5 - SMARTVU CONTROL: MENU STRUCTURE
Setpoint
–
SETPOINT
Point Name
Status
Default
Unit
Description
Low Limit
High Limit
blank
-
Temperature
setpoints :
²²
occ_cool
50 to 89.6
78.8
°F
Occupied Cooling
Stpt
50
89.6
uno_cool
50 to 89.6
82.4
°F
Unocc. Cooling Stpt 50
89.6
occ_heat
50 to 75.2
66.2
°F
Occupied Heating
Stpt
50
75.2
uno_heat
50 to 75.2
62.6
°F
Unocc. Heating
Stpt
50
75.2
frst_sp
50 to 75.2
59
°F
holiday setpoint
50
75.2
blank
-
Humidity :
oc_rh_sp
10 to 80
50
%
Occupied Humidity
Stpt
10
80
oc_rh_db
10 to 50
10
%
Occupied Humidity
DBand
10
50
un_rh_sp
10 to 80
70
%
Unoccupied
Humidity Stpt
10
80
un_rh_db
10 to 50
30
%
Unoccupied
Humidity Db
10
50
blank
-
Miscellaneous :
purg_low
45 to 59
50
°F
Purge: OAT Low
Limit
45
59
purg_hig
60 to 110
60.8
°F
Purge: OAT High
Limit
60
110
purg_du
1 to 5
2
min
Purge Duration
1
5
iaq_sp
50 to 10000
700
-
IAQ Setpoint
50
10000
Trendings
–
TRENDING
Name
Status
Unit
Displayed text*
Description**
GENUNIT_cap_t
0 to 100
%
Perecent Total Capacity
Perecent Total Capacity
GENUNIT_CTRL_PN
0 to 100
°C / °F
Control Point
Control point
TEMP_OAT
-
°C / °F
Outdoor Air Temp
Outdoor air temperature
TEMP_SAT
-
°C / °F
Supply Air Temperature
Supply Air Temperature
TEMP_SPT
-
°C / °F
Space Temperature
Space Temperature
TEMP_SCT_A
-
°C / °F
Saturated Cond Tmp cir A
Saturated condensing temperature, circuit A
TEMP_SCT_B
-
°C / °F
Saturated Cond Tmp cir B
Saturated condensing temperature, circuit B
TEMP_SST_A
-
°C / °F
Saturated Suction Temp cir A
Saturated suction temperature, circuit A
TEMP_SST_B
-
°C / °F
Saturated Suction Temp cir B
Saturated suction temperature, circuit B
*Depends on the selected language (English by default).
**The list of trending points cannot be modified. Trending points can only be enabled or disabled.