– 118 –
<In case of wireless remote controller>
<Outline of test operation from the wireless remote controller>
Test cooling operation:
Start
→
64°F (18°C)
→
66°F (19°C)
→
64°F (18°C)
→
66°F (19°C)
→
64°F (18°C)
→
66°F (19°C)
→
64°F (18°C)
→
(Test operation)
→
Stop
Test heating operation:
Start
→
86°F (30°C)
→
84°F (29°C)
→
86°F (30°C)
→
84°F (29°C)
→
86°F (30°C)
→
84°F (29°C)
→
86°F (30°C)
→
(Test operation)
→
Stop
2
3, 4, 5, 6
2, 7
Be sure to set the
air speed to [High]
Procedure
1
2
3
4
5
6
7
Description
Turn on power of the air conditioner.
The operation is not accepted for 5 minutes when power has been turned on at first time after installation,
and 1 minute when power has been turned on at the next time and after.
After the specified time has passed, perform a test operation.
Push [
Start/Stop
] button and change the operation mode to [
COOL
] or [
HEAT
] with [
Mode
] button.
Then change the fan speed to [
High
] using [
Fan
] button.
Test cooling operation
Test heating operation
Set temperature to [64°F (18°C)] using
Set temperature to [86°F (30°C)] using
[
Temperature set
] button.
[
Temperature set
] button.
After checking the receiving sound “Pi”,
After checking the receiving sound “Pi”,
immediately push [
Temperature set
] button to
immediately push [
Temperature set
] button to
set to [66°F (19°C)]
set to [84°F (29°C)].
After checking the receiving sound “Pi”,
After checking the receiving sound “Pi”,
immediately push [
Temperature set
] button to
immediately push [
Temperature set
] button to
set to [64°F (18°C)].
set to [86°F (30°C)].
Then repeat the procedure
4
→
5
→
4
→
5
.
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,
[
Operation
] (Green), [
Timer
] (Green), and [
Ready
] (Yellow) flash and the air conditioner starts operation.
If the lamps do not flash, repeat the procedure
2
and after.
After the test operation, push [