5 - SMARTVU CONTROL: MENU STRUCTURE
Heat Cool Configuration
–
HCCONFIG
Point Name
Status
Default
Unit
Description
Low Limit
High Limit
cr_sel
NO_YES
0
-
Cooling Reset
Select
0
1
ehs_th
23 to 70
41
°F
Elec Stage OAT
Threshold
23
70
hs_back
NO_YES
0
-
1 HS For Backup
0
1
hs_pull
0 to 60
0
min
HS Pulldown Time
0
60
hs_defr
NO_YES
0
-
Quick HS For
Defrost
0
1
Reset Configuration
–
RESETCFG
Point Name
Status
Default
Unit
Description
Low Limit
High Limit
blank
-
Cooling :
oathr_no
14 to 125
14
°F
OAT No Reset
Value
14
125
oathr_fu
14 to 125
14
°F
OAT Full Reset
Value
14
125
cr_deg
-30 to 30
0
^F
Cooling Reset Deg.
Value
-30
30
Date/Time Configuration
–
DATETIME
Status
Displayed text*
Description
on/off
Daylight Saving Time
Information of setting the clocks forward one hour
from standard time during the summer months, and
back again in the fall, in order to make better use of
natural daylight
Greenwich Mean Time
(UTC)
Location
Time zone
YYYY/MM/DD, HH:MM:SS
Date/Time
Current date and time (must be set manually)
no/yes
Today is a Holiday
Information about holidays (read-only). Please
note that holidays are set in the Holiday menu
(see also section 5.4)
no/yes
Tomorrow is a Holiday
Information about the upcoming holiday period
(read-only). Please note that holidays are set in the
Holiday menu (see also section 5.4)
Control Identification
–
CTRL_ID
Status
Default
Displayed text*
Description
0-239
1
CCN Element Number Element number
0-239
0
CCN Bus Number
Bus number
9600 / 19200 /
38400
9600
CCN Baud Rate
Communication speed
-
50/48 UCUP-V
SmartVu
Device Description
Unit description
-
-
Location Description
Location description: The number corresponds to
the country
-
ECG-SR-20V4B100
Software Part Number Software version
-
-
Serial Number
Serial number (MAC address)
*Depends on the selected language (English by default).