Step 4
Write the on-site SET DATA to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above
again.
Step 5
Change the CODE No. (DN) to “
” by pushing
/
buttons for the temperature setting.
(this is the setting for the filter sign lighting time.)
Step 6
Check the SET DATA displayed at this time with the SET DATA put down in [1].
1. If the SET DATA is different, modify the SET DATA by pushing / buttons for the timer setting to the
data put down in [1].
The operation completes if the SET DATA is displayed.
2. If the data is the same, proceed to next step.
Step 7
Change the CODE No. (DN) by pushing
/
buttons for the temperature setting.
As described above, check the SET DATA and modify to the data put down in [1].
Step 8
Repeat the steps 6 and 7.
Step 9
After the setting completes, push
TEST
button to return to the normal stop status.
(It takes approx. 1 min until the remote controller operation is available again.)
∗
The CODE No. (DN) are ranged from “
” to “
..
”. The CODE No. (DN) is not limited to be serial No.
Even after modifying the data wrongly and pushing
SET
button, it is possible to return to the data before
modification by pushing
CL
button if the CODE No. (DN) is not changed.
<Fig. 2 EEPROM layout diagram>
The EEPROM (4-Way: IC503, Under Ceiling: IC10) is attached to the IC socket. When detaching the EEPROM,
use a tweezers, etc.
Be sure to attach the EEPROM by fitting its direction as shown in the figure.
∗
Do not bend the IC lead when replacing.
<In case of 4-Way Air Discharge Cassette Type>
IC503
EEPROM
MCC-1570
EEPROM
Cut out
Cut out
IC socket
<In case of Under Ceiling Type>
EEPROM(IC10)
Match the notched parts of IC socket and
EEPROM and then put in.
MCC-1402
EEPROM
IC socket
Notch