Carrier KFCEH0401N03 Скачать руководство пользователя страница 6

3. Heater staging

The units are shipped circuited for single-stage operation. Use outdoor thermostat kit Part No. KHAOT0301FST for 2-stage operation. Use
both kit Part No. KHAOT0201SEC and KHAOT0301FST for 3-stage operation. When 2-stages are desired, cut W3 at the W2 wire nut,
strip and reconnect per wiring staging layout in Installation Instructions for fan coils.

a. The 3-, 5-, 8-, and 10-kw heaters are single stage only.

b. The 9- and 15-kw heaters are adaptable for 2-stage operation.

c. The 18-, 20-, 24-, and 30-kw heaters are adaptable for 3-stage operation.

4. Intelligent Heat Staging

40FK, FK4, and FV4 Fan Coils are capable of Intelligent Heat Staging when installed with capable electric heaters (See Table 1) and a
corporate 2-speed programmable thermostat (TSTATXXP2S01-B), Thermidistat™ Control (TSTATXXPRH01-B), or Comfort Zone
II/Zone Perfect Plus. Consult the fan coil Installation and Set-up Instructions for wiring details. Do not install with outdoor thermostats when
installing for Intelligent Heat Staging.

5. Rectifier and Time Delay Boards

Each heater element is controlled by a relay mounted on the heater panel. The relay has a 24v DC coil. Each relay has a small rectifier board
attached directly to relay coil terminals. The rectifier board converts incoming 24v AC control signal to DC. Some heaters may have up
to three relays. The second and/or third relay rectifier board also has a time delay feature and a small jumper wire built into it. With the
jumper uncut, the time delay allows the second stage heat to be energized approximately 5 sec after the first stage. On 18, 24, and 30kw
heaters, the third stage relay board jumper is cut at factory. This provides an 8 sec delay after first stage relay closes.

B.

Power Connections

NOTE:

Heater supply circuit wire size and overcurrent protection must comply with National Electrical Code (NEC) and UL branch circuit

requirements. (See Table 3, 4, and 5.) Wires and overcurrent protection, integral to the heater, are not required to meet branch circuit requirements.
Internal circuit protection of 60 amps (maximum) is acceptable.

1. Unprotected heaters: (See Fig. 6, 10, and 11.)

a. The 5- through 10-kw single-phase and 15- and 18-kw 3-phase heaters can be wired for single-supply circuit only. Supply circuit

connects to heater pigtail leads (terminal block on 18-kw heaters).

b. The 3- through 10-kw single-phase heaters can use a separate field-installed, factory-authorized disconnect kit which installs in fan coil.

NOTE:

Refer to wiring label for component locations.

c. The 9-kw heater is factory wired for single supply circuit, single phase. To convert heater to single supply circuit, 3 phase:

(1.) Disconnect blue wire from limit switch (LS3). Cut, strip, and connect to field wire L3.

(2.) Disconnect yellow wire from LS1 and connect to LS3.

(3.) Disconnect blue wire from relay 2 terminal 2 and connect to LS1.

2. Circuit breaker heaters: (See Fig. 7 and 9.)

a. The 3- through 10-kw heaters can be wired for single-supply circuit only.

b. The 15- and 20-kw heaters can be wired for dual-supply circuits only.

Fig. 5—Connection of Transformer

A94067

230

C

208

BRN
RED

YEL
BLK

SECONDARY

PRIMARY

—6—

Содержание KFCEH0401N03

Страница 1: ...or personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe...

Страница 2: ...B PF SIZE MODEL FC SIZE MODEL FH SIZE MODEL FX SIZE MODEL FE4 FK4 FV4 40FK SIZE FK FV 40FK INTELLIGENT HEAT CAPABLE 1 Phase KFCEH0401N03 3 Non fused 018 024 024 001 NO KFCEH0501N05 KFCEH2401C05 5 Non...

Страница 3: ...w Bezel mounts on the outside of the blower door See Fig 4 a Cut insulation away from rectangular access hole in blower access panel b Remove adhesive backing from window bezel and from the outside In...

Страница 4: ...0 Table 4 Smart Heat Electrical Data HEATER PART NO KW PHASE INTERNAL CIRCUIT PROTECTION HEATER AMPS 208 230V MIN AMPACITY 208 230V BRANCH CIRCUIT Min Wire Size AWG 208 230v Min Gnd Wire Size 208 230v...

Страница 5: ...230 v terminal and reconnect it to 208 v terminal See Fig 5 The secondary circuit of transformer is protected by a 5 amp fuse mounted on PCB CAUTION On FA FB FC FH FX or PF1MNB018 070 if W2 W3 and E...

Страница 6: ...jumper uncut the time delay allows the second stage heat to be energized approximately 5 sec after the first stage On 18 24 and 30kw heaters the third stage relay board jumper is cut at factory This...

Страница 7: ...Attach L1 through L6 power leads as indicated on label next to fuse block Fig 8 15 and 20kw Fused Heaters 15 and 20kw fused heaters are factory wired for dual supply circuits Single supply circuit is...

Страница 8: ...e Phase Single Supply Circuit Field Modified A00083 Field Ground Wiring L1 L2 Field Power Wiring Ground lug Fig 11 18kw 3 Phase Heater A00081 Field Ground Wiring L2 L3 Field Power Wiring L1 Ground lug...

Страница 9: ...it breaker mounting bracket for dual circuit grounding See Fig 3 3 For 15 and 20 kw fused heaters an additional ground lug is provided on fuse mounting bracket for dual circuit grounding See Fig 2 4 F...

Страница 10: ...eater rating label included with kit over existing electrical information label located on front access panel of fan coil See Fig 17 If kit contains multiple rating labels ensure correct label is appl...

Страница 11: ...980 1085 1250 1100 1100 1250 1225 1225 1250 42 000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460 UNIT FAN SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER KW RANGE 0 10 0 15 0 20 0 30 LO...

Страница 12: ...FE4A FV4B 40FK PF1MNB071 Minimum CFM for Electric Heater Application CFM Electric Heating Modes FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE KW 5 8 9 10 15 18 20 24 30 001 002 Heater Only 625 625...

Отзывы: