Associated table:
PUMPSTAT - Pump status
No.
Status
Unit
Displayed text*
Description
1
yes/no
-
Cooler Flow Setpoint Out
Evaporator fl ow setpoint output
2
on/off
-
Cooler Pump #1 Command
Evaporator pump control 1
3
on/off
-
Cooler Pump #2 Command
Evaporator pump control 2
4
on/off
-
Rotate Cooler Pumps ?
Evaporator pump rotation?
5
open/closed
-
Cooler Flow Switch
Flow switch
6
on/off
-
Condenser Pump Command1
Condenser pump control 1
7
on/off
-
Condenser Pump Command2
Condenser pump control 2
8
on/off
-
Rotate Condenser Pumps ?
Condenser pump rotation?
9
open/closed
-
Condenser Flow Status
Condenser fl ow status
Associated table: RUNTIME -
Run times
No.
Status
Unit
Displayed text*
Description
1
-
hour
Machine Operating Hours
Unit operating hours
2
-
-
Machine Starts Number
Number of unit starts
3
-
hour
Compressor A Hours
Operating hours, compressor A
4
-
-
Compressor A Starts
Number of starts, compressor A
5
-
hour
Compressor B Hours
Operating hours, compressor B
6
-
-
Compressor B Starts
Number of starts, compressor B
7
-
hour
Cooler Pump #1 Hours
Operating hours, evaporator pump 1
8
-
hour
Cooler Pump #2 Hours
Operating hours, evaporator pump 2
9
-
hour
Condenser Pump #1 Hours
Operating hours, condenser pump 1
10
-
hour
Condenser Pump #2 Hours
Operating hours, condenser pump 2
Associated table: MODES - Modes
No.
Status
Unit
Displayed text*
Description
1
yes/no
-
Start-up delay in eff ect
Start-up delay in eff ect
2
yes/no
-
Second Setpoint in Use
Second setpoint in use
3
yes/no
-
Reset in eff ect
Setpoint reset active
4
yes/no
-
Demand limit active
Demand limit active
5
yes/no
-
Cooler Pump Rotation
Evaporator pump rotation
6
yes/no
-
Pump Periodic Start
Periodic pump start-up
7
yes/no
-
Night Low Noise Active
Night mode active
8
yes/no
-
Master Slave Active
Master/slave active
9
yes/no
-
Auto Changeover Active
Automatic changeover active
10
yes/no
-
Condenser Pump Rotation
Condenser pump rotation
11
yes/no
-
Cond Pump Periodic Start
Periodic condenser pump start-up
12
yes/no
-
Ice Mode in Eff ect
Ice storage mode active
Associated table: SETPOINT - Setpoint table
No.
Status
Default
Unit
Displayed text*
Description
1
-28.9 to 26.0
6.7
°C
Cooling Setpoint 1
Cooling setpoint 1
2
-28.9 to 26.0
6.7
°C
Cooling Setpoint 2
Cooling setpoint 2
3
-28.9 to 26.0
6.7
°C
Cooling Ice Setpoint
Ice storage setpoint
4
0.1 to 11.1
0.6
^C
Cooling Ramp Loading
Cooling ramp loading
5
26.7 to 63.0
37.8
°C
Heating Setpoint 1
Heating setpoint 1
6
26.7 to 63.0
37.8
°C
Heating Setpoint 2
Heating setpoint 2
7
0.1 to 11.1
0.6
^C
Heating Ramp Loading
Heating ramp loading
8
3.9 to 50.0
23.9
°C
Cool Changeover Setpt
Auto changeover setpoint, cooling
9
0 to 46.1
17.8
°C
Heat Changeover Setpt
Auto changeover setpoint, heating
10
26.7 to 48.9
35.0
°C
Water Val Condensing Stp
Water valve condensing setpoint
11
0 to 100
100
%
Switch Limit Setpoint 1
Limit setpoint switch 1
12
0 to 100
100
%
Switch Limit Setpoint 2
Limit setpoint switch 2
13
0 to 100
100
%
Switch Limit Setpoint 3
Limit setpoint switch 3
*
Depends on selected language, default is English
No.
Status
Unit
Displayed text*
Description
22
on/off
-
Drycooler Fan 6
Output, dry cooler 6
23
on/off
-
Drycooler Fan 7
Output, dry cooler 7
24
on/off
-
Drycooler Fan 8
Output, dry cooler 8
25
0 to 10
V
Dry Cool Vfan 1 Output
Dry Cooler variable speed fan 1 output
26
0 to 10
V
Dry Cool Vfan 2 Output
Dry Cooler variable speed fan 2 output