5 - SMARTVU CONTROL: MENU STRUCTURE
Modes
–
MODES
Point Name
Status
Default
Unit
Description
Low
Limit
High
Limit
CCN Force LEN Force
m_limit
NO_YES
0
-
demand limit active
0
1
m_ifan
NO_YES
0
-
Indoor Fan Cycling
0
1
m_night
NO_YES
0
-
Night Condensing
Mode
0
1
m_frostp
NO_YES
0
-
Frost Protection
Mode
0
1
m_master
NO_YES
0
-
Master Slave Active
0
1
m_reset
NO_YES
0
-
Reset in Effect?
0
1
m_heater
NO_YES
0
-
Electric Heat Active
0
1
m_eco
NO_YES
0
-
Economizer Mode
0
1
m_purge
NO_YES
0
-
Purge Mode
0
1
m_pwrh
NO_YES
0
-
Power Exhaust Mode 0
1
m_humid
NO_YES
0
-
Humidification Mode
0
1
m_dehumi
NO_YES
0
-
Dehumidification
Mode
0
1
m_iaq
NO_YES
0
-
IAQ Mode
0
1
m_gas
NO_YES
0
-
OAT Gas Threshold
0
1
m_fire
NO_YES
0
-
Fire Shutdown
Active?
0
1
m_enth
NO_YES
0
-
Enthalpy Lockout
0
1
m_start
NO_YES
0
-
Optimal Start Mode
0
1
m_oat_h
NO_YES
0
-
VSPD High Oat
Derating
0
1
m_defr_a
NO_YES
0
-
A:Defrost Active
0
1
m_defr_b
NO_YES
0
-
B:Defrost Active
0
1
m_defr_c
NO_YES
0
-
THR:Defrost Active
0
1
m_sst_a
NO_YES
0
-
A:Low Suction
0
1
m_sst_b
NO_YES
0
-
B:Low Suction
0
1
m_sst_c
NO_YES
0
-
THR:Low Suction
0
1
m_dgt_a
NO_YES
0
-
A:Compressor
Envelope
0
1
m_dgt_b
NO_YES
0
-
B:Compressor
Envelope
0
1
m_dgt_c
NO_YES
0
-
THR:Compressor
Envelope
0
1
m_hp_a
NO_YES
0
-
A:High Pressure
Override
0
1
m_hp_b
NO_YES
0
-
B:High Pressure
Override
0
1
m_hp_c
NO_YES
0
-
THR:High Press
Override
0
1