Appendix A: VVT Zone II Points/Properties
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
82
ZS Zone CO2
- Configure additional ZS CO
2
sensors used on the VVT Zone II.
•
Use
- Check to include ZS sensors' value in the
Combined Algorithm
(
Maximum
is
the default).
•
Raw Value
-Displays sensed CO
2
for each ZS CO
2
sensor's address
•
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS sensor's sensed value.
•
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
ZS CO
2
to calculate
the
Corrected Value
for CO
2
control.
D:
(Index) Area
- (1) Main ZS
Sensor
Use -
unchecked
Calibration
- 0
Combination Algorithm
-
Maximum
Input Smoothing
-
Medium
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- 10
WS Battery Strength % —
Displays charge strength indicated on the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
R:
_%
WS Signal Strength % —
Displays radio signal strength of the wireless space temperature
sensor. If there are multiple wireless sensors, it displays the lowest value.
R:
_%
Rnet Sensed Occupancy
– Displays occupancy status detected by wireless infrared
motion sensor.
R:
Off/On
ZS model to show on graphic –
Select the ZS model, from the drop-down list, that you
want to display on the graphic.
D:
R:
ZS Pro model
None
ZS Pro model
ZS Base model
ZS Plus model
WS model to show on graphic –
Select the wireless model, from the drop-down list, that
you want to display on the graphic.
D:
R:
WS Plus model
WS Base model
WS Plus model
WS Pro model
Net Space Temp to show on graphic —
Select the type of sensor to display on graphic.
D:
R:
Equipment Touch
Network Temp
Equipment Touch
System Space Temperature
– The current value of the controlling space temperature
received over the network from another source. -999 indicates no value has been
received and it will not be used.
R:
-50 to 150°F
(-45.5 to 65.5°C)
System Setpoint Adjustment
– The space temperature setpoint adjustment value
received over the network.
R:
-5 to 5 °F
(-2.7 to 2.7 °C)