What is the TV-VVTBP-E2?
TruVu™ VVTBP
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
7
MTBF @ 77°F (25°C)
184,811 hours
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) and B-BBMD
Standard Device Profiles as defined in ANSI/ASHRAE Standard 135-2012 (BACnet)
Annex L, Protocol Revision 14
Compliance
United States of America:
FCC CFR47, Part 15, Subpart B, Class B
Canada:
Industry Canada Compliant, ICES-003, Class B
Contains IC ID: 6713A-STM300U
Europe:
Mark, UK:
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
RoHS Compliant: 2015/863/EU
REACH Compliant
Zone sensors
You can wire ZS sensors and/or a Wireless Adapter that communicates with wireless sensors to the TV-VVTBP-E2's
Rnet port. You can have up to 10 ZS and/or wireless sensors.
NOTES
•
A control program can use no more than 5 ZS sensors, so you must use multiple control programs if your
Rnet network has more than 5 sensors.
•
ZS and wireless sensors can share the Rnet with an Equip
ment Touch or TruVu™ ET Display.
CAUTION
Rnet power
The Rnet port provides 12 Vdc at up to 260 mA. When determining which devices to put on the Rnet, verify that
the total current draw of the sensors does not exceed the controller's Rnet power. See the sensor's I
nstallation
and Start-up Guide
to determine the power required.