VVT Zone Controller
31
Point Name/Description
Default/Range
Hysteresis
For example, the following graph shows the zone color that results as the zone
temperature departs from and returns to the acceptable range in a zone with the
following settings:
– The desired difference between the temperature at which the zone color
changes as the zone temperature departs from the acceptable range between the
heating and cooling setpoints (green) into the Cooling 1 (yellow) or Heating 1 (light
blue) and the temperature at which the zone color changes back to the acceptable
range between the heating and cooling setpoints.
•
Color Change Hysteresis = .5° (applies as the temperature returns to the
acceptable range)
•
Occupied cooling setpoint = 76°
•
Occupied heating setpoint = 70°
Time
Temp
Occupied heating setpoint: 70°
75.5°
70.5°
Occupied cooling setpoint: 76°
.5° hysteresis
.5° hysteresis
D:
R:
0.5°F
0.2 to 1.0°F
Learning Adaptive Optimal Start
– This function gradually adjusts the unoccupied setpoints over a specified period of time to
achieve the occupied setpoint by the time scheduled occupancy begins. This learning adaptive algorithm uses the
learned
heating capacity
and
learned cooling capacity
values to calculate the effective setpoints prior to the occupied start time. The
algorithm calculates a learned cooling and heating capacity during the previous unoccupied time. Set the
Learning Adaptive
Optimal Start
recovery period from 1 to 4 hours in
Optimal Start
. When the
Learning Adaptive Optimal Start
routine runs,
adjustments are based on the color that is achieved when occupancy begins. Adjustment amounts are defined in the
thermographic color fields located directly above the
Effective Set Points
graph under
Setpoints
.
Effective Setpoints
The Effective Setpoints graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current
programmed setpoints plus the offset of any setpoint adjustment that may be in affect. If unoccupied, the values are the
programmed unoccupied setpoints.
Heating –
(Occupied or Unoccupied, depending on mode) The current programmed
Heating
R:
setpoint adjusted by any offset that may be in effect.
0 to 120°F
Cooling –
(Occupied or Unoccupied, depending on mode) The current programmed
Cooling
R:
setpoint adjusted by any offset that may be in effect.
0 to 120°F