Troubleshooting inputs and outputs
The i-Vu® interface shows if you have I/O errors resulting from a misconfigured microblock.
To check for errors:
1
In the i-Vu® navigation tree, select the equipment controlled by the TV-VVTBP-E2.
2
On the
Properties
page, select the
I/O Points
tab.
3
Click the
Name
of any input or output whose name is red (indicates an error) to open its dialog box.
4
On the
Details
tab, scroll down to see the
Reliability
field under
BACnet Configuration
.
5
Anything other than
No Fault Detected
indicates an error. See the table below to determine the error and
possible actions to take.
Reliability
description
Possible error
Verify that...
Configuration
Error
•
The microblock's
I/O Type
and
Sensor/Actuator Type
are not
compatible.
•
The
I/O Type
and
Sensor/Actuator Type
combination is valid for the I/O number
and microblock type.
•
The output's DIP switch setting does
not match the connected device.
•
The DIP switch setting is appropriate for
the output and microblock type.
•
Invalid expander address or I/O
number.
•
The expander is present and functional at
the address shown in the i-Vu® interface
and that I/O number is valid.
Over Range
•
Input exceeds the
Min/Max
limits.
•
The input is within the
Min/Max
limits.
No Sensor
•
No device is attached to the output.
•
The device is present and functioning.
Shorted Loop
•
Internal voltage feedback does not
correspond with commanded value.
•
The load on the output is within the valid
range.
•
A voltage/current source has not been
connected to an output.