INTRODUCTION
This instruction describes the installation of Part No. KFCEH accessory heaters in FA, FB, FC, FH, FX, and PF1MNB018-070 fan coils and in
the FE4, FK4, FV4, 40FK, and PF1MNA071 fan coils.
NOTE:
Electric heaters require a minimum airflow. Minimum airflow and motor speed selection are listed in Table 2. For 3- through 18-kw
standard heaters there are no clearance requirements for the first 36 in. of ductwork. For 20- through 30-kw heaters, a 1-in. clearance is required
for the first 36 in. of ductwork.
INSTALLATION
PROCEDURE 1—INSTALL ELECTRIC HEATER ASSEMBLY
NOTE:
Ensure heater coils are not deformed or damaged during heater installation.
1. Make sure power to unit is off.
2. Remove blower access panel of fan coil unit.
CAUTION: Before installation of heater, the black and yellow pigtail leads must be removed from the fan coil PCB or
wire harness to prevent possible damage to the product. Electrical power will be provided to the board through the heater
circuit plug.
3. Disconnect 2 power wires (black and yellow pigtail leads) from PCB or wire harness (if applicable) and discard. Wires may be part of a
plug assembly or attached to terminals L1 and L2. Remove cooling control plate from fan coil (if equipped). For 18-, 24-, and 30-kw heaters,
remove adapter plate. (See Fig. 1.)
4. Insert heater assembly into front of fan coil so that element rods engage holes in rear heat shield.
5. Attach heater control plate to fan coil using 2 screws provided. For 18-, 24-, and 30-kw heater models, attach front of heater to fan deck
using third screw. (See Fig. 1.)
→
Table 1—Accessory Heater Usage
ELECTRIC HEATER
PART NO.
KW
INTERNAL
PROTECTION
MODEL FA, FB, PF
SIZE
MODEL FC
SIZE
MODEL FH
SIZE
MODEL FX
SIZE
MODEL
FE4, FK4, FV4, 40FK
SIZE
FK, FV, 40FK
INTELLIGENT
HEAT CAPABLE
1 Phase
KFCEH0401N03
3
Non-fused
018, 024
024
001
—
—
NO
KFCEH0501N05
KFCEH2401C05
5
Non-fused
Circuit Breaker
018-071
024-070
001-004
030-060
001-006
NO
NO
KFCEH0801N08
KFCEH2501C08
8
Non-fused
Circuit Breaker
018-071
024-070
001-004
030-060
001-006
NO
NO
KFCEH2901N09
9*
Non-fused
036-071
036-070
002-004
036-060
003-006
YES†
KFCEH0901N10
KFCEH2601C10
10
Non-fused
Circuit Breaker
018-071
024-070
001-004
030-060
001-006
NO
NO
KFCEH3001F15
KFCEH2701C15
KFCEH3101C15
15
Fused
Circuit Breaker
Circuit Breaker
024-071
024-070
001-004
030-060
001-006
YES†
YES†
YES†
KFCEH3201F20
KFCEH2801C20
KFCEH3301C20
20
Fused
Circuit Breaker
Circuit Breaker
030-071
030-070
002-004
030-060
001-006
YES†
YES†
YES†
3 Phase Only
KFCEH1601315
15
Non-fused
036-071
036-070
002-004
036-060
001-006
NO
KFCEH2001318
18
Non-fused
042-071
042-070
003, 004
042-060
003-006
NO
3 Phase, Factory Shipped‡
KFCEH3401F24
KFCEH3501F30
24
30
Fused
Fused
048-071
048-070
003, 004
048-060
005, 006
YES†
YES†
† These heaters are Intelligent Heat capable when used with the FK4, FV4, and 40FK fan coils and corporate 2-speed programmable thermostat (TSTATXXP2S01-B),
Thermidistat™ Control (TSTATXXPRH01-B), or capable zoning system.
‡ Field convertible to 1 phase, single or multiple supply circuit.
* Field convertible to 3 phase.
Table 2—Minimum CFM and Motor Speed Selection
FAN COIL
SIZES
FA, FB, FC, FH, FX,
PF
HEATER KW
3
5
8
9
10
15
18
20
24
30
018
525
525
525
—
600*
—
—
—
—
—
024
700
700
700
700
700
775*
—
—
—
—
030, 033
—
875
875
875
875
875
—
1060*
—
—
036, 038,
—
1050
970
970
970
920
—
1040
—
—
042
—
1225
1225
1225
1225
1225
1225
1225
—
—
048, 054,
—
1400
1400
1400
1400
1400
1400
1400
1400
1400
060, 070,
—
1750
1750
1750
1750
1750
1750
1750
1750
1750
* Indicates medium speed (blue). All other motor speeds at low tap.
—2—