05 Control Wiring Diagram 575 3 60 ...
Страница 80: ...80 APPENDIX V WIRING DIAGRAMS C160013 Fig 60 50HCQ 06 Control Wiring Diagram 575 3 60 ...
Страница 84: ...84 APPENDIX V WIRING DIAGRAMS C150243 Fig 64 50HCQ 04 05 06 Power Wiring Diagram 208 230 1 60 ...
Страница 85: ...85 APPENDIX V WIRING DIAGRAMS C12347 Fig 65 50HCQ 04 05 06 Power Wiring Diagram 208 230 3 60 ...
Страница 86: ...86 APPENDIX V WIRING DIAGRAMS C12353 Fig 66 50HCQ 04 05 06 Power Wiring Diagram 460 3 60 ...
Страница 87: ...87 APPENDIX V WIRING DIAGRAMS C12354 Fig 67 50HCQ 04 05 06 Power Wiring Diagram 575 3 60 ...
Страница 88: ...88 APPENDIX V WIRING DIAGRAMS C160015 Fig 68 50HCQ 07 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 89: ...89 APPENDIX V WIRING DIAGRAMS C12348 Fig 69 50HCQ 09 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 90: ...90 APPENDIX V WIRING DIAGRAMS C12349 Fig 70 50HCQ 12 Power Wiring Diagram 208 230 3 60 460 3 60 575 3 60 ...
Страница 91: ...91 APPENDIX V WIRING DIAGRAMS C12356 Fig 71 50HCQ 12 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 92: ...92 APPENDIX V WIRING DIAGRAMS C150432 Fig 72 50HCQ PremierLink Control Diagram ...
Страница 93: ...93 APPENDIX V WIRING DIAGRAMS C12359 Fig 73 50HCQ RTU Open Control Diagram ...