To set up the controller through the Comm/Service ports

 

 

 

 
 

TruVu™ VVTBP

-E2 

 

©2022 Carrier. 

Installation and Start-up Guide 

 

All rights reserved. 

 

57 

 

  You can communicate with the TV-VVTBP-E2 through a web browser by connecting a computer to one of the 
Comm/Service USB ports on the controller, using either the Carrier wireless service adapter or a USB cable.  

NOTE

  You cannot access the Service port by plugging an Ethernet cable into Eth0 or Eth1. 

 

Once you are connected to the network, you can:  

 

Access the controller setup pages 

 

Address and configure controllers 

 

View the controller's Module Status report 

 

View/change controller and network settings. Changes take effect immediately. 

 

Troubleshoot 

 

Use BACnet/Service port to access the i-Vu® application or a touchscreen device. See 

To communicate 

through a BACnet/Service port network

 (page 57).  

  

 

 

To access the controller setup pages and use the 

Local Network

 tab, you must first connect to and manually 

address one TV-VVTBP-E2. For instructions on connecting, see 

Addressing the TV-VVTBP-E2 through the 

Comm/Service ports

 (page 15). Navigate to http://local.access or http://169.254.1.1 to access the pages. Then 

set up the address on your selected TV-VVTBP-E2 on the 

Ports

 tab

 (page 58)

 

NOTE

  The first time you access the controller in the i-Vu® interface, after you have changed settings through the 

Service port, be sure to upload the changes to the system database. This will preserve those settings when you 
download memory or parameters to the controller. 

 

 

 

ModStat tab 

This tab provides the controller's Module Status report that gives information about the controller and network 
communication status. See 

Appendix - Module Status field descriptions

 (page 82)

 

 

 

To set up the controller through the Comm/Service ports 

Содержание TruVu VVTBP-E2

Страница 1: ...TruVu VVTBP E2 Installation and Start up Guide 2022 Carrier All rights reserved Catalog No 11 808 875 01 7 22 2022...

Страница 2: ...version of this document from www hvacpartners com the Carrier Partner Community website or your local Carrier office Important changes are listed in Document revision history at the end of this docu...

Страница 3: ...ring inputs and outputs 24 Inputs 24 Outputs 24 Wiring specifications 25 To wire inputs and outputs 25 To adjust input and output properties 28 Input values 29 Output values 30 Resolution values 30 Of...

Страница 4: ...BACnet Service port network 63 Wiring specifications 64 To communicate locally through the Rnet port 65 To set up a Local Access connection in the i Vu interface 66 Troubleshooting 67 LEDs 67 To use t...

Страница 5: ...Document revision history 84...

Страница 6: ......

Страница 7: ...a component of the i Vu Control System maintains supply duct static pressure by regulating airflow and protects the air source from excessive supply air temperature It has a built in static pressure...

Страница 8: ...What is the TV VVTBP E2 TruVu VVTBP E2 2022 Carrier Installation and Start up Guide All rights reserved 2 The following illustration shows the TV VVTBP E2 in a typical i Vu Control System...

Страница 9: ...de All rights reserved 3 You can use the TV VVTBP E2 s physical communication ports as follows Port Port type For routing this type of communication At Eth0 Eth1 10 100 Mbps Ethernet BACnet IP BACnet...

Страница 10: ...driverx Maximum number of control programs 2 NOTE You can run 1 VVT bypass Product Integrated Control PIC and 1 programmable Zone Controller II program OR up to 2 Zone Controller II programs Maximum n...

Страница 11: ...1 A DC supply 15W 0 625A Use an external transformer if your devices exceed the maximum power Comm Service ports USB 2 0 host ports for setting up the controller and troubleshooting through a local c...

Страница 12: ...r details Tricolor Net LED to show network status Tricolor Sys LED to show controller status A Tx Transmit and Rx Receive LED for Port S1 Tx Transmit and Rx Receive activity LED and yellow link status...

Страница 13: ...and light industry environment RoHS Compliant 2015 863 EU REACH Compliant Zone sensors You can wire ZS sensors and or a Wireless Adapter that communicates with wireless sensors to the TV VVTBP E2 s R...

Страница 14: ...s a 24 Vac external power source USB ports You can connect the TruVu ET Display to either of the TV VVTBP E2 s Comm Service ports to view or change the controller s property values schedule equipment...

Страница 15: ...s reserved 9 To install the TV VVTBP E2 1 Mount the controller page 10 2 Wire the controller for power page 13 3 Set the controller s address page 18 page 15 4 Wire the controller to the BACnet IP or...

Страница 16: ...o fully close the damper position Ensure the damper is closed 2 Mount the controller to the bypass duct by sliding the clamp assembly onto the damper shaft 3 Mount and secure an enclosure to cover the...

Страница 17: ...l movement of the damper shaft 5 Hold down the TV VVTBP E2 s actuator release button and rotate the actuator clamp in the same direction that closed the damper Rotate the clamp until it stops then rot...

Страница 18: ...tube provided to either one of the controller s airflow ports Using 1 4 poly tubing connect the other end to a duct static pressure probe for example Dwyer Instruments part A 491 or the equivalent for...

Страница 19: ...a Class 2 power source Take appropriate isolation measures when mounting it in a control panel where non Class 2 circuits are present Carrier controllers can share a power supply as long as you Mainta...

Страница 20: ...rom the power supply s negative terminal to earth ground This wire must not exceed 12 in 30 5 cm 6 Apply power to the power supply 7 Measure the voltage at the red screw terminal connector to verify t...

Страница 21: ...and possibly the computer s USB port will occur if the controller s input power polarity was not maintained and was also not properly grounded floating If you are not sure of the wiring polarity and...

Страница 22: ...elow 2 A new Ethernet connection will appear on your computer 3 If your computer uses a static IP address use the following settings for the new connection Address 169 254 1 x where x is 2 to 7 Subnet...

Страница 23: ...ated on the other side of an IP router Be connected to any third party IP devices NOTE Carefully plan your addressing scheme to avoid duplicating addresses If third party devices are integrated into t...

Страница 24: ...click the Clear All button to erase the Local Devices table if there is information in it 6 Click Discover The table finds and lists the first 256 unconfigured devices on the same subnet The table is...

Страница 25: ...bnet Mask and Default Gateway NOTE The other devices that you configure inherit this device s subnet mask and default gateway 4 On the Local Network tab click the Clear All button to erase any pre exi...

Страница 26: ...worker exactly where he is and then presses the DSC button The second technician who is sitting at a computer connected to the controller watches for the blue dot to show up on the Local Devices tabl...

Страница 27: ...BACnet IP BACnet Ethernet Ethernet 10 or 100 Mbps Port S1 1 BACnet MSTP RS485 9 6 to 115 2 kbps Comm Service USB Port 2 USB 2 0 USB Rnet Port See Wiring devices to the TV VVTBP E2 s Rnet port page 22...

Страница 28: ...rt in a daisy chain configuration ZS sensors Wireless Adapter that communicates with wireless sensors Equipment Touch TruVu ET Display See the device s Installation and Start up Guide for complete wir...

Страница 29: ...as the TV VVTBP E2 controller so that it shares a common earth ground reference thereby reducing the potential for ground loops A remote Act Net power source installed near the Act Net devices should...

Страница 30: ...st input and output properties Outputs Analog outputs Analog outputs can be used for 0 10 Vdc devices Resistance to the ground must be 500 Ohms minimum NOTE The device must share the same ground as th...

Страница 31: ...output wiring consider the following Total loop distance from the controller to the controlled device NOTE Include the total distance of actual wire For 2 conductor wires this is twice the cable leng...

Страница 32: ...1 Verify that the TV VVTBP E2 s power and communications connections work properly 2 Turn off the TV VVTBP E2 s power 3 Connect the input wiring to the screw terminals on the TV VVTBP E2 NOTE Connect...

Страница 33: ...p Guide All rights reserved 27 4 Connect binary and analog output wiring to the screw terminals on the TV VVTBP E2 and to the controlled device 5 Connect the ground wire to the AO outputs terminals 6...

Страница 34: ...1 in the Num field for Heat Stage 1 NOTES Exp expander number is 00 for the inputs and outputs located on the TV VVTBP E2 Do not assign the same output number to more than one point 4 Enter the approp...

Страница 35: ...Dry Contact Dry Contact N A N A Binary Contact Binary Contact N A N A Special BI 4 Binary Special Online flow sensor status N A 1 The sensor reads a value and sends a corresponding signal Volts to the...

Страница 36: ...TV VVTBP E2 to a device For example set Min to 0 and Max to 100 for an Analog Output microblock that receives a 0 to 100 open signal from a PID microblock and that controls a 0 10 Vdc actuator so that...

Страница 37: ...red value Analog Output BAO You can use the Offset value positive or negative to calibrate an output but you generally do not need to If used the driver adds the offset value to the wire input value b...

Страница 38: ...to the controller CAUTION Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring Do not abrade cut or nick the outer jacket of the cable Do not pull or d...

Страница 39: ...actuators to the TV VVTBP E2 s analog output instead of using the controller s 45 in lb 5 Nm actuator NMX24 MFT P 10028 90 in lb 10 Nm actuator with 0 10 Vdc control and 0 10 Vdc feedback AMX24 MFT P...

Страница 40: ...nk actuators whose travel times and other parameters coincide LMX24 MFT P 10028 45 in lb 5 Nm actuator with 0 10 Vdc control NMX24 MFT P 10028 90 in lb 10 Nm actuator with 0 10 Vdc control AMX24 MFT P...

Страница 41: ...ield supplied actuators to the analog output TruVu VVTBP E2 2022 Carrier Installation and Start up Guide All rights reserved 35 NOTE Maintain polarity if using the same power supply for more than one...

Страница 42: ...s are found select one or more routers in the list on the Manage tab and click Upload All Content to upload to the i Vu application Use Ctrl click Shift click or both to select multiple items 4 Click...

Страница 43: ...The combined high and low tubing length should not exceed 16 4 ft 5 meters in order to ensure accurate measurements For a single duct system 1 Turn off the TV VVTBP E2 s power 2 Connect the tubes to t...

Страница 44: ...and Setup Guide for detailed instructions 4 See the System Touch Installation and Setup Guide for detailed instructions CAUTION If multiple controllers share power but polarity was not maintained when...

Страница 45: ...rs click Apply f Enable the air source fan output using one of the following methods Physically connect the air source controller s fan enable wiring at the unit In the i Vu or Field Assistant tree se...

Страница 46: ...o zero the pressure sensor When Done appears click Apply f Enable the air source fan output using one of the following methods Physically connect the air source controller s fan enable wiring at the u...

Страница 47: ...monitoring and limiting To protect the air source from excessive supply air temperature conditions the TV VVTBP E2 monitors the supply air temperature If the temperature reaches either the Minimum Co...

Страница 48: ...controller monitors the static pressure to determine when the equipment fan restarts If it rises above 10 of the nominal pressure setpoint the controller assumes the fan restarted and controls to mai...

Страница 49: ...ding cooling using only the economizer and usually during an unoccupied period The terminal modulates its primary air damper to maintain the midpoint between the configured occupied heating and occupi...

Страница 50: ...nce between the controller s time and the time sync s time is greater than this field s value the controller s time is immediately changed If the difference is less than this field s value the control...

Страница 51: ...e per second For these situations clear this checkbox but make sure that your network can support the increased traffic You will also need to disable the Excessive COV alarms under the driver s Common...

Страница 52: ...onse is received APDU Segment Timeout How many milliseconds the device will wait before resending a message segment if no response is received Number of APDU Retries The number of times the device wil...

Страница 53: ...e that appears in the Recipients table Recipient Type Use Address static binding for either of the following Third party BACnet device recipients that do not support dynamic binding When you want alar...

Страница 54: ...is type from the TV VVTBP E2 Notification Class In a typical i Vu system the Notification Class is 1 however if needed you can associate a different notification class with the alarm See Notification...

Страница 55: ...Whether Port S1 is being used for MS TP and is disabled NOTE The options shown on the page change according to your controller s settings MS TP Configuration on Port S1 Address For Port S1 A unique a...

Страница 56: ...communicate with the Next Default Gateway Address The controller will use the Next setting as soon as the controller can communicate with the Next Default Gateway Address or when the timeout occurs wh...

Страница 57: ...Network Activity tab Eth0 Eth1 Port Statistics BACnet IP Statistics BACnet IP Rx Unicast Packets BACnet IP packets received from a single BACnet device BACnet IP Tx Unicast Packets BACnet IP packets t...

Страница 58: ...le The capture will automatically resume Click on the Start Stop option to end the Continuous capture If the port is set up for MS TP select an option in the Capture section To download the capture fi...

Страница 59: ...device This number is printed on a label on the device Device Status Displays the current status of the device Possible statuses Description Normal Operation Successful communication No Communication...

Страница 60: ...click Accept after every change Unknown Error Firmware or bus error Auto addressed device When a device that does not have an address is found on the bus an unused address in automatically assigned Yo...

Страница 61: ...rough the stand alone Airflow Test and Balance Utility Flow Sensor Input Tubes Not Calibrated Flow reading is being generated from default pressure table Flow sensor always reads absolute Calibrated F...

Страница 62: ...end data to the system database Store Trends Now Writes all trend data in the controller to the system database without having to enable trend historian Write to historian every __ trend samples Write...

Страница 63: ...To communicate through a BACnet Service port network page 57 To access the controller setup pages and use the Local Network tab you must first connect to and manually address one TV VVTBP E2 For instr...

Страница 64: ...efore resending a message if no response is received APDU Segment Timeout How many milliseconds the device will wait before resending a message segment if no response is received APDU Retries The numb...

Страница 65: ...on this controller s network See the number of devices discovered and the total number on the network Identify the i Vu XT or TruVu controller that has had its DSC button pressed Export the Local Dev...

Страница 66: ...ited to 256 devices 4 Click Discover to populate the table with your i Vu XT or TruVu devices that are on a single network communicating with the connected i Vu XT or TruVu controller To auto assign I...

Страница 67: ...correct addresses are shown with SN for subnet and GW for default gateway To resolve a mismatch select the device s by clicking the Select checkbox and then clicking the Resolve button The subnet mask...

Страница 68: ...whenever the actuator moves the LED rotates in the same direction LED rotation is automatically disabled after 1 hour and can be re enabled by pressing the Blink button again NOTES The blue dot appear...

Страница 69: ...ot available you will have to assign a network number and enter it 5 Click Apply 6 On the right of the page in the Networks using selected connection table click the checkbox next to the network you w...

Страница 70: ...elect Module Status If a Modstat report appears the i Vu application is communicating with the controller Wiring specifications For Use Maximum Length Ethernet not daisy chained Cat5e or higher Ethern...

Страница 71: ...etween the controller s ground and the computer s AC power ground could damage the USB Link and the controller If you are not sure of the wiring polarity use a USB isolator between the computer and th...

Страница 72: ...ntrol Panel System Device Manager Ports Com LPT The COM port number is beside Silicon Labs CP210x USB to UART Bridge 6 Set the Baud rate to 115200 7 Click Apply 8 On the right of the page in the Netwo...

Страница 73: ...Red On Ethernet connection problem No Ethernet Link Connect Ethernet Cable Check other network components Red 1 blink One of the following BACnet IP Ethernet DLL reporting issue Unable to create task...

Страница 74: ...Green On All enabled networks are functioning properly No errors No action required Magenta Operating system changes are downloading WARNING This process could take several minutes Do NOT power off th...

Страница 75: ...nutes Do NOT power off the controller during the download N A No action required To use the Locator LED The Locator LED turns on when you power on the controller change the driver Click the Blink butt...

Страница 76: ...BAO with ON pulse 0 5 seconds and OFF pulse 0 5 seconds LED 2 BAO 0 62 Special 0 Normal 15 On The number of blinks equals the Present Value The pulse pattern repeats after a 2 second delay LED will b...

Страница 77: ...take Reliability description Possible error Verify that Configuration Error The microblock s I O Type and Sensor Actuator Type are not compatible The I O Type and Sensor Actuator Type combination is v...

Страница 78: ...ou to get the controller s Device Log containing diagnostic information for troubleshooting 1 Select the TV VVTBP E2 in the i Vu navigation tree 2 On the Properties page click Device Log NOTE You can...

Страница 79: ...n remove the fuse as described below and use a multimeter to check it If the fuse is blown try to determine why it blew before you replace it Check the power wiring polarity of the TV VVTBP E2 and any...

Страница 80: ...to reconfigure all custom settings You must connect locally to the TV VVTBP E2 and manually reconfigure all the communications and firewall information We highly recommend that you revert the defaults...

Страница 81: ...ith this document it may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be req...

Страница 82: ...n R 0 to 100 VFD output If Control Device Type is VFD this is the current VFD speed capacity R 0 to 100 LAT Control The status of LAT Limit duct static pressure override control of the bypass R On Off...

Страница 83: ...rolling setpoint this value the output modulates accordingly CAUTION If this value is too low the damper may oscillate to maintain the static pressure This could cause the actuator to fail prematurely...

Страница 84: ...when you finish using any of the other Test and Balance commands Damper Full Close Overrides the damper to its full closed position Local Sensor Calibration Supply Air Temperature Displays the curren...

Страница 85: ...eld Assistant Properties Control Program Linkage Point Name Description Range Air Linkage Status If Active the controller is part of a linked system If Not Active the controller is operating as a stan...

Страница 86: ...I O Points Point Name Description Range Pressure Input The current duct static pressure of the controller s integrated airflow sensor R 0 to 2 0 in H2O 0 to 498 kPa SAT Sensor The current duct air tem...

Страница 87: ...y R W sec 60 start_delay AV 9007 Pressure Control Deadband R W in H2O 0 05 press_hysteresis AV 3016 Static Pressure Prime Variable R in H2O static_press AV 1016 Supply Air Temperature R F sa_temp AV 1...

Страница 88: ...ersions Reset Counters The number of times each of the following events have occurred since the last time the controller was commanded to clear the reset counters See NOTE below this table Power failu...

Страница 89: ...such as parameters and trend data Volatile partition 6 MB maximum contains data that does not need to be preserved through a power cycle such as status values that are calculated during runtime IP Ne...

Страница 90: ...anged IN 03 to IN 01 C AE BB O CE and UKCA Compliance Updated for next gen X O BH E FCC Compliance 5 3 22 CE and UKCA Compliance Added UKCA Compliance X PM AB R BH Specifications Specifications Change...

Страница 91: ......

Страница 92: ...Carrier 2022 Catalog No 11 808 875 01 7 22 2022...

Отзывы: