Installation
6
VVT Zone Controller
To install the VVT Zone Controller:
1
Mount the controller to the VVT box.
(page 7)
2
Wire the controller for power.
(page 8)
3
Set the controller's address.
(page 9)
4
Wire the controller to the MS/TP network.
(page 10)
5
Wire sensor(s) to the controller.
(page 11)
6
Wire equipment to the controller's outputs.
(page 21)
Field-supplied hardware
Each zone controller installation requires the following field-supplied components:
•
zone terminal unit
•
round or rectangular mounting bracket
•
space temperature sensor
•
supply air temperature sensor
•
4x2-in. electrical box
•
transformer— 24 Vac, 40 VA
•
two no. 10 x 1/2-in. sheet metal screws (to secure SAT sensor to duct)
•
two no. 6-32 x 5/8-in. screws (to mount space temperature sensor base to electrical box)
•
wiring
•
bushings (required when mounting SAT sensor in a duct 6-in. or less in diameter)
Optional:
•
contactors (if required for fan or electric heat)
•
indoor air quality sensor
•
relative humidity sensor
•
2 screws and 2 hollow wall anchors (to mount relative humidity sensor directly to wall)
•
valve and actuator for hot water heat (if required)
Installation