background image

1

PG9UAA

Troubleshooting Guide

VARIABLE SPEED, TWO---STAGE

ELECTRONIC CONDENSING

GAS FURNACE

INDEX

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTRUCTIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EXAMPLE

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SEQUENCE OF OPERATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Single--Stage Thermostat and Two--Stage Heating (Adaptive Mode)

2

. . . . . . . . . . . . . . .

Two--Stage Thermostat and Two--Stage Heating

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cooling Mode

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Single--Speed Cooling

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Single--Stage Thermostat and Two--Speed Cooling (Adaptive Mode)

4

. . . . . . . . . . . . . .

Two--Stage Thermostat and Two--Speed Cooling

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Dehumidify Mode

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Super--Dehumidify Mode

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Continuous--Blower Mode

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Heat Pump Defrost

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Component Test

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE/STATUS CODE INSTRUCTIONS

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START HERE

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RAPID FLASHING AMBER LED

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IMPROPER COOLING AIR FLOW

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

HIGH HEAT TEMPERATURE RISE TOO LOW

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 11 -- NO PREVIOUS CODE

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 12 -- BLOWER ON AFTER POWER UP

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 13 -- LIMIT CIRCUIT LOCKOUT

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 14 -- IGNITION LOCKOUT

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 15 – BLOWER MOTOR LOCKOUT

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 21 -- GAS HEATING LOCKOUT

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 22 -- ABNORMAL FLAME--PROVING SIGNAL

15

. . . . . . . . . . . . . . . . . . . . .

STATUS CODE 23 -- PRESSURE SWITCH DID NOT OPEN

15

. . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 24 -- SECONDARY VOLTAGE FUSE IS OPEN

16

. . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 25 – MODEL SELECTION OR SETUP ERROR

18

. . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 31 – HIGH--HEAT SWITCH OR RELAY DID NOT CLOSE OR REOPEN

18

. .

STATUS CODE 32 -- LOW--HEAT PRESSURE SWITCH DID NOT CLOSE OR

REOPENED

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 33 -- LIMIT CIRCUIT FAULT

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 34 -- IGNITION--PROVING FAULT

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 41 – BLOWER MOTOR FAULT

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 42 – INDUCER MOTOR FAULT

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 43 -- LOW--HEAT PRESSURE SWITCH OPEN WHILE HIGH--HEAT

PRESSURE SWITCH IS CLOSED

29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STATUS CODE 45 – CONTROL CIRCUITRY LOCKOUT

30

. . . . . . . . . . . . . . . . . . . . . . . . . . .

CLEANUP AND START--UP INSTRUCTIONS

30

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX A -- BOARD LAYOUT & WIRING SCHEMATIC

31

. . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX B -- ECM BLOWER MOTOR DESCRIPTION & OPERATION

33

. . . . . . . . . . . . . .

APPENDIX C -- PRESSURE CHECK DIAGRAM

34

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX D -- STATIC PRESSURE READING LOCATION DIAGRAMS

35

. . . . . . . . . . . . . .

APPENDIX E -- QUICK REFERENCE INFORMATION

36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX F -- FURNACE STAGING ALGORITHM

37

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified

personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such

as cleaning coils, or cleaning and replacing filters. All other

operations should be performed by trained service personnel.
When working on heating equipment, observe precautions in

literature, on tags, and on labels attached to or shipped with the
unit, and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA

54--2009/ANSI Z223.1--2009. In Canada, refer to the National

Standard of Canada Natural Gas and Propane Installation Codes
(NSCNGPIC), CSA B149.1--10.
Wear safety glasses and work gloves. Have a fire extinguisher
available during start--up, adjustment procedures, and service calls.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the furnace and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION, and NOTE. The words DANGER, WARNING, and

CAUTION are used with the safety--alert symbol. DANGER
identifies the most serious hazards which will result in severe

personal injury or death. WARNING signifies hazards which

could result in personal injury or death. CAUTION is used to
identify unsafe practices which may result in minor personal injury,

or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or

operation.

INSTRUCTIONS

This guide uses your expertise and observations to lead you to the

trouble spot as efficiently as possible. This is only intended as a

guide and should not be used blindly. Your experience and
expertise are of high value when troubleshooting this unit. Do not

disregard all of your instincts.
The variable speed furnace control was designed with diagnostic

capabilities built in. An AMBER LED is used to flash a status

code which will lead you to one of the sections as listed in the
Index.
You should ALWAYS begin in the START HERE section (see
Index for page number) which will guide you to the appropriate

section where a minimal number of steps will be used to correct the
problem. Once in a section, read the ACTION. An ACTION may

have a number in the GO TO column. Do whatever the ACTION

says, then proceed to the step indicated in the GO TO column.
If the ACTION is a question (a question will have a number in the

YES or NO column), answer it YES or NO. If the answer is YES,
go to the step indicated in the YES column. If the answer is NO,

go to the step indicated in the NO column.

Содержание PG9UAA

Страница 1: ...be performed by trained service personnel When working on heating equipment observe precautions in literature on tags and on labels attached to or shipped with the unit and other safety precautions th...

Страница 2: ...the switch Correct inadequate combustion air supply component failure before resetting the switch CAUTION Before operating the furnace check each manual reset switch for continuity If necessary press...

Страница 3: ...eat pressure switch HPS closes When the high heat pressure switch HPS closes the high heat gas valve solenoid GV HI is energized and the inducer motor RPM is noted by the furnace control CPU The RPM i...

Страница 4: ...If the furnace control CPU switches from low cooling to high cooling the furnace control CPU will energize the air conditioning relay ACR When the air conditioning relay ACR is energized the R to Y1 a...

Страница 5: ...ll continue operating for an additional 5 seconds if no other function requires blower motor BLWM operation a Continuous Blower Speed Selection from Thermostat To select different continuous blower ai...

Страница 6: ...Flame is proved while gas valve is de energized Inducer will run until fault is cleared Check for Leaky gas valve Stuck open gas valve 23 PRESSURE SWITCH DID NOT OPEN Check for Obstructed pressure tu...

Страница 7: ...ration or the inducer RPM signal was lost for 5 seconds during operation Check for Proper vent sizing Restricted combustion air supply Failed inducer motor Improper motor wiring 43 LOW HEAT PRESSURE S...

Страница 8: ...re erased after 72 hours or can be manually erased by putting setup switch SW1 1 in the ON position and jumpering R W W1 and Y Y2 simultaneously until status code 11 is flashed 9 10 9 Go to page numbe...

Страница 9: ...ly in only one of the twinned units 9 16 9 Are the fuses breakers or manual disconnects to the problem unit correctly set 11 10 10 Fix problem 5 11 Are the Auxiliary Limit switches properly set 12 10...

Страница 10: ...airflow when the G thermostat lead is disconnected and a call to dehumidify is active 12 13 12 Replace the variable speed furnace control 7 13 Reconnect the G thermostat lead or jumper and observe op...

Страница 11: ...HI solenoid in gas valve GV has failed or the furnace is extremely underfired STEP ACTION YES NO GO TO 1 Remove the blower access panel Disconnect the R thermostat lead from the furnace con trol board...

Страница 12: ...in Index for the CLEANUP AND STARTUP INSTRUC TIONS INDEX 5 Is setup switch SW1 6 in the ON position 6 7 6 Put setup switch SW1 6 in the OFF position 4 7 Jiggle setup switches SW1 1 and SW1 6 back and...

Страница 13: ...S 8 26 Power to the furnace was probably interrupted or line voltage was too low during a call for heat This is normal operation Go to the page number indicated in Index for the CLEANUP AND STARTUP IN...

Страница 14: ...code indicates the furnace failed to ignite gas and or prove flame in 4 attempts The variable speed furnace control will auto reset in 3 hours If the inducer motor is not running during lockout refer...

Страница 15: ...oving sensor electrode FSE 8 5 Does status code 22 stop flashing 6 7 6 Clean flame sensor with fine steel wool Inspect burner box assembly and remove any carbon deposits near the flame sensor opening...

Страница 16: ...t PL1 from variable speed furnace control 9 9 Do you have continuity between either RED wire connected to the limit circuit and chassis ground 10 3 10 You have a short circuit in the limit switch circ...

Страница 17: ...ure switch HPS and gas valve GV is shorting to ground Replace or repair it 11 45 Disconnect jumper wire across R W W1 and W2 thermostat terminals and wait until blower stops 46 46 Jumper R G and Y Y2...

Страница 18: ...chematic for the correct part number If absolutely necessary you can install two resistors into the PL4 connection on the control board R1 goes across the middle 2 pins and R2 goes across the outer 2...

Страница 19: ...lay is completed the variable speed will stop displaying status code 31 STEP ACTION YES NO GO TO 1 Turn power off remove blower access panel and disconnect the R thermostat lead from the furnace contr...

Страница 20: ...the high heat pressure switch HPS 12 Status Code 32 LOW HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED This status code can occur as a result of the low heat pressure switch LPS not making or the low...

Страница 21: ...l across heat exchangers when fault occurs 25 26 25 Replace the pressure switch assembly 8 26 Is inducer motor rotating in direction indicated on the inducer housing 28 27 27 Replace inducer motor or...

Страница 22: ...have continuity across limit switch LS 19 16 16 Wait for unit to cool then recheck for continuity across limit switch LS 17 17 Do you have continuity across limit switch LS 19 18 18 Replace limit swit...

Страница 23: ...low 210 deg F 18 56 56 The problem may be related to poor air distribution or excessive pressure drop across filter Check filter and return air grilles for blockage Add turning vanes more supply openi...

Страница 24: ...ed component 15 15 Fix problem 8 16 Put setup switch SW1 6 in the OFF position and jumper the R and W W1 thermostat ter minals 17 17 Is 24 vac across BLUE and GREEN YELLOW wire to gas valve GV 21 18 1...

Страница 25: ...sure within 4 seconds after the gas valve is energized Flame sensor location Air leakage around igniter bracket 8 48 Furnace will not operate or ignite on low heat Check the following Flame sensor loc...

Страница 26: ...te The voltage should be very stable and should not fluctuate more than 02 vdc If the voltage fluctuates get a different volt meter before going on to the following steps Note Since the variable speed...

Страница 27: ...rol module from motor portion of blower motor DO NOT PULL ON WIRES GRIP PLUG ONLY 42 42 When blower control module is completely detached from blower motor verify with stand ard ohmmeter that the resi...

Страница 28: ...29 Disconnect collector box tube to pressure switch assembly 30 30 Turn power on and jumper the R and W W1 thermostat terminals 31 31 Does status code 42 flash within 20 seconds after a call for heat...

Страница 29: ...ressure switch HPS makes 45 49 Status Code 43 LOW HEAT PRESSURE SWITCH OPEN WHILE HIGH HEAT PRESSURE SWITCH IS CLOSED This status code can occur as a result of the low heat pressure switch LPS not mak...

Страница 30: ...rol 8 19 Replace the low heat pressure switch or the pressure switch assembly 8 Status Code 45 CONTROL CIRCUITRY LOCKOUT This status code indicates the variable speed furnace control detected one of t...

Страница 31: ...ONNECTOR SW1 SETUP SWITCHES AND BLOWER OFF DELAY STATUS AND COMM LED LIGHTS 3 AMP FUSE TRANSFORMER 24 VAC CONNECTIONS PL3 ECM BLOWER HARNESS CONNECTOR PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR EAC 1 TERM...

Страница 32: ...32 A09683 Fig 2 Wiring Diagram PG9UAA...

Страница 33: ...en delivers requested airflow CFM as defined by serial commands received from the variable speed furnace control The ECM blower motor is configured via the variable speed furnace control to react to c...

Страница 34: ...LOW HEAT PRESSURE SWITCH Make Point Break Point Make Point Break Point 60 000 1 81 in W C max 1 63 in W C 0 05 0 86 in W C max 0 71 in W C 0 05 80 000 0 91 in W C max 0 76 in W C 0 05 100 000 0 95 in...

Страница 35: ...0 20 in w c Supply ESP before Coil 0 40 in w c Total ESP 0 60 in w c Example 2 Return ESP before Filter 0 10 in w c Filter Static Pressure Drop 2000 cfm 0 10 in w c Supply ESP after Coil 0 20 in w c...

Страница 36: ...ill work within the voltage range of 102 to 132 VAC Hence there is no voltage regulation circuits on the furnace control board A new Silicon Nitride igniter has a normal resistance range of 40 to 70 o...

Страница 37: ...rnace will do on a cold start coming out of night setback coming on in low heat and coming on in high heat EXAMPLE 1 Furnace ran for 16 minutes in low heat and 5 minutes in high heat during previous c...

Страница 38: ...f time as calculated by the following LH run time 5600 HL 122 Unit will initiate the next cycle in Low Heat for a maximum of 16 minutes before initiating High Heat if the call for heat still exists Un...

Страница 39: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Страница 40: ...s D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 10 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations...