– 110 –
9-2. High Wall Type
[Requirement when replacing the service indoor P.C. board assembly]
In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P.C. board before
replacement, the type and capacity code exclusive to the corresponding model have been stored at shipment
from the factory and the important setup data such as refrigerant line /indoor unit /group address in
(AUTO/MANUAL) mode have been stored at installation.
Replace the service indoor P.C. board assembly according to the following procedure.
After replacement, make sure that the indoor unit address is set correctly and also the refrigerant cycle is
working correctly by test operation.
<Replacement procedure>
CASE 1
Before replacement, power of the indoor unit can be turned on and the setup data can be readout
by the wired remote controller.
Read EEPROM data (see
H
1
in Page 111)
ò
Replace service P.C. board & power ON (see
H
2
in Page 112)
ò
Write the read data to EEPROM (see
H
3
in Page 114)
ò
Power reset
(If in group operation, reset the power for all indoor units which are connected to the remote controller.)
CASE 2
Before replacement, the setup data can not be read out by the wired remote controller.
Replace service P.C. board & power ON (see
H
2
in Page 112)
ò
Write the data such as “option input selection” setup to EEPROM (see
H
3
in Page 114)
(According to the customers’ information)
ò
Power reset
Model type
RAV-SP
✻✻✻
KRT-UL series
P.C. board model
MCC-1510
Label display on P.C. board
04DD 03