11. Exit the scheduling mode by either closing the door or
pressing the SCHEDULE button.
12. If changes are made, you will be asked to
″
SAVE CHANGES
YES/NO
″
INSTALL / SERVICE MENUS
The
″
INSTALL / SERVICE
″
menus contain a set of vital
information. This information enables the Installer or Service
person to view a summary of what has been installed, etc. This
information is notcovered in the Owner’s Manual.
To enter INSTALL / SERVICE menus, press and hold the
ADVANCED button for at least ten seconds. The following menu
will appear (See Fig. 20):
NOTE:
The INSTALL / SERVICE menu will automatically exit
after 60 minutes of no push button activity.
EQUIPMENT SUMMARY: Shows all equipment recognized by
and attached to the system.
INSTALL: Used when adding, changing out, or uninstalling
equipment.
SETUP: Used to view or modify equipment settings.
CHECKOUT: Allows testing of equipment operation
SERVICE: Used to view operation and fault history of equipment
and enter dealer name/phone number for display.
EQUIPMENT SUMMARY MENU
An example screen is shown in Fig. 21:
This screen shows indoor unit type and model number, outdoor
unit type (and model number if a 2-speed unit), filter type, any
accessories that are installed, and how many zones are recognized.
INSTALL MENU
This menu item will perform start-up process in order to learn all
equipment in system. Press right side button to initiate the process.
See Fig. 22.
SETUP MENU
This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP
switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip
switches. Fig. 23 shows all the information that can be found in the
SETUP menu.
Setup = THERMOSTAT:
AUTO MODE SETUP:
•
Enable/Disable Auto Changeover mode (default=Enable).
•
Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30 minute timer is deleted.
HEAT/COOL DEADBAND:
•
0 to 6 degrees, (default = 2°).
A minimum difference of 2° is enforced between heating and
cooling desired temperatures. This will allow one setting to
″
push
″
the other to maintain this difference.
OFFSETS: This option allows calibration (or deliberate miscali-
bration) of the temperature and humidity sensors. These offsets are
added to the actual temperature/humidity values (defaults = 0).
•
Zone 1 Offset: -5 to +5 degrees.
•
Outside Temp Offset: -5 to +5 degrees.
•
Humidity Offset: -10 to +10 percent.
CYCLES PER HOUR:
•
Maximum cycles per hour = 4 (default) or 6.
•
Anticipator = 1 to 9 (default=3). This adjusts sensitivity to zone
temperature changes. 1 = most sensitive, 9 = least sensitive.
PROGRAMMING:
•
On or Off (default=On)
•
Periods Per Day = 2 or 4 (default=4)
•
Programmable Fan On/Off (default=Off). If ON is selected, fan
can be set to Auto, Low, Med, or High independently in each
zone.
Fig. 20 — INSTALL / SERVICE MENUS
A03200
INSTALL/SERVICE
EQUIPMENT SUMMARY
INSTALL
SETUP
CHECKOUT
SERVICE
SOFTWARE VERSION 1
EXIT SELECT
Fig. 21 — EQUIPMENT SUMMARY
A04090
EQUIPMENT SUMMARY
FURNACE 58MVP0100-12
AC 38TDB036300
FILTER EAC
HUMIDIFIER YES
UV LIGHTS YES
ZONES
1234
BACK
Fig. 22 — INSTALL
A03202
INSTALL
TO ADD, UNINSTALL OR
RE-INSTALL EQUIPMENT,
PRESS RIGHT SIDE
BUTTON
BACK INSTALL
Fig. 23 — SETUP MENU
A04089
SETUP
THERMOSTAT
FURNACE
HEAT PUMP
ZONING
ACCESSORIES
SYSTEM MAINTENANCE
BACK SELECT
8