INTRODUCTION

This instruction describes the installation of Part No. KFCEH accessory heaters in FA, FB, FC, FH, FX, and PF1MNB018-070 fan coils and in
the FE4, FK4, FV4, 40FK, and PF1MNA071 fan coils.

NOTE:

Electric heaters require a minimum airflow. Minimum airflow and motor speed selection are listed in Table 2. For 3- through 18-kw

standard heaters there are no clearance requirements for the first 36 in. of ductwork. For 20- through 30-kw heaters, a 1-in. clearance is required
for the first 36 in. of ductwork.

INSTALLATION

PROCEDURE 1—INSTALL ELECTRIC HEATER ASSEMBLY

NOTE:

Ensure heater coils are not deformed or damaged during heater installation.

1. Make sure power to unit is off.

2. Remove blower access panel of fan coil unit.

CAUTION: Before installation of heater, the black and yellow pigtail leads must be removed from the fan coil PCB or

wire harness to prevent possible damage to the product. Electrical power will be provided to the board through the heater
circuit plug.

3. Disconnect 2 power wires (black and yellow pigtail leads) from PCB or wire harness (if applicable) and discard. Wires may be part of a

plug assembly or attached to terminals L1 and L2. Remove cooling control plate from fan coil (if equipped). For 18-, 24-, and 30-kw heaters,
remove adapter plate. (See Fig. 1.)

4. Insert heater assembly into front of fan coil so that element rods engage holes in rear heat shield.

5. Attach heater control plate to fan coil using 2 screws provided. For 18-, 24-, and 30-kw heater models, attach front of heater to fan deck

using third screw. (See Fig. 1.)

Table 1—Accessory Heater Usage

ELECTRIC HEATER

PART NO.

KW

INTERNAL

PROTECTION

MODEL FA, FB, PF

SIZE

MODEL FC

SIZE

MODEL FH

SIZE

MODEL FX

SIZE

MODEL

FE4, FK4, FV4, 40FK

SIZE

FK, FV, 40FK

INTELLIGENT

HEAT CAPABLE

1 Phase

KFCEH0401N03

3

Non-fused

018, 024

024

001

NO

KFCEH0501N05
KFCEH2401C05

5

Non-fused

Circuit Breaker

018-071

024-070

001-004

030-060

001-006

NO
NO

KFCEH0801N08
KFCEH2501C08

8

Non-fused

Circuit Breaker

018-071

024-070

001-004

030-060

001-006

NO
NO

KFCEH2901N09

9*

Non-fused

036-071

036-070

002-004

036-060

003-006

YES†

KFCEH0901N10
KFCEH2601C10

10

Non-fused

Circuit Breaker

018-071

024-070

001-004

030-060

001-006

NO
NO

KFCEH3001F15

KFCEH2701C15
KFCEH3101C15

15

Fused

Circuit Breaker
Circuit Breaker

024-071

024-070

001-004

030-060

001-006

YES†
YES†
YES†

KFCEH3201F20

KFCEH2801C20
KFCEH3301C20

20

Fused

Circuit Breaker
Circuit Breaker

030-071

030-070

002-004

030-060

001-006

YES†
YES†
YES†

3 Phase Only

KFCEH1601315

15

Non-fused

036-071

036-070

002-004

036-060

001-006

NO

KFCEH2001318

18

Non-fused

042-071

042-070

003, 004

042-060

003-006

NO

3 Phase, Factory Shipped‡

KFCEH3401F24
KFCEH3501F30

24
30

Fused
Fused

048-071

048-070

003, 004

048-060

005, 006

YES†
YES†

† These heaters are Intelligent Heat capable when used with the FK4, FV4, and 40FK fan coils and corporate 2-speed programmable thermostat (TSTATXXP2S01-B),
Thermidistat™ Control (TSTATXXPRH01-B), or capable zoning system.
‡ Field convertible to 1 phase, single or multiple supply circuit.
* Field convertible to 3 phase.

Table 2—Minimum CFM and Motor Speed Selection

FAN COIL

SIZES

FA, FB, FC, FH, FX,

PF

HEATER KW

3

5

8

9

10

15

18

20

24

30

018

525

525

525

600*

024

700

700

700

700

700

775*

030, 033

875

875

875

875

875

1060*

036, 038,

1050

970

970

970

920

1040

042

1225

1225

1225

1225

1225

1225

1225

048, 054,

1400

1400

1400

1400

1400

1400

1400

1400

1400

060, 070,

1750

1750

1750

1750

1750

1750

1750

1750

1750

* Indicates medium speed (blue). All other motor speeds at low tap.

—2—

Содержание KFCEH0401N03

Страница 1: ...or personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe...

Страница 2: ...B PF SIZE MODEL FC SIZE MODEL FH SIZE MODEL FX SIZE MODEL FE4 FK4 FV4 40FK SIZE FK FV 40FK INTELLIGENT HEAT CAPABLE 1 Phase KFCEH0401N03 3 Non fused 018 024 024 001 NO KFCEH0501N05 KFCEH2401C05 5 Non...

Страница 3: ...w Bezel mounts on the outside of the blower door See Fig 4 a Cut insulation away from rectangular access hole in blower access panel b Remove adhesive backing from window bezel and from the outside In...

Страница 4: ...0 Table 4 Smart Heat Electrical Data HEATER PART NO KW PHASE INTERNAL CIRCUIT PROTECTION HEATER AMPS 208 230V MIN AMPACITY 208 230V BRANCH CIRCUIT Min Wire Size AWG 208 230v Min Gnd Wire Size 208 230v...

Страница 5: ...230 v terminal and reconnect it to 208 v terminal See Fig 5 The secondary circuit of transformer is protected by a 5 amp fuse mounted on PCB CAUTION On FA FB FC FH FX or PF1MNB018 070 if W2 W3 and E...

Страница 6: ...jumper uncut the time delay allows the second stage heat to be energized approximately 5 sec after the first stage On 18 24 and 30kw heaters the third stage relay board jumper is cut at factory This...

Страница 7: ...Attach L1 through L6 power leads as indicated on label next to fuse block Fig 8 15 and 20kw Fused Heaters 15 and 20kw fused heaters are factory wired for dual supply circuits Single supply circuit is...

Страница 8: ...e Phase Single Supply Circuit Field Modified A00083 Field Ground Wiring L1 L2 Field Power Wiring Ground lug Fig 11 18kw 3 Phase Heater A00081 Field Ground Wiring L2 L3 Field Power Wiring L1 Ground lug...

Страница 9: ...it breaker mounting bracket for dual circuit grounding See Fig 3 3 For 15 and 20 kw fused heaters an additional ground lug is provided on fuse mounting bracket for dual circuit grounding See Fig 2 4 F...

Страница 10: ...eater rating label included with kit over existing electrical information label located on front access panel of fan coil See Fig 17 If kit contains multiple rating labels ensure correct label is appl...

Страница 11: ...980 1085 1250 1100 1100 1250 1225 1225 1250 42 000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460 UNIT FAN SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER KW RANGE 0 10 0 15 0 20 0 30 LO...

Страница 12: ...FE4A FV4B 40FK PF1MNB071 Minimum CFM for Electric Heater Application CFM Electric Heating Modes FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE KW 5 8 9 10 15 18 20 24 30 001 002 Heater Only 625 625...

Отзывы: