Table 8—FE4A Fan Coil Airflow Delivery (cfm) -- Electric Heating Modes

MODEL

FE4A

OUTDOOR

UNIT

CAPACITY

BTUH

ELECTRIC HEATER KW RANGE

3,5

8,9,10

15

18,20

002

EMERGENCY

625

650

825

1025

18,000

650

650

--

--

24,000

675

775

900

--

30,000

850

950

1050

1125

36,000

1000

1050

1125

1225

003

EMERGENCY

675

725

850

1100

24,000

675

875

900

--

30,000

850

950

1100

1150

36,000

1025

1075

1150

1275

42,000

1150

1200

1300

1400

MODEL

FE4A

OUTDOOR

UNIT

CAPACITY

BTUH

ELECTRIC HEATER KW RANGE

3,5

8,9,10

15

18,20

24,30

005

EMERGENCY

675

725

850

1100

1600

30,000

850

950

1100

1150

--

36,000

1025

1075

1150

1275

--

42,000

1150

1200

1300

1400

--

48,000

1325

1325

1400

1500

1600

006

EMERGENCY

1050

1050

1050

1100

1750

36,000

1150

1150

1350

1350

--

42,000

1150

1150

1350

1575

--

48,000

1325

1325

1400

1500

1750

60,000

1650

1650

1650

1750

1750

Table 9—FK4D, FE4A, FV4B, 40FK, PF1MNB071 Minimum CFM for Electric Heater Application (CFM) - Electric Heating Modes

FAN

COIL
UNIT

HEAT PUMP

UNIT

SIZE

CFM

HEATER SIZE KW

5

8, 9, 10

15

18, 20

24, 30

001
002

Heater Only

625

625

725

875

018

625

625

024

650

725

875

030

800

875

875

1040

036

970

970

970

1040

003

Heater Only

675

700

850

1050

024

675

875

875

030

800

875

1100

1150

036

975

975

1100

1225

042

1125

1125

1125

1225

005

Heater Only

675

700

850

1050

1400

030

800

875

875

1150

036

975

975

1100

1225

042

1125

1125

1125

1225

048

1305

1305

1305

1305

1400

006
071

Heater Only

1050

1050

1050

1050

1750

036

1100

1100

1350

1350

042

1125

1125

1350

1350

048

1300

1300

1350

1465

1750

060

1625

1625

1625

1750

1750

NOTES:
1. Heater Only—Air conditioner with electric heater application.
2. These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow delivery chart for Electric Heating Modes.

© 2003 CAC/BDP

7310 W. Morris St., Indianapolis, IN 46231

agfceh09

—12—

Book/Tab 1/3d, 4/2e

Catalog No. 63FC-EH7

Содержание KFCEH0401N03

Страница 1: ...or personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe...

Страница 2: ...B PF SIZE MODEL FC SIZE MODEL FH SIZE MODEL FX SIZE MODEL FE4 FK4 FV4 40FK SIZE FK FV 40FK INTELLIGENT HEAT CAPABLE 1 Phase KFCEH0401N03 3 Non fused 018 024 024 001 NO KFCEH0501N05 KFCEH2401C05 5 Non...

Страница 3: ...w Bezel mounts on the outside of the blower door See Fig 4 a Cut insulation away from rectangular access hole in blower access panel b Remove adhesive backing from window bezel and from the outside In...

Страница 4: ...0 Table 4 Smart Heat Electrical Data HEATER PART NO KW PHASE INTERNAL CIRCUIT PROTECTION HEATER AMPS 208 230V MIN AMPACITY 208 230V BRANCH CIRCUIT Min Wire Size AWG 208 230v Min Gnd Wire Size 208 230v...

Страница 5: ...230 v terminal and reconnect it to 208 v terminal See Fig 5 The secondary circuit of transformer is protected by a 5 amp fuse mounted on PCB CAUTION On FA FB FC FH FX or PF1MNB018 070 if W2 W3 and E...

Страница 6: ...jumper uncut the time delay allows the second stage heat to be energized approximately 5 sec after the first stage On 18 24 and 30kw heaters the third stage relay board jumper is cut at factory This...

Страница 7: ...Attach L1 through L6 power leads as indicated on label next to fuse block Fig 8 15 and 20kw Fused Heaters 15 and 20kw fused heaters are factory wired for dual supply circuits Single supply circuit is...

Страница 8: ...e Phase Single Supply Circuit Field Modified A00083 Field Ground Wiring L1 L2 Field Power Wiring Ground lug Fig 11 18kw 3 Phase Heater A00081 Field Ground Wiring L2 L3 Field Power Wiring L1 Ground lug...

Страница 9: ...it breaker mounting bracket for dual circuit grounding See Fig 3 3 For 15 and 20 kw fused heaters an additional ground lug is provided on fuse mounting bracket for dual circuit grounding See Fig 2 4 F...

Страница 10: ...eater rating label included with kit over existing electrical information label located on front access panel of fan coil See Fig 17 If kit contains multiple rating labels ensure correct label is appl...

Страница 11: ...980 1085 1250 1100 1100 1250 1225 1225 1250 42 000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460 UNIT FAN SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER KW RANGE 0 10 0 15 0 20 0 30 LO...

Страница 12: ...FE4A FV4B 40FK PF1MNB071 Minimum CFM for Electric Heater Application CFM Electric Heating Modes FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE KW 5 8 9 10 15 18 20 24 30 001 002 Heater Only 625 625...

Отзывы: