4.13 - Menu confi guration
icon
Displayed text
Description
Associated
table
General
Confi guration
General confi guration
GEN_CONF
Pump
Confi guration
Pump confi guration
PUMPCONF
User Confi guration User confi guration
USERCONF
Reset
Confi guration
Setpoint reset
RESETCFG
Schedule Menu
Time schedule
SCHEDULE
Holiday Menu
Holidays
HOLIDAY
Broadcast Menu
Broadcast menu
BROCASTS
Date/Time
confi guration
Date/time confi guration
DATETIME
Control
Identifi cation
Control identifi cation
CTRL_ID
Associated table: GEN_CONF - General confi guration
No.
Status
Default
Unit
Displayed text*
Description
1
0 to 2
0
-
Cir Priority Sequence
Circuit priority
2
0 = Auto, 1 = A Prio
0 = auto, 1 = priority circuit A
3
2 = B Prio
2 = priority circuit B
4
yes/no
no
-
Staged Loading Sequence
Staged loading sequence
5
yes/no
no
-
Ramp Loading Select
Ramp loading selection
6
1 to 15
1
-
Unit Off to On Delay
Start-up delay
7
0 to 2
0
-
Demand Limit Type Select
Limitation type selection
8
0 = None
0 = none
9
1 = Switch Control
1 = switch control
10
2 = 4-20 mA Control
2 = 4-20 mA signal control
11
00:00
0
-
Night Mode Start Hour
Night mode start hour
12
00:00
0
-
Night Mode End Hour
Night mode end hour
13
-
100
%
Night capacity Limit
Night mode capacity limit
14
yes/no
no
-
Current Limit select
Active limitation selection
15
yes/no
no
-
Ice mode enable
Ice storage validation
16
0 to 4000
2000
A
Maximum Current Limit
Maximum current limit
17
yes/no
no
-
short cycle management
Short cycle management (compressor protection)
Associated table: PUMPCONF - Pump confi guration
No.
Status
Default
Displayed text*
Description
1
0 to 4
0
Condenser Pump Sequence
Condenser pump sequence
2
0 to 4
0
Cooler Pump Sequence
Evaporator pump sequence
3
0 = No Pump
0 = No pump
4
1 = One Pump Only
1 = 1 pump
5
2 = Two Pumps Auto
2 = 2 pumps automatic
6
3 = Pump#1 Manual
3 = pump 1 manual
7
4 = Pump#2 Manual
4 = pump 2 manual
8
24 to 3000
48
Pump Auto Rotation Delay
Pump rotation delay
9
yes/no
no
Pump Sticking Protection
Pump sticking protection
10
yes/no
no
Stop Pump During Standby
Stop pump when unit is in standby
11
yes/no
yes
Flow Checked if Pump Off
Flow check when pump is off
12
yes/no
no
Cooler pump off in heat
Evaporator pump off in heating
13
yes/no
no
Cond pump off in cool
Condenser pump off in cooling
*
Depends on selected language, default is English