3. Fused heaters: (See Fig. 8, 12, 13, and 14.)

a. The 15- and 20-kw heaters can be wired for single- or dual-supply circuits. Single-supply circuit wiring requires a factory-authorized,

single-point adapter kit.

b. The 24- and 30-kw heaters can be wired for single- or multiple-supply circuits. Heaters are factory wired for single circuit 3 phase. To

convert heaters to single circuit single phase, disconnect yellow lead from L3 and connect to L1. Disconnect black lead from L3 and
connect to L2. To convert heaters to multiple-supply circuit single phase, remove and discard leads between single-circuit terminal block
and fuse block. Remove and discard single-circuit terminal block. Attach L1 through L6 power leads as indicated on label next to fuse
block.

Fig. 8—15 and 20kw Fused Heaters

(15 and 20kw fused heaters are factory wired for dual

supply circuits. Single supply circuit is possible

with approved single point wiring kit.)

A00078

Field Ground

Wiring

L4

L2

Field Ground

Wiring

L1

L3

Circuit 1 : L1-L2

Circuit 2 : L3-L4

Ground lug

Ground lug

Field P

o

w

e

r

Wir

ing

Fig. 6—3, 5, 8, 9, 10kw Non-fused Heaters

(9kw is field convertible to 3-phase.

See Procedure 3. B. 1. c.)

A00076

Yellow

Black

Ground

Lug

Field

Ground

Wiring

L1

L2

Field

Power

Wiring

Fig. 9—15 and 20kw Circuit Breaker Heaters

A00079

Field Ground

Wiring

L1

L2

Field Ground

Wiring

L3

L4

Circuit 1 : L1-L2

Circuit 2 : L3-L4

ON

OFF

ON

OFF

Field P

o

w

e

r

Wir

ing

Ground lug

Ground lug

Fig. 7—5, 8, 10kw Circuit Breaker

and Disconnect Heaters

A00077

Ground

Lug

Field

Power

Wiring

Field

Ground

Wiring

ON

OFF

L1

L2

—7—

Содержание KFCEH0401N03

Страница 1: ...or personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe...

Страница 2: ...B PF SIZE MODEL FC SIZE MODEL FH SIZE MODEL FX SIZE MODEL FE4 FK4 FV4 40FK SIZE FK FV 40FK INTELLIGENT HEAT CAPABLE 1 Phase KFCEH0401N03 3 Non fused 018 024 024 001 NO KFCEH0501N05 KFCEH2401C05 5 Non...

Страница 3: ...w Bezel mounts on the outside of the blower door See Fig 4 a Cut insulation away from rectangular access hole in blower access panel b Remove adhesive backing from window bezel and from the outside In...

Страница 4: ...0 Table 4 Smart Heat Electrical Data HEATER PART NO KW PHASE INTERNAL CIRCUIT PROTECTION HEATER AMPS 208 230V MIN AMPACITY 208 230V BRANCH CIRCUIT Min Wire Size AWG 208 230v Min Gnd Wire Size 208 230v...

Страница 5: ...230 v terminal and reconnect it to 208 v terminal See Fig 5 The secondary circuit of transformer is protected by a 5 amp fuse mounted on PCB CAUTION On FA FB FC FH FX or PF1MNB018 070 if W2 W3 and E...

Страница 6: ...jumper uncut the time delay allows the second stage heat to be energized approximately 5 sec after the first stage On 18 24 and 30kw heaters the third stage relay board jumper is cut at factory This...

Страница 7: ...Attach L1 through L6 power leads as indicated on label next to fuse block Fig 8 15 and 20kw Fused Heaters 15 and 20kw fused heaters are factory wired for dual supply circuits Single supply circuit is...

Страница 8: ...e Phase Single Supply Circuit Field Modified A00083 Field Ground Wiring L1 L2 Field Power Wiring Ground lug Fig 11 18kw 3 Phase Heater A00081 Field Ground Wiring L2 L3 Field Power Wiring L1 Ground lug...

Страница 9: ...it breaker mounting bracket for dual circuit grounding See Fig 3 3 For 15 and 20 kw fused heaters an additional ground lug is provided on fuse mounting bracket for dual circuit grounding See Fig 2 4 F...

Страница 10: ...eater rating label included with kit over existing electrical information label located on front access panel of fan coil See Fig 17 If kit contains multiple rating labels ensure correct label is appl...

Страница 11: ...980 1085 1250 1100 1100 1250 1225 1225 1250 42 000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460 UNIT FAN SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER KW RANGE 0 10 0 15 0 20 0 30 LO...

Страница 12: ...FE4A FV4B 40FK PF1MNB071 Minimum CFM for Electric Heater Application CFM Electric Heating Modes FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE KW 5 8 9 10 15 18 20 24 30 001 002 Heater Only 625 625...

Отзывы: