17
5.5 - Water flow switch
The controller is configurable. The configuration depends on
the unit size and is made automatically at the start-up.
If the measured flow rate in the water loop is lower than the
configured flow rate, an alarm condition shuts off the unit.
5.7.1 - Active setpoint
Two setpoints can be selected. Usually, the second cooling
setpoint is used for unoccupied periods. Depending on the
current operation type, the active setpoint can be selected
by choosing the item in the table Status => Genunit, with the
volt-free user contacts, with network commands or with the
setpoint timer program (schedule 2).
The following tables summarise the possible selections
depending on the control types (local, remote or network)
and the following parameters:
•
Setpoint select in local control
: item “Setpoint select”
in the table Status => Genunit permits selection of the
active setpoint, if the unit is in local operating type.
•
Control contacts 2:
status of control contact 2.
•
Schedule 2 status:
schedule for setpoint selection.
5.7 - Control point
The control point represents the water temperature that the
unit must satisfy.
In cooling mode the evaporator outlet water is controlled by
default, but the evaporator inlet water can also be controlled
(requires a Service configuration modification).
In heating mode the condenser outlet water is controlled by
default, but the condenser inlet water can also be controlled
(requires a Service configuration modification).
Control point = active se reset
Parameter status
On/off status
Control type
Heating/cooling selection
in local mode
Heating/cooling contact
in remote mode
HC_SEL
Operating mode
Off
-
-
-
-
Cooling
On
Local
Cooling
-
-
Cooling
On
Local
Heating
-
-
Heating
On
Remote
-
On cooling
-
Cooling
On
Remote
-
On heating
-
Heating
On
Network
-
-
Cooling
Cooling
On
Network
-
-
Heating
Heating
5.6 - Heating/cooling selection
For units configured in the heat pump mode, heating/cooling
selection can be controlled in various ways, depending on
the active operating type:
•
locally at the unit using the HC_SEL item in the
GENUNIT table,
•
remotely via the heating/cooling selection contact, if
the unit is in the Remote mode operating type,
•
via a CCN or BACnet/IP (option) network command,
if the unit is in the network operating type.
LOCAL OPERATING MODE
Parameter status
Active setpoint
Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status*
Schedule 2 status
Cooling
csp 1
-
-
-
Cooling setpoint 1
Cooling
csp 2
-
-
-
Cooling setpoint 2
Cooling
auto
Activated
Open
Unoccupied
Ice storage setpoint
Cooling
auto
Activated
Closed
Unoccupied
Cooling setpoint 2
Cooling
auto
-
-
Occupied
Cooling setpoint 1
Cooling
auto
Deactivated
-
Unoccupied
Heating setpoint 2
Heating
hsp 1
-
-
-
Heating setpoint 1
Heating
hsp 2
-
-
-
Heating setpoint 2
Heating
auto
-
-
Occupied
Heating setpoint 1
Heating
auto
-
-
Unoccupied
Heating setpoint 2
REMOTE OPERATING MODE
Parameter status
Active setpoint
Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status*
Control contact 2
Cooling
csp control
-
-
-
Control setpoint
Cooling
-
-
-
csp 1 (open)
Cooling setpoint 1
Cooling
-
-
-
csp 2 (closed)
Cooling setpoint 2
Cooling
-
Activated
-
Open
Cooling setpoint 1
Cooling
-
Activated
Open
Closed
Ice storage setpoint
Cooling
-
Activated
Closed
Closed
Cooling setpoint 2
Heating
-
-
-
Open
Heating setpoint 1
Heating
-
-
-
Closed
Heating setpoint 2
NETWORK OPERATING MODE
Parameter status
Active setpoint
Heating/cooling operating mode Local setpoint selection Ice storage configuration* Ice storage contact status*
Schedule 2 status
Cooling
-
-
-
Occupied
Cooling setpoint 1
Cooling
-
-
-
Unoccupied
Cooling setpoint 2
Cooling
-
Activated
Open
Unoccupied
Ice storage setpoint
Cooling
-
Activated
Closed
Unoccupied
Cooling setpoint 2
Heating
-
-
-
Occupied
Heating setpoint 1
Heating
-
-
-
Unoccupied
Heating setpoint 2
* Only with energy management option