31
No. Code
Alarm description
Reset type
Action taken
Possible cause
12
15018 Circuit A Condenser Subcooling Liquid
Thermistor
Automatic, if thermistor
reading returns to normal
Circuit A shuts down
Defective thermistor
13
15019 Circuit B Condenser Subcooling Liquid
Thermistor
As above
Circuit B shuts down
As above
14
15021 Space Temperature Thermistor
As above
Alert
As above
15
15024 Circuit A Economizer Gas Thermistor
As above
Economizer function
disabled
As above
16
15025 Circuit B Economizer Gas Thermistor
As above
As above
As above
17
15026 Circuit C Economizer Gas Thermistor
Not applicable to this unit
Transducer failures
18
12001 Circuit A Discharge Transducer
Automatic, if sensor voltage
reading returns to normal
Circuit A shuts down
Defective transducer
19
12002 Circuit B Discharge Transducer
As above
Circuit B shuts down
As above
20
12003 Circuit C Discharge Transducer
Not applicable to this unit
21
12004 Circuit A Suction Transducer
Automatic, if sensor voltage
reading returns to normal
Circuit A shuts down
Defective transducer
22
12005 Circuit B Suction Transducer
As above
Circuit B shuts down
As above
23
12006 Circuit C Suction Transducer
Not applicable to this unit
24
12010 Circuit A Oil Pressure Transducer
Automatic, if sensor voltage
reading returns to normal
Circuit A shuts down
Defective transducer
25
12011 Circuit B Oil Pressure Transducer
As above
Circuit B shuts down
As above
26
12012 Circuit C Oil Pressure Transducer
Not applicable to this unit
27
12013 Circuit A Economizer Pressure Transducer Automatic, if sensor voltage
reading returns to normal
Circuit A shuts down
Defective transducer
28
12014 Circuit B Economizer Pressure Transducer As above
Circuit B shuts down
As above
29
12015 Circuit C Economizer Pressure Transducer Not applicable to this unit
Communication failures
30
4101
Loss of communication with Compressor
Board A
Automatic, if communication
is re-established
Unit shuts down
Bus installation fault,
communication error
31
4201
Loss of communication with Compressor
Board B
As above
Unit shuts down
As above
32
4301
Loss of communication with Compressor
Board C
Not applicable to this unit
33
4901
Loss of communication with SIOB Board A Automatic, if communication
is re-established
Unit shuts down
Bus installation fault,
communication error
34
4902
Loss of communication with SIOB Board B As above
Unit shuts down
As above
35
4903
Loss of communication with SIOB Board C Not applicable to this unit
36
4906
Loss of communication with SIOB Board
EMM
Automatic, if communication
is re-established
Unit shuts down
Bus installation fault,
communication error
37
4907
Loss of communication with SIOB Board
DGT
As above
Unit shuts down
As above
38
4501
Loss of communication with Aux Board
Number 1 (leak detection option board)
As above
Circuit A shuts down OR
circuit B shuts down
As above
Process failures and other
39
10001 Cooler Freeze Protection
Manual
Unit shuts down
No water flow, defective
thermistor
40
10002 Circuit A Condenser Freeze
Automatic (if saturated
discharge temperature is
above 4.4°C) or Manual
Circuit A shuts down, but
the pump is running
Discharge pressure
transducer defective,
refrigerant leak or low
condenser water
temperature
41
10003 Circuit B Condenser Freeze
As above
Circuit B shuts down, but
the pump is running
As above
42
10004 Circuit C Condenser Freeze
Not applicable to this unit
43
10005 Circuit A Low Suction Temperature
Automatic (the first alarm
within 24 hours) or Manual
Circuit A shuts down
Pressure sensor
defective, EXV blocked
or lack of refrigerant
44
10006 Circuit B Low Suction Temperature
As above
Circuit B shuts down
As above
45
10007 Circuit C Low Suction Temperature
Not applicable to this unit