background image

4

blower motor BLWM will transition to low-heat airflow
five seconds after the R to W2 circuit opens.

3. COOLING MODE

The thermostat ”calls for cooling”.

a. Single--Speed Cooling

The thermostat closes the R to G--and--Y circuits. The R to Y

circuit starts the outdoor unit, and the R to G-and-Y/Y2 circuits
start the furnace blower motor BLWM on cooling airflow. Cooling

airflow is based on the A/C selection shown in Table 1

.

The electronic air cleaner terminal EAC-1 is energized with 115

vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y circuits are

opened. The outdoor unit will stop, and the furnace blower motor

BLWM will continue operating at cooling airflow for an additional
90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling

off-delay to 5 seconds. (See Fig. 1.)

b. Single--Stage Thermostat and Two--Speed Cooling

(Adaptive Mode)

This furnace can operate a two--speed cooling unit with a

single--stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which

selects low--cooling or high--cooling operation. This selection is

based upon the stored history of the length of previous cooling
period of the single--stage thermostat.

Table 1 – Cooling Tonnage vs. Airflow (CFM)

525

700

700 
875  1050 

875 

700 

875

1050 

1050

1225 
1225 

1225 
1400 
1400 

1225 

1750

1750

1225 
1750 
2100 

DEF. 
DEF. 
DEF. 

040, 060, 3T-080 

5T-080, 100 

120 

BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF) 

SETUP SWITCH SW2/SW3 POSITIONS

 

 

MODEL 

SIZE 

 

600

800

800 

1000  1200 

1000 

800  1000

1200 

1200

1400 
1400 

1400 
1600 
1600 

1400 

2000

2000

1400 
2000 
2100 

DEF. 
DEF. 
DEF. 

040, 060, 3T-080 

5T-080, 100 

120 

BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON) 

1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION 

2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION 

3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM

 

SETUP SWITCH SW2/SW3 POSITIONS

 

 

MODEL 

SIZE 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

A10472

NOTE

: The air conditioning relay disable jumper ACRDJ must

be connected to enable the adaptive cooling mode in response to a
call for cooling. (See Fig. 1.) When in place the furnace control
CPU can turn on the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in either
low-- or high--cooling. If starting up in low--cooling, the furnace

control CPU determines the low--cooling on--time (from 0 to 20
minutes) which is permitted before switching to high--cooling.
If the power is interrupted, the stored history is erased and the

furnace control CPU will select low--cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the

Y/Y2 terminal and switch the outdoor unit to high--cooling, as
long as the thermostat continues to call for cooling. Subsequent

selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G--and--Y
circuits.

The R to Y1 circuit starts the outdoor unit on

low--cooling speed, and the R to G--and--Y1 circuits starts the

furnace blower motor BLWM at low--cooling airflow which is the
true on--board CF selection as shown in Table 1.
If the furnace control CPU switches from low--cooling to
high--cooling, the furnace control CPU will energize the air

conditioning relay ACR. When the air conditioning relay ACR is

energized the R to Y1--and--Y2 circuits switch the outdoor unit to
high--cooling speed, and the R to G--and--Y1--and--Y/Y2 circuits

transition the furnace blower motor BLWM to high--cooling
airflow. High--cooling airflow is based on the A/C selection shown

in Table 1.

NOTE

: When transitioning from low--cooling to high--cooling the

outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high--cooling
airflow.
The electronic air cleaner terminal EAC--1 is energized with 115

vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y circuit are

opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC--1 will remain energized

for an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off--delay to 5 seconds. (See Fig. 1.)

c. Two--Stage Thermostat and Two--Speed Cooling

NOTE

: The air conditioning relay disable jumper ACRDJ must

be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 1.)
The thermostat closes the R to G--and--Y1 circuits for low--cooling

or closes the R to G--and--Y1--and--Y2 circuits for high--cooling.

The R to Y1 circuit starts the outdoor unit on low--cooling speed,
and the R to G--and--Y1 circuit starts the furnace blower motor

BLWM at low--cooling airflow which is the true on--board CF
selection as shown in Table 1. The R to Y1--and--Y2 circuits start

the outdoor unit on high--cooling speed, and the R to G--and--Y/Y2

circuits start the furnace blower motor BLWM at high--cooling
airflow. High--cooling airflow is based on the A/C selection shown

in Table 1.
The electronic air cleaner terminal EAC--1 is energized with 115

vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y1 or
R to G--and--Y1--and--Y2 circuits are opened. The outdoor unit

stops, and the furnace blower BLWM and electronic air cleaner
terminal EAC--1 will remain energized for an additional 90

seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to
5 seconds. (See Fig. 1.)

4. DEHUMIDIFY MODE

The dehumidification output, DHUM on the thermostat should be

connected to the furnace control thermostat terminal DHUM.

When there is a dehumidify demand, the DHUM input is activated,
which means 24 vac signal is removed from the DHUM input

terminal. In other words, the DHUM input logic is reversed. The
DHUM input is turned ON when no dehumidify demand exists.

Once 24 vac is detected by the furnace control on the DHUM

input, the furnace control operates in Thermidistat mode. If the
DHUM input is low for more than 48 hours, the furnace control

reverts back to non--dehumidify mode.
The cooling operation described in Item 3 above also applies to

operation with a dehumidify enabled thermostat. The exceptions

are listed below:

a. When the R to G--and--Y1 circuit is closed and there is a

demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 86% of low--
cooling airflow which is the true on--board CF selection

as shown in Table 1.

b. When the R to G--and Y/Y2 circuit is closed and there is

a demand for dehumidification, the furnace blower
motor BLWM will drop the blower airflow to 86% of

Содержание PG9UAA

Страница 1: ...be performed by trained service personnel When working on heating equipment observe precautions in literature on tags and on labels attached to or shipped with the unit and other safety precautions th...

Страница 2: ...the switch Correct inadequate combustion air supply component failure before resetting the switch CAUTION Before operating the furnace check each manual reset switch for continuity If necessary press...

Страница 3: ...eat pressure switch HPS closes When the high heat pressure switch HPS closes the high heat gas valve solenoid GV HI is energized and the inducer motor RPM is noted by the furnace control CPU The RPM i...

Страница 4: ...If the furnace control CPU switches from low cooling to high cooling the furnace control CPU will energize the air conditioning relay ACR When the air conditioning relay ACR is energized the R to Y1 a...

Страница 5: ...ll continue operating for an additional 5 seconds if no other function requires blower motor BLWM operation a Continuous Blower Speed Selection from Thermostat To select different continuous blower ai...

Страница 6: ...Flame is proved while gas valve is de energized Inducer will run until fault is cleared Check for Leaky gas valve Stuck open gas valve 23 PRESSURE SWITCH DID NOT OPEN Check for Obstructed pressure tu...

Страница 7: ...ration or the inducer RPM signal was lost for 5 seconds during operation Check for Proper vent sizing Restricted combustion air supply Failed inducer motor Improper motor wiring 43 LOW HEAT PRESSURE S...

Страница 8: ...re erased after 72 hours or can be manually erased by putting setup switch SW1 1 in the ON position and jumpering R W W1 and Y Y2 simultaneously until status code 11 is flashed 9 10 9 Go to page numbe...

Страница 9: ...ly in only one of the twinned units 9 16 9 Are the fuses breakers or manual disconnects to the problem unit correctly set 11 10 10 Fix problem 5 11 Are the Auxiliary Limit switches properly set 12 10...

Страница 10: ...airflow when the G thermostat lead is disconnected and a call to dehumidify is active 12 13 12 Replace the variable speed furnace control 7 13 Reconnect the G thermostat lead or jumper and observe op...

Страница 11: ...HI solenoid in gas valve GV has failed or the furnace is extremely underfired STEP ACTION YES NO GO TO 1 Remove the blower access panel Disconnect the R thermostat lead from the furnace con trol board...

Страница 12: ...in Index for the CLEANUP AND STARTUP INSTRUC TIONS INDEX 5 Is setup switch SW1 6 in the ON position 6 7 6 Put setup switch SW1 6 in the OFF position 4 7 Jiggle setup switches SW1 1 and SW1 6 back and...

Страница 13: ...S 8 26 Power to the furnace was probably interrupted or line voltage was too low during a call for heat This is normal operation Go to the page number indicated in Index for the CLEANUP AND STARTUP IN...

Страница 14: ...code indicates the furnace failed to ignite gas and or prove flame in 4 attempts The variable speed furnace control will auto reset in 3 hours If the inducer motor is not running during lockout refer...

Страница 15: ...oving sensor electrode FSE 8 5 Does status code 22 stop flashing 6 7 6 Clean flame sensor with fine steel wool Inspect burner box assembly and remove any carbon deposits near the flame sensor opening...

Страница 16: ...t PL1 from variable speed furnace control 9 9 Do you have continuity between either RED wire connected to the limit circuit and chassis ground 10 3 10 You have a short circuit in the limit switch circ...

Страница 17: ...ure switch HPS and gas valve GV is shorting to ground Replace or repair it 11 45 Disconnect jumper wire across R W W1 and W2 thermostat terminals and wait until blower stops 46 46 Jumper R G and Y Y2...

Страница 18: ...chematic for the correct part number If absolutely necessary you can install two resistors into the PL4 connection on the control board R1 goes across the middle 2 pins and R2 goes across the outer 2...

Страница 19: ...lay is completed the variable speed will stop displaying status code 31 STEP ACTION YES NO GO TO 1 Turn power off remove blower access panel and disconnect the R thermostat lead from the furnace contr...

Страница 20: ...the high heat pressure switch HPS 12 Status Code 32 LOW HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED This status code can occur as a result of the low heat pressure switch LPS not making or the low...

Страница 21: ...l across heat exchangers when fault occurs 25 26 25 Replace the pressure switch assembly 8 26 Is inducer motor rotating in direction indicated on the inducer housing 28 27 27 Replace inducer motor or...

Страница 22: ...have continuity across limit switch LS 19 16 16 Wait for unit to cool then recheck for continuity across limit switch LS 17 17 Do you have continuity across limit switch LS 19 18 18 Replace limit swit...

Страница 23: ...low 210 deg F 18 56 56 The problem may be related to poor air distribution or excessive pressure drop across filter Check filter and return air grilles for blockage Add turning vanes more supply openi...

Страница 24: ...ed component 15 15 Fix problem 8 16 Put setup switch SW1 6 in the OFF position and jumper the R and W W1 thermostat ter minals 17 17 Is 24 vac across BLUE and GREEN YELLOW wire to gas valve GV 21 18 1...

Страница 25: ...sure within 4 seconds after the gas valve is energized Flame sensor location Air leakage around igniter bracket 8 48 Furnace will not operate or ignite on low heat Check the following Flame sensor loc...

Страница 26: ...te The voltage should be very stable and should not fluctuate more than 02 vdc If the voltage fluctuates get a different volt meter before going on to the following steps Note Since the variable speed...

Страница 27: ...rol module from motor portion of blower motor DO NOT PULL ON WIRES GRIP PLUG ONLY 42 42 When blower control module is completely detached from blower motor verify with stand ard ohmmeter that the resi...

Страница 28: ...29 Disconnect collector box tube to pressure switch assembly 30 30 Turn power on and jumper the R and W W1 thermostat terminals 31 31 Does status code 42 flash within 20 seconds after a call for heat...

Страница 29: ...ressure switch HPS makes 45 49 Status Code 43 LOW HEAT PRESSURE SWITCH OPEN WHILE HIGH HEAT PRESSURE SWITCH IS CLOSED This status code can occur as a result of the low heat pressure switch LPS not mak...

Страница 30: ...rol 8 19 Replace the low heat pressure switch or the pressure switch assembly 8 Status Code 45 CONTROL CIRCUITRY LOCKOUT This status code indicates the variable speed furnace control detected one of t...

Страница 31: ...ONNECTOR SW1 SETUP SWITCHES AND BLOWER OFF DELAY STATUS AND COMM LED LIGHTS 3 AMP FUSE TRANSFORMER 24 VAC CONNECTIONS PL3 ECM BLOWER HARNESS CONNECTOR PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR EAC 1 TERM...

Страница 32: ...32 A09683 Fig 2 Wiring Diagram PG9UAA...

Страница 33: ...en delivers requested airflow CFM as defined by serial commands received from the variable speed furnace control The ECM blower motor is configured via the variable speed furnace control to react to c...

Страница 34: ...LOW HEAT PRESSURE SWITCH Make Point Break Point Make Point Break Point 60 000 1 81 in W C max 1 63 in W C 0 05 0 86 in W C max 0 71 in W C 0 05 80 000 0 91 in W C max 0 76 in W C 0 05 100 000 0 95 in...

Страница 35: ...0 20 in w c Supply ESP before Coil 0 40 in w c Total ESP 0 60 in w c Example 2 Return ESP before Filter 0 10 in w c Filter Static Pressure Drop 2000 cfm 0 10 in w c Supply ESP after Coil 0 20 in w c...

Страница 36: ...ill work within the voltage range of 102 to 132 VAC Hence there is no voltage regulation circuits on the furnace control board A new Silicon Nitride igniter has a normal resistance range of 40 to 70 o...

Страница 37: ...rnace will do on a cold start coming out of night setback coming on in low heat and coming on in high heat EXAMPLE 1 Furnace ran for 16 minutes in low heat and 5 minutes in high heat during previous c...

Страница 38: ...f time as calculated by the following LH run time 5600 HL 122 Unit will initiate the next cycle in Low Heat for a maximum of 16 minutes before initiating High Heat if the call for heat still exists Un...

Страница 39: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Страница 40: ...s D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 10 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations...

Отзывы: