5 - SMARTVU CONTROL: MENU STRUCTURE
Outputs
–
OUTPUTS
Point Name
Status
Default
Unit
Description
Low Limit High
Limit
CCN Force LEN Force
cp_a1
OFF_ON
0
-
Compressor A1 0
1
cp_a2
OFF_ON
0
-
Compressor A2 0
1
VSPD_SPD
0 to 100
0.0
%
VSPD speed
0
100
X
X
vspdsafe
OFF_ON
0
-
VSPD safety
contact
0
1
fan_l_a
OFF_ON
0
-
Fan A1 Speed
0
1
fan_h_a
OFF_ON
0
-
Fan A1 Speed
0
1
rv_a
OFF_ON
0
-
4Way
Refrigerant
Valve A
0
1
heater_a
OFF_ON
0
-
Drain Pan
Heater A
0
1
cp_b1
OFF_ON
0
-
Compressor B1 0
1
cp_b2
OFF_ON
0
-
Compressor B2 0
1
fan_l_b
OFF_ON
0
-
Fan B1 Speed
0
1
fan_h_b
OFF_ON
0
-
Fan B1 Speed
0
1
rv_b
OFF_ON
0
-
4Way
Refrigerant
Valve B
0
1
heater_b
OFF_ON
0
-
Drain Pan
Heater B
0
1
cp_c1
OFF_ON
0
-
THR
Compressor 1
Output
0
1
cp_c2
OFF_ON
0
-
THR
Compressor 2
Output
0
1
rv_c
OFF_ON
0
-
4Way Refrig
Valve THR
0
1
ecopos
0 to 0
0
%
Economizer
Position
0
0
gas_on
OFF_ON
0
-
Modulated Gas
Enable
0
1
gas_v
0 to 0
0
%
Modulated Gas
Value
0
0
WV
0 to 0
0
%
Water Valve
0
0
humid
OFF_ON
0
-
Humidifier
Output
0
1
dehumid
OFF_ON
0
-
Dehumidifier
Output
0
1
pexhaust
OFF_ON
0
-
Power Exhaust
0
1
fire_dmp
OFF_ON
0
-
Fire Damper
0
1
hs_step
0 to 0
0
-
Additional Heat
Stage
0
0
alarm
OFF_ON
0
-
Alarm Relay
Status
0
1
RUNNING
OFF_ON
0
-
Running Relay
Status
0
1
hrw
OFF_ON
0
-
Heat Recovery
Wheel
0
1
vlt_en
OFF_ON
0
-
Supply Fan
Enable
0
1
vlt_rf
OFF_ON
0
-
Return Fan
Enable
0
1
cur_spd
0 to 0
0
%
Current S Fan
Speed
0
0
cur_spd2
0 to 0
0
%
Current R Fan
Speed
0
0
cur_airf
0 to 0
0
KGPH Current Supply
Airflow
0
0
cur_air2
0 to 0
0
KGPH Current Return
Airflow
0
0
freshair
0 to 0
0
%
Fresh Air Rate
0
0
exv_a
0 to 0
0
%
EXV Position
Circuit A
0
0