Appendix A: VVT Zone II Points/Properties
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
79
Point Name/Description
Default/Range
Direction Clockwise
– If
Damper Actuator
is set to
Built-in actuator
, set this field
to the damper's position when it rotates clockwise.
D:
R:
Close
Close/Open
Target Damper Position
- The current damper position. To override normal
control for troubleshooting purposes, select
Lock value to
and then enter a value.
The damper moves to that position until
Lock value to
checkbox is cleared.
R: 0 to 100%
Auxheat
- The current configured
Reheat Min Damper Position
. To override
normal control for reheat troubleshooting purposes, select
Lock value to
and then
enter a value. The damper moves to that position until
Lock value to
checkbox is
cleared.
R: 0 to 100%
Fan
– The current value of the fan output relay. To override normal control for
troubleshooting purposes, select
Lock value to
and then enter
On
or
Off
. The relay
stays in that state until the
Lock value to
checkbox is cleared.
R: On/Off
Cooling Min Damper Position
– The minimum damper position the terminal
controls to when the air source mode is Cooling, Vent, or Free Cooling and the
space requirements for cooling are at a minimum. We recommend that you set
this no lower than 10%.
D:
R:
20%
0 to 100%
Cooling Max Damper Position
– The maximum damper position the terminal
controls to when the air source mode is Cooling, Vent, or Free Cooling and the
space requirements for cooling are at a maximum.
D:
R:
100%
0 to 100%
Reheat Min Damper Position
– For Single Duct units with ducted reheat. Set to
the desired damper position at which the reheat will provide optimum
performance. This value is compared to the
Cooling Min Damper Position
value,
and the greater of the two values determines the damper position.
D:
R:
45%
0 to 100%
Heating Min Damper Position
– The minimum damper position the terminal
controls to when the air source mode is Heat and the space requirements are at a
minimum.
D:
R:
20%
0 to 100%
Heating Max Damper Position
– The maximum damper position the terminal
controls to when the air source mode is Heat and the space requirements are at a
maximum.
D:
R:
20%
0 to 100%
Vent Position
– The ventilation damper position the terminal controls to when the
air source mode is Vent and the terminal mode is not in the Heat or Cool mode. If
Linkage is not active, the zone determines vent mode by verifying that its SAT
sensor is between 65°F (18.3°C) and 80°F (26.6°C).
D:
R:
50%
0 to 100%