SMART RECOVERY:
•
On or Off, (default=On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling
mode.
ENGLISH/METRIC DISPLAY:
•
°F or °C, (default = °F)
RESET FACTORY DEFAULTS:
Program Schedule:
•
Yes/No to reset back to Energy Star default Time and Temp
schedules.
User Settings:
•
Yes/No to reset the user settings in the Advanced Setup to
factory default settings.
Install Settings:
•
Yes/No to reset install settings in Install/Service menus to
factory default settings.
Last 10 Faults:
•
Yes/No to reset last 10 faults under Service Info menu.
Setup = FURNACE:
Upon a first time start-up of the Infinity Zone Control™, the
furnace DIP switch settings will be copied to the furnace setup
menu. Any changes can then be made from the Infinity Zone
Control™.
AIRFLOW:
•
COMFORT (default)
•
EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is
the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
AC AIRFLOW:
•
EFFICIENCY
•
COMFORT (default)
•
MAXIMUM
Selects the airflow of the furnace when cooling. COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MUM is a fixed airflow of 400 CFM/ton based on the outdoor unit
size.
DEHUM AIRFLOW:
•
NORMAL (default)
•
HIGH
NORMAL airflow adjustment is used during dehumidifying. If
duct sweating is an issue, selecting HIGH will increase the
dehumidifying airflow and reduce the sweating.
LOW HEAT RISE:
•
ON
•
OFF (default)
Set this to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.
STAGING:
•
SYSTEM (default)
•
LOW
•
HIGH
Controls the staging of the furnace. SYSTEM setting will allow
the Infinity Zone Control™ to determine furnace staging. LOW
will only run the low stage of furnace heat. HIGH will only run the
high stage of furnace heat.
OFF DELAY:
•
90 seconds
•
120 seconds (default)
•
150 seconds
•
180 seconds
Amount of time the blower will continue to run after heating has
shut off.
LOCKOUT TEMP:
•
NONE (default)
•
+5 to 55 deg F
Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.
Setup = FAN COIL:
HP/AC AIRFLOW:
•
EFFICIENCY
•
COMFORT (default)
•
MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MUM is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
•
NORMAL (default)
•
HIGH
Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.
HEATER SIZE:
•
(choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self-identifying,
this value is not shown.
Setup = HEAT PUMP / AC:
COOLING LOCKOUT:
•
NONE (default)
•
45° F.
•
50° F.
•
55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
•
(dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
DEFROST INTERVAL:
•
30 minutes
•
60 minutes
•
90 minutes
•
120 minutes (default)
Time interval at which defrost cycles can occur on a heat pump.
9