Carrier RHW036-060 Скачать руководство пользователя страница 36

36

Specifications subject to change without notice.

36

2SP H/C and 3 Speed Fan Operation

FAN TYPE = 2SP H/C and FAN TYPE = 3SPEED are not

used on RHW units.
CHECKOUT
Inspect all wiring connections at the economizer module’s

terminals, and verify compliance with the installation wiring

diagrams. For checkout, review the Status of each config

-

ured parameter and perform the Checkout tests.

NOTE: For information about menu navigation and use of

the keypad see Interface Overview on page 28.

  

Power Up

After  the  W7220  module  is  mounted  and  wired,  apply

power.

Initial Menu Display

On initial start up, Honeywell displays on the first line and

economizer W7220 on the second line. After a brief pause,

the revision of the software appears on the first line and the

second line will be blank.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any

power loss or interruption.

NOTE: All settings are stored in non-volatile flash memory.

Status

Use the Status menu (see Table 9) to check the parameter

values for the various devices and sensors configured.

NOTE: For information about menu navigation and use of

the keypad see Interface Overview on page 28.

Checkout Tests

Use the Checkout menu (see page 32) to test the damper

operation and any configured outputs. Only items that are

configured are shown in the Checkout menu.

NOTE: For information about menu navigation and use of

the keypad see Interface Overview on page 28.

To perform a Checkout test:

1. Scroll to the desired test in the Checkout menu using

the ▲ and ▼ buttons. 

2. Press the 

 (Enter) button to select the item. RUN?

appears. 

3. Press the 

 (Enter) button to start the test. The unit

pauses and then displays IN PROGRESS. When the

test is complete, DONE appears. 

4. When  all  desired  parameters  have  been  tested,

press the 

 (Menu Up/Exit) button to end the test.

The Checkout tests can all be performed at the time of in

-

stallation or at any time during the operation of the system

as a test that the system is operable.

TROUBLESHOOTING

Alarms

The economizer module provides alarm messages that dis

-

play on the 2-line LCD.

NOTE: Upon power up, the module waits 60 minutes before

checking for alarms. This allows time for all the configured

devices (e.g. sensors, actuator) to become operational. The

exception is the SAT sensor which will alarm immediately.

If one or more alarms are present and there has been no

keypad activity for at least 5 minutes, the Alarms menu dis

-

plays and cycles through the active alarms.

You can also navigate to the Alarms menu at any time.

Clearing Alarms

Once the alarm has been identified and the cause has been

removed  (e.g.  replaced  faulty  sensor)  the  alarm  can  be

cleared from the display.

To clear an alarm, perform the following:

1. Navigate to the desired alarm.

2. Press the 

 (Enter) button. ERASE? displays.

3. Press  the 

  (Enter)  button.  ALARM  ERASED

displays.

4. Press the 

 (Menu Up/Exit) button to complete the

action and return to the previous menu.

NOTE:  If  the  alarm  still  exists  after  clearing  it,  it  is  redis

-

played within 5 seconds.

Controller Options

LOW AMBIENT
If the unit comes with Electro-Mechanical (EM) control, then

no adjustment is necessary. 

If the unit is equipped with a third party controller, then refer

to  its  installation  control  manual  for  details  on  adjusting

“Cooling Lock-Out” setting and configure for the specific job

requirements.

Smoke Detectors

Smoke detectors are available as factory-installed options

on RHW models. Smoke  detectors may be specified for

Supply Air only or for Return Air without or with economiz

-

er, or in combination of Supply Air and Return Air. Return

Air smoke detectors are arranged for vertical return config

-

urations only. All components necessary for operation are

factory-provided and mounted. The unit is factory-config

-

ured  for  immediate  smoke  detector  shutdown  operation;

additional  wiring  or  modifications  to  unit  terminal  board

may be necessary to complete the unit and smoke detec

-

tor configuration to meet project requirements.

Units equipped with factory-optional Return Air smoke de

-

tectors  require  a  relocation  of  the  sensor  module  at  unit

installation. See Fig. 47 for the as-shipped location.

WARNING

Failure  to  follow  this  warning  could  result  in  personal

injury, property damage, or death. 

Before performing service or maintenance operations on

unit, always turn off main power switch to unit and install

lock(s) and lockout tag(s). Unit may have more than one

power  switch.  Ensure  electrical  service  to  rooftop  unit

agrees with voltage an amperage listed on the unit rating

plate.

If any wiring changes are required, first be sure to re

-

move power from the Economizer module before start

-

ing work. Pay particular attention to verifying the power

connection (24 Vac).

CAUTION

Failure  to  follow  this  caution  may  result  in  damage  to

equipment. Be sure to allow enough time for compressor

startup  and  shutdown  between  checkout  tests  so  that

you do not short-cycle the compressors.

Содержание RHW036-060

Страница 1: ...ors 36 COMPLETING RETURN AIR SMOKE SENSOR INSTALLATION ADDITIONAL APPLICATION DATA Step 12 Adjust Factory Installed Options 37 SMOKE DETECTORS ECONOMI ER IV OCCUPANCY SWITCH Step 13 Install Accessorie...

Страница 2: ...ON AND SAFETY HAZARD Failure to follow this warning could cause personal inju ry death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not...

Страница 3: ...e K voltage code models the following are not available as factory installed options Coated or copper fin coils Economizers and 2 position damper Powered convenience outlet 1 See Specification Sheet f...

Страница 4: ...4 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing...

Страница 5: ...527 01 2701 00 Specifications subject to change without notice 5 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Страница 6: ...6 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Страница 7: ...ed ductwork at unit duct openings 6 Install outdoor air hood 7 Install condensate line trap and piping 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounte...

Страница 8: ...BER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MF...

Страница 9: ...n place The red drain pan can be tightened with a 1 2 in square socket drive extension For further details see Step 10 Install External Condensate Trap and Line on page 12 Before setting the unit onto...

Страница 10: ...o the flanges Insulate and weatherproof all external ductwork joints and roof or building openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibili...

Страница 11: ...installed on the unit the hood shipped with the unit will not be used and must be discarded Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be...

Страница 12: ...he convenience outlet s transformer primary are not factory connected Installer must connect these leads according to required operation of the conve nience outlet If an always energized convenience o...

Страница 13: ...the handle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the control box access panel The NFD enclosure is located below the control box see Fig 19 2 Remove 3 cap he...

Страница 14: ...wiring connections Provide a ground fault and short circuit over current protec tion device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Max imum O...

Страница 15: ...t access is through the unit s control box access panel See Fig 21 The primary leads to the convenience outlet transformer are not factory connected Selection of primary power source is a customer opt...

Страница 16: ...does not get into the building or conduit in the interim Check tightness of connector lock nuts before connecting electrical conduits Field supplied and field installed liquid tight conduit connector...

Страница 17: ...nal features which might require addi tional conductors in the cable For wire runs up to 50 ft 15 m use no 18 AWG Ameri can Wire Gage insulated wire 35 C 95 F minimum For 50 to 75 ft 15 to 23 m use no...

Страница 18: ...delay feature user selectable The DFB also provides an indoor fan off delay feature user selectable See Fig 29 for board arrangement The DFB is located in the main control box of the RHW unit see Fig...

Страница 19: ...1 Heating cycle for an Emergency Heating sequence compressors are off and only the elec tric heaters are energized and also during the Defrost cycle to eliminate a cold blow condition in the space De...

Страница 20: ...value exceeds 60 A unit mounted supplementary fuses are required for each heater circuit These fuses are included in accessory Single Point Boxes with power distribution and fuse blocks The single poi...

Страница 21: ...e left of the Heater module Connect the VIO lead from Heater circuit 1 to terminal TB4 1 For 2 stage heating connect the VIO lead from Heater circuit 2 to terminal TB4 2 See Fig 36 Fig 36 Accessory El...

Страница 22: ...22 Specifications subject to change without notice 527 01 2701 00 Fig 37 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 208 230 3 60 Unit Shown...

Страница 23: ...527 01 2701 00 Specifications subject to change without notice 23 Fig 38 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 460 575 3 60 Unit Shown...

Страница 24: ...24 Specifications subject to change without notice 24 Fig 39 Typical RHW036 060 Power Wiring Diagram 208 230 3 60 Unit Shown...

Страница 25: ...527 01 2701 00 Specifications subject to change without notice 25 Fig 40 Typical RHW036 060 Power Wiring Diagram 460 575 3 60 Unit Shown...

Страница 26: ...vailable with bus sensors User Interface Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keyp...

Страница 27: ...ity Insensitive Connection Bottom Left Terminal Block IAQ 2 10 2 10 vdc Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source AC...

Страница 28: ...Enter button to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus Fig 45 W7220 Controller Navigation Buttons To...

Страница 29: ...d stage cooling ON 24 Vac on terminal Y2 I OFF 0 Vac on terminal Y2 I COOL Y2 OUT OFF ON OFF SECOND STAGE COOLING RELAY OUTPUT Cool Stage 2 Relay Output to mechanical cooling Y2 OUT terminal MA TEMP _...

Страница 30: ...y sensor option Enthalpy boundary curves for economizing using single enthalpy DCV SET 1100ppm 500 to 2000 ppm increment by 100 DEMAND CONTROLLED VENTILATION SETPOINT Displays only if CO2 sensor is co...

Страница 31: ...ivate power exhaust EXH2 H SET 75 0 to 100 EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with 1 heat and 2 cool Based on economizer OA damper position to activate power exhaust SYSTEM SET...

Страница 32: ...perator to adjust for an out of calibration temperature sensor OA H CAL 0 RH 10 RH OUTSIDE AIR HUMIDITY CALIBRATION Allows for operator to adjust for an out of calibration humidity sensor RA T CAL 0 0...

Страница 33: ...onnected check wiring then replace sensor if the alarm continues RA SYLK H ERR N A N A DA SYLK T ERR N A N A DISCHARGE AIR S BUS SENSOR ERROR Discharge air sensor has failed or become disconnected che...

Страница 34: ...OA temperature and humidity input from the OA enthalpy sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary the economizer sets the economizing mode to YES e...

Страница 35: ...YPE 2SPEED With stage 3 delay STG3 DLY in Advanced setup COOL Y2 OUT will be turned ON after the delay time specified N A Not applicable STATE FAN SPEED OCC Low Y1 Low Y2 High W High INPUTS OUTPUTS DE...

Страница 36: ...has been no keypad activity for at least 5 minutes the Alarms menu dis plays and cycles through the active alarms You can also navigate to the Alarms menu at any time Clearing Alarms Once the alarm h...

Страница 37: ...utdown terminals on the UCB and then attach the wiring harness from the smoke detector ECONOMI ER IV OCCUPANCY SWITCH See Fig 49 on page 38 for general EconoMi er IV wiring External occupancy control...

Страница 38: ...a multimeter to the Vdc terminals on the UCB 4 Set the Range Switch to either A B or C per the Switch Range table 5 Using a straight blade screwdriver turn the Vdc con trol dial to fine tune the Vdc...

Страница 39: ...5 2250 2375 2500 0 1 0 4 6 2 6 5 6 8 7 1 7 4 7 7 8 0 8 4 8 7 0 1 0 6 6 9 7 1 7 4 7 7 7 9 8 2 8 5 8 8 0 1 0 8 7 5 7 7 8 0 8 2 8 5 8 7 9 0 0 1 1 0 8 1 8 3 8 5 8 7 9 0 0 1 1 2 8 6 8 8 9 0 9 2 0 1 1 4 9 1...

Страница 40: ...tion operation and converging coil circuits during the condenser function operation Fig 52 Typical Piping Schematic Table 14 Cooling Mode each circuit COMPONENT STATUS POSITION Reversing Valve Energiz...

Страница 41: ......

Страница 42: ...Specifications are subject to change without notice 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Страница 43: ...e of obstructions and rotor spins freely Y N _____ Verify that scroll compressors are rotating in the correct direction Y N _____ Verify installation of thermostat Y N _____ III START UP ELECTRICAL Su...

Страница 44: ...CUT ALONG D OTTED LINE CUT ALONG DOTTED LINE CL 2 Specifications are subject to change without notice 7 2020 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Отзывы: