14
6 - TOUCH PILOT CONTROL: DETAILED MENU STRUCTURE
6.1 - Main menu
Icon
Displayed text*
Description
Associated table
General Parameters
General parameters
GENUNIT
Temperatures
Temperatures
TEMP
Pressures
Pressures
PRESSURE
Inputs Status
Inputs status
INPUTS
Outputs Status
Outputs status
OUTPUTS
Pump Status
Pump status
PUMPSTAT
Run Times
Run times
RUNTIME
Modes
Modes
MODES
Setpoint Table
Setpoint
SETPOINT
Configuration Menu
Configuration menu
(see also section 6.2)
CONFIG
Trendings
Trendings **
TRENDING
* Depends on the selected language (English by default).
** The Trendings menu is displayed in form of a graph. For more information about Trendings, see section 7.18.
CAUTION:
Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
General Parameters Menu – GENUNIT
No. Name
Status
Unit
Displayed text*
Description
1
CTRL_TYP
0 to 2
-
Local=0 Net.=1 Remote=2
Operating mode:
0 = Local
1 = Network
2 = Remote
2
STATUS
-
-
Run Status
Off, Running, Stopping, Delay, Trip out, Ready,
Override, etc.
3
CHIL_S_S
dsable/enable
-
Net.: Cmd Start/Stop
Unit start/stop via Network: When the unit is in
Network mode, start/stop command can be forced
4
CHIL_OCC
no/yes
-
Net.: Cmd Occupied
Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
5
min_left
-
min
Minutes Left for Start
Minutes before the unit start-up
6
HEATCOOL
Heat/Cool
-
Heat/Cool status
Heating/cooling status: Heat/Cool
7
HC_SEL
0 to 2
-
Heat/Cool Select
Heating/cooling selection:
8
0=Cool. 1=Heat. 2=Auto
0 = Cooling mode
1 = Heating mode
2 = Auto mode (Not applicable to this unit!)
9
SP_SEL
0 to 2
-
Setpoint Select
Setpoint selection
10
0=Auto. 1=Spt1. 2=Spt2
0 = Auto (schedule control)
1 = Setpoint 1 (active during occupied period)
2 = Setpoint 2 (active during unoccupied period)