PROCEDURE 2—ATTACH FUSE BOX OR CIRCUIT BREAKER BOX

1. For 15- and 20-kw fused models:

After installing heater assembly, attach fuse assembly to side of fan coil unit by inserting fuse box tab between insulation and to left side
of unit and fan deck. Mount front of assembly to side flange with 2 screws provided. On fan coil units size 042 and larger, remove wire
tie that shortens wire length between heater and fuses. Fuse cover is closed by engaging dimples in fuse box. (See Fig. 2.)

2. For 24- and 30-kw fused models:

Fuse assembly is mounted on heater. Be sure fuse cover is closed by engaging clip latch on unit top panel. (See Fig. 1.)

WARNING: Ensure fuse box is closed before power is turned to ON position. Electrical shock may cause personal

injury or death.

3. For 5- through 20-kw circuit breaker models:

After installing heater assembly, attach circuit breaker assembly to unit with screws provided. (See Fig. 3.) On fan coil units size 042 and
larger, remove wire tie that shortens wire length between heater and circuit breaker assembly to allow mounting of circuit breaker assembly.
(See Fig. 3.)

4. Circuit breaker models require installing a window bezel in unit door to provide safe access to circuit breakers. The Window Bezel mounts

on the outside of the blower door. (See Fig. 4.)

a. Cut insulation away from rectangular access hole in blower access panel.

b. Remove adhesive backing from window bezel and from the outside. Insert the window through the rectangular hole and seat firmly on

the door surface. Press firmly in place to seat the adhesive. (See Fig. 4.)

PROCEDURE 3—ELECTRICAL CONNECTIONS

Refer to unit instructions for recommended wiring procedures. Install wiring in accordance with all applicable local and national codes. (See Tables
3, 4, and 5.)

Connect heater wiring harness plug to receptacle on PCB or wire harness. A positive connection must be made between plug and receptacle. Plug
will interlock with receptacle when properly seated. Harness contains both 24-v control and high-voltage wiring. Blower power is provided through
heater harness.

NOTE:

Units with or without electric heaters require a minimum CFM. Refer to unit wiring label to ensure the fan speed selected with electric

heaters is equal to or greater than the minimum fan speed indicated. The minimum CFM for cooling is determined by the outdoor unit requirements.
Use the higher of the 2 for year-round operation.

Fig. 2—Installation of Fused Model Heater

A90151

DUAL-CIRCUIT

GROUND LUG

FUSE BOX

DIMPLE

FUSE BOX TAB

SINGLE-CIRCUIT

GROUND LUG

INSERT FUSE

BOX TAB HERE

COVER PLATE
OR
KNOCKOUT

FUSE COVER

WIRE TIE
(REMOVE ON
LARGE FAN COILS)

HEATER/CUTOUT 
COVER

—3—

Содержание KFCEH0401N03

Страница 1: ...or personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe...

Страница 2: ...B PF SIZE MODEL FC SIZE MODEL FH SIZE MODEL FX SIZE MODEL FE4 FK4 FV4 40FK SIZE FK FV 40FK INTELLIGENT HEAT CAPABLE 1 Phase KFCEH0401N03 3 Non fused 018 024 024 001 NO KFCEH0501N05 KFCEH2401C05 5 Non...

Страница 3: ...w Bezel mounts on the outside of the blower door See Fig 4 a Cut insulation away from rectangular access hole in blower access panel b Remove adhesive backing from window bezel and from the outside In...

Страница 4: ...0 Table 4 Smart Heat Electrical Data HEATER PART NO KW PHASE INTERNAL CIRCUIT PROTECTION HEATER AMPS 208 230V MIN AMPACITY 208 230V BRANCH CIRCUIT Min Wire Size AWG 208 230v Min Gnd Wire Size 208 230v...

Страница 5: ...230 v terminal and reconnect it to 208 v terminal See Fig 5 The secondary circuit of transformer is protected by a 5 amp fuse mounted on PCB CAUTION On FA FB FC FH FX or PF1MNB018 070 if W2 W3 and E...

Страница 6: ...jumper uncut the time delay allows the second stage heat to be energized approximately 5 sec after the first stage On 18 24 and 30kw heaters the third stage relay board jumper is cut at factory This...

Страница 7: ...Attach L1 through L6 power leads as indicated on label next to fuse block Fig 8 15 and 20kw Fused Heaters 15 and 20kw fused heaters are factory wired for dual supply circuits Single supply circuit is...

Страница 8: ...e Phase Single Supply Circuit Field Modified A00083 Field Ground Wiring L1 L2 Field Power Wiring Ground lug Fig 11 18kw 3 Phase Heater A00081 Field Ground Wiring L2 L3 Field Power Wiring L1 Ground lug...

Страница 9: ...it breaker mounting bracket for dual circuit grounding See Fig 3 3 For 15 and 20 kw fused heaters an additional ground lug is provided on fuse mounting bracket for dual circuit grounding See Fig 2 4 F...

Страница 10: ...eater rating label included with kit over existing electrical information label located on front access panel of fan coil See Fig 17 If kit contains multiple rating labels ensure correct label is appl...

Страница 11: ...980 1085 1250 1100 1100 1250 1225 1225 1250 42 000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460 UNIT FAN SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER KW RANGE 0 10 0 15 0 20 0 30 LO...

Страница 12: ...FE4A FV4B 40FK PF1MNB071 Minimum CFM for Electric Heater Application CFM Electric Heating Modes FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE KW 5 8 9 10 15 18 20 24 30 001 002 Heater Only 625 625...

Отзывы: