Appendix A: VVT Zone II Points/Properties
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
80
Point Name/Description
Default/Range
Test and Balance
– Use the following command buttons when commissioning a zone,
balancing the system
(page
42), replacing the zone controller, or troubleshooting. If
Automatic Control
is not selected within 4 hours, the
controller will resume normal control.
Calibrated Damper Close
– Forces the damper closed so the 0% damper position can be set.
Calibrated Damper Open
– Forces the damper to its maximum open position so that the 100% damper position can
be set.
Cool Max
– Forces the damper to its cool maximum position regardless of its current local mode.
Cool Min
– Forces the damper to its cool minimum position regardless of its current local mode.
Automatic Control
– Returns the damper to its normal control routines.
This must be activated when you finish
using any of the other Test and Balance commands.
Damper Full Close
– Overrides the damper to its full closed position.
Heat Max
– Forces the damper to its heat maximum position regardless of its current local mode.
Heat Min
– Forces the damper to its heat minimum position regardless of its current local mode.
Reheat Min
– Forces the damper to its reheat position regardless of its current local position.
Vent
– Forces the damper to its ventilation position regardless of its current local mode.
Sensor Binder / Zone Temp / Zone Humidity / ZS Zone CO2
Ctrl+click
on the name of these properties to access the microblock popup
Properties
page >
Details
tab. See below for instructions on configuring your ZS or wireless sensors.
See the microblock Help for more detailed explanations.
Sensor Binder
- Use the
Associated Sensors
table to configure the Rnet to use additional
ZS or wireless sensors.
•
Network Type
- Set to
Rnet
•
Address
- Enter the DIP switch settings that are on the additional ZS sensors (up to 5
total) or RnetID assigned to each wireless sensor in SensorBuilder
•
Lock Display
- Check to make the sensor display-only
D:
(Index)
- (1)
Network Type
- Rnet
Address
- 1