VVT Zone Controller
65
Alarms
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Alarms
HOME
>
ALARM
Point Name/Description
Range
Space Temperature
– Indicates if the space temperature exceeds the high or low alarm limit. R:
Normal/Alarm
Alarming Temperature
– Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the
Space Temperature
alarm (above)
is in
Alarm
.
R:
-56 to 245°F
Alarm Limit Exceeded
– Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the
Space
Temperature
alarm (above) is in
Alarm
.
R:
-56 to 245°F
Space Temp Sensor –
Indicates if the space temperature sensor fails.
R:
Normal/Alarm
Indoor Air Quality
– Indicates if the occupied CO
2
R:
level exceeds the
Occupied High CO2
Alarm Limit
.
Normal/Alarm
Supply Air Temperature
– Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
R:
Normal/Alarm
Filter
– Indicates if the filter's runtime hours exceeds the runtime alarm limit.
R:
Clean/Dirty
Space Relative Humidity
– Indicates if the relative humidity exceeds the high RH alarm limit. R:
Normal/Alarm
Network OAT -
Indicates if the controller is not receiving a valid OAT value over the network. R:
Normal/Alarm
Airside Linkage Status
– If the controller is the VVT Master,
Alarm
indicates that it lost
Linkage communications with the air source. If the controller is a slave,
Alarm
indicates that
it lost Linkage communications with the VVT master.
R:
Normal/Alarm
Linkage
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Linkage
HOME
>
CONFIG
>
LINKAGE
Point Name/Description
Default/Range
Airside Linkage
Click
Linkage Collector/Linkage Provider
to access the microblock popup's
Summary
and
Details
tabs. See the microblock popup's Help files for more detailed
explanations.
Linkage
Collector
– Set the
Number of Providers
to the total number of controllers in
the linked system, including the bypass and VVT Master.
D:
R:
1
1 to 32