ELECT HEAT LOCKOUT / LOCKOUT TEMP:
•
NONE (default)
•
+5 to 55 deg. F
Outside temperature above which the electric heat will not operate.
In dual fuel applications, heat pump will not operate below
selected temperature.
HIGH COOL LATCH:
•
NONE (default)
•
80 - 110 deg F
Outside temperature above which only the high speed (of a
2-speed outdoor unit) will run when cooling.
Setup = ZONING
DISABLE ZONING
•
No (default)
•
Yes
If Yes is selected, zoning is disabled and all dampers open. The
system will run unzoned using the Zone 1 sensor.
ZONE OFFSETS:
•
Zone Temperature Offsets (defaults = 0) Range -5° to +5°
This option allows actual temperature offset for each zone,
allowing calibration (or deliberate mis-calibration) of each sensor.
AIRFLOW LIMITS:
•
Low
•
Medium
•
High (default)
•
Maximum
Zone airflow limit, which is selectable for each zone. Low,
Medium, and High allows a relative noise/airflow relationship in a
zone (i.e. comfort vs. noise). Maximum allows unlimited
noise/airflow (i.e. maximum airflow allowed).
Setup = ACCESSORIES
FILTER TYPE:
•
MEDIA (i.e. TrueSense™)
•
EAC
•
MEDIA+EAC (i.e. TrueSense™)
CLEAN INTERVAL: 30 to 180 days (of actual blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC filter selection only.
HUMIDIFIER INSTALLED:
•
NO
•
YES
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months of humidifier
operation (default=6 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:
•
NO (default)
•
YES
If YES, the humidifier will run with Continuous Fan operation if
there is a humidify demand.
VENTILATOR:
NOTE:
Only appears if ventilator is installed.
CLEAN INTERVAL:
•
60 to 180 days of actual operation (default=90)
Interval at which the Clean Ventilator Pre-filter notification will
turn on.
UV LIGHTS INSTALLED:
•
NO
•
YES
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
•
6 to 48 months operation time (default=12 months)
Interval at which the Change UV Lights notification will be
displayed.
Setup = SYSTEM MAINTENANCE
REMIND OWNER OF ROUTINE MAINTENANCE EVERY:
This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.
•
Range= OFF, 6 to 24 months, (default=12 months)
CHECKOUT MENUS
The Checkout menu will show the equipment installed in the
system. A sample checkout menu is shown in Fig. 24.
Checkout = FURNACE
Make sure the furnace is properly installed before continuing.
•
LOW HEAT RUNTIME: 5 min.
•
HIGH HEAT RUNTIME: 5 min.
This menu item allows the furnace to be exercised. First, a low
heat runtime and high heat runtime are selected. Range = 5 - 120
min.
If only the low heat is to be exercised:
The furnace will execute its ignition start-up sequence. This
sequence will be displayed on the Infinity Zone Control screen.
After the gas valve and blower motor turn on, the screen will
automatically change to
″
FURNACE CHECK
″
and show the
current operating status of the furnace.
Checkout = FAN COIL
ELECTRIC HEAT CHECK
•
ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range = 0 - 120 min.
If you have a fan coil with electric heaters, this menu item will
allow the heaters to be exercised.
With self-identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non-identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be
exercised then press START (right-side button). The display will
change to show the fan coil’s operating status.
Fig. 24 — CHECKOUT MENUS
A03204
CHECKOUT
FURNACE
HEAT PUMP HEATING
HEAT PUMP COOLING
HUMIDIFIER
ZONING
VENTILATOR
BACK SELECT