7.5.2 - Variator sub-code alarms
No.
Alarm/alert
level
Description
Action taken
Variator sub-code alarms
2
Alarm
Error at function "Live Zero"
Contact Carrier Service
4
Alarm
Phase loss detection
Check the VFD supply voltage and the phase balance (±3%)
7
Alarm
Overvoltage detected
Contact Carrier Service
8
Alarm
Undervoltage detected
Contact Carrier Service
9
Alarm
Inverter overload
Check the VFD output current/compressor current
10
Alarm
Motor overheated
Check the motor temperature
11
Alarm
Motor overheat thermistor defective
Contact Carrier Service
12
Critical alarm
Torque limit exceeded
Check the VFD output current/compressor current
13
Critical alarm
Overcurrent detected
Check the VFD output current/compressor current
14
Critical alarm
Poor earthing
Check if an earth fault exists
16
Critical alarm
Motor short-circuit detected
Check if there is a short-circuit at the VFD terminals
17
Alarm
Communication loss with the frequency converter
Check the connections and the shielding of the serial communication cable
23**
Alarm
Internal fan operating problem
Check the internal fan rotation
25
Alarm
Brake resistor short-circuited
Contact Carrier Service
26
Alarm
Capacity dissipated by the brake resistor too high
Contact Carrier Service
28
Alarm
Brake verification
Contact Carrier Service
29
Critical alarm
VFD temperature too high
Space temperature too high or VFD ventilation obstructed or damaged
30
Critical alarm
Motor phase U missing
Check wiring of phase U
31
Critical alarm
Motor phase V missing
Check wiring of phase V
32
Critical alarm
Motor phase W missing
Check wiring of phase W
33
Alarm
Current demand too high
Let the VFD cool down for 20 minutes before starting it
34
Alarm
Problem on the site communication bus
Check the connections and the shielding of the serial communication cable
36
Alarm
Supply voltage problem
Check the VFD supply voltage and the phase balance (±3%)
38
Critical alarm
Internal frequency variator problem
Contact Carrier Service
47
Alarm
24 V supply too low
Contact Carrier Service
48
Alarm
1.8 V supply too low
Contact Carrier Service
57*** Alarm
No response from AMA
Contact Carrier Service
65
Alarm
Control board overheated
Check the space temperature and the VFD fan
67
Critical alarm
Option configuration modifications
Contact Carrier Service
68
Alarm
Numerical input 37 - emergency stop activated
Contact Carrier Service
71
Alarm
Emergency stop at thermistor PTC1
Contact Carrier Service
72
Critical alarm
Emergency stop
Contact Carrier Service
80
Alarm
Frequency variator reset to default values
Contact Carrier Service
94
Alarm
Curve end
Contact Carrier Service
95
Alarm
Torque loss
Contact Carrier Service
243
Alarm
IGBT defective
Contact Carrier Service
251† Critical alarm
New parts detached
Contact Carrier Service
301
Alarm
Problem in set 1 of the configuration parameters
Check the communication bus connections and the software version
302
Alarm
Problem in set 2 of the configuration parameters
Check the communication bus connections and the software version
303
Alarm
Problem in set 3 of the configuration parameters
Check the communication bus connections and the software version
Variator sub-code alerts
(WY-XXX*)
1
Alert
10 V supply to low
Contact Carrier Service
2
Alert
Error at function "Live Zero"
Contact Carrier Service
3
Alert
No motor
Check the motor connections
4
Alert
Phase loss detection
Check the VFD supply voltage and the phase balance (±3%)
5
Alert
Intermediate voltage too high
Check the VFD supply voltage and the phase balance (±3%)
6
Alert
Intermediate voltage too high
Check the VFD supply voltage and the phase balance (±3%)
7
Alert
Intermediate voltage too high
Contact Carrier Service
8
Alert
Intermediate voltage too high
Contact Carrier Service
9
Alert
Inverter overload
Check the VFD output current/compressor current
10
Alert
Motor overheated
Check the motor temperature
11
Alert
Motor overheat thermistor defective
Contact Carrier Service
12
Alert
Torque limit exceeded
Check the VFD output current/compressor current
13
Alert
Overcurrent detected
Check the VFD output current/compressor current
14
Alert
Poor earthing
Check if an earth fault exists
17
Alert
Motor short-circuit detected
Check the connections and the shielding of the serial communication cable
23**
Alert
Communication loss with the frequency converter
Check the internal fan rotation
25
Alert
Brake resistor short-circuited
Contact Carrier Service
26
Alert
Capacity dissipated by the brake resistor too high
Contact Carrier Service
28
Alert
Brake verification
Contact Carrier Service
34
Alert
Problem on the site communication bus
Check the connections and the shielding of the serial communication cable
36
Alert
Supply voltage problem
Check the VFD supply voltage and the phase balance (±3%)
47
Alert
24 V supply too low
Contact Carrier Service
49
Alert
Motor speed limit exceeded
Contact Carrier Service
59
Alert
Current limit exceeded
Check the VFD output current/compressor current
62
Alert
Frequency at the maximum limit
Check the VFD output current/compressor current
64
Alert
Voltage limit
Supply voltage too low
65
Alert
Control board overheated
Check the space temperature and the VFD fan
66
Alert
Internal frequency variator temperature too low
Space temperature too low
*
Y = 0: circuit A; Y=1: circuit B; XXX = sub-code
**
Error 24 and 104 possible
*** Error 50 to 58 possible
†
Error 250 or 70 possible
†† Not applicable for variator size 102