43
Master Chiller
Control
Box
Control
Box
Slave Chiller
Pump and Check Valve
or Isolation Valve
Dual Chiller
LWT Sensors
and Wells
Pump and Check Valve
or Isolation Valve
a30-3987ef
LEGEND
NOTE: This is a simplified piping diagram — not all hydronic spe-
cialties are shown.
Fig. 34 — Dual Chiller Control Option Thermistor
Location
LWT
—
Leaving Water (Fluid) Temperature
Field Wiring
Field Communication Wiring
a30-3185ef
Tank Installation
BAD
BAD
GOOD
GOOD
Fig. 35 — Tank Baffling
Distribution Pump
Expansion
Tank(s)
Air Separator
with Vent
Decoupler
Chiller 1
Chiller 2
Zone 1
Zone 2
Zone 3
NOTE: Expansion tanks for 30RB hydronic kits must be installed for chillers piped in parallel in the primary water loop.
Fig. 36 — Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems
a30-4002ef