![Carrier Touch Pilot Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/carrier/touch-pilot/touch-pilot_manual_2562438017.webp)
17
Outputs Menu – OUTPUTS
No. Name
Status
Unit
Displayed text*
Description
1
COMP_A
off/on
-
Compressor A
Compressor A status (circuit A)
2
OIL_SL_A
off/on
-
Oil Solenoid Output A
Oil solenoid output, circuit A
3
SLID_1_A
off/on
-
Slide Valve 1 Output A
Slide valve 1 output, circuit A
4
SLID_2_A
off/on
-
Slide Valve 2 Output A
Slide valve 2 output, circuit A
5
CAPT010A
-
V
Capacity Signal Cir A
0-10V capacity signal, circuit A
6
COMP_B
off/on
-
Compressor B
Compressor B status (circuit B)
7
OIL_SL_B
off/on
-
Oil Solenoid Output B
Oil solenoid output, circuit B
8
SLID_1_B
off/on
-
Slide Valve 1 Output B
Slide valve 1 output, circuit B
9
SLID_2_B
off/on
-
Slide Valve 2 Output B
Slide valve 2 output, circuit B
10
CAPT010B
-
V
Capacity Signal Cir B
0-10V capacity signal, circuit B
11
COMP_C
off/on
-
Compressor C
Not applicable to this unit
12
OIL_SL_C
off/on
-
Oil Solenoid Output C
Not applicable to this unit
13
SLID_1_C
off/on
-
Slide Valve 1 Output C
Not applicable to this unit
14
SLID_2_C
off/on
-
Slide Valve 2 Output C
Not applicable to this unit
15
CAPT010C
-
V
Capacity Signal Cir C
Not applicable to this unit
16
CAPT_010
-
V
Chiller Capacity signal
Chiller capacity signal
17
ALARM
off/on
-
Alarm Relay Status
Alarm relay status
18
RUNNING
off/on
-
Running Relay Status
Running relay status
19
ALERT
off/on
-
Alert Relay State
Alert relay state
20
SHUTDOWN
off/on
-
Shutdown Indicator State
Shutdown indicator state
21
POS_3WV
0 to 100
%
Cond 3 Way Valve Pos
Condenser 3-way valve position
22
READY
off/on
-
Ready or Running Status
Unit ready/running status
23
ELBXFAN
off/on
-
Electrical Box Fan
Electrical box fan status
*Depends on the selected language (English by default).
Pump Status Menu – PUMPSTAT
No. Name
Status
Unit
Displayed text*
Description
1
SET_FLOW
no/yes
-
Cooler Flow Setpoint Out
Evaporator flow setpoint output
2
CPUMP_1
off/on
-
Cooler Pump #1 Command
Evaporator pump 1 control enabled
3
CPUMP_2
off/on
-
Cooler Pump #2 Command
Evaporator pump 2 control enabled
4
ROTCPUMP
no/yes
-
Rotate Cooler Pumps ?
Evaporator pumps rotation
5
FLOW_SW
open/close
-
Cooler Flow Switch
Evaporator flow switch
6
HPUMP_1
off/on
-
Condenser Pump Command1 Condenser pump control enabled
7
HPUMP_2
off/on
-
Condenser Pump Command2 Not applicable to this unit
8
ROTHPUMP
no/yes
-
Rotate Condenser Pumps ?
Not applicable to this unit
9
CONDFLOW
open/close
-
Condenser Flow Status
Condenser flow status
*Depends on the selected language (English by default).
Run Times Menu – RUNTIME
No. Name
Status
Unit
Displayed text*
Description
1
HR_MACH
-
hour
Machine Operating Hours
Unit operating hours
2
st_mach
-
-
Machine Starts Number
Number of unit starts
3
hr_cp_a
-
hour
Compressor A Hours
Operating hours, compressor A
4
st_cp_a
-
-
Compressor A Starts
Number of starts, compressor A
5
hr_cp_b
-
hour
Compressor B Hours
Operating hours, compressor B
6
st_cp_b
-
-
Compressor B Starts
Number of starts, compressor B
7
hr_cp_c
-
hour
Compressor C Hours
Not applicable to this unit
8
st_cp_c
-
-
Compressor C Starts
Not applicable to this unit
9
hr_cpum1
-
hour
Cooler Pump #1 Hours
Operating hours, evaporator pump 1