background image

5

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Improper wiring of the ABCD connector will cause the

Infinity System to operate improperly. Check to make sure all

wiring is correct before proceeding with installation or turning

on power.

CAUTION

!

9. Push any excess wire into the wall. Seal hole in wall to pre-

vent any air leaks. Leaks can affect operation.

10. Attach Infinity Control to the mounting plastic by lining up

the plastic guides on the back of the control with the open-

ing on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

dampers, humidifier, ventilator, UV lights, etc.).

12. Turn on power to equipment.

See wiring diagram, Fig. 11, which includes an indoor

communicating furnace or FE fan coil, with a communicating
outdoor unit. No additional OAT (outdoor air temperature) sensor

is required because the Infinity Control will use the temperature

sensor inside the outdoor unit.
See wiring diagram, Fig. 12, for connecting an indoor

communicating furnace or FE fan coil with a 1--stage air
conditioning unit (non--communicating outdoor). An Outdoor Air

Temperature (OAT) sensor may be installed (but is not required) at

the indoor furnace or fan coil OAT terminals. When OAT sensor is
applied, the Infinity System will provide enhanced system features

and benefits.
See wiring diagram, Fig. 13, for connecting an FE fan coil with a

1--stage heat pump (non--communicating outdoor unit). When
OAT is applied, the Infinity System will provide enhanced system

features and benefits.
In a hybrid heat installation with a non--communicating heat pump,
an OAT sensor must be installed, or the heat pump with not run.

NOTE

: For other applications not listed, refer to the Network

Interface Module (NIM) Installation Instructions.

Humidifier Connection

A 24VAC bypass or fan powered humidifier may be installed.

NOTE

:

Do Not Use

a traditional humidistat to control humidifier

operation. If a humidifier is installed, let the Infinity Control
operate humidifier.

Bypass Humidifiers

A bypass humidifier should be wired directly to the furnace or fan

coil HUM and 24VAC COM terminals. The Infinity Control will

automatically energize the HUM output during a call for
humidification.

Fan Powered Humidifiers

Most fan powered humidifiers produce internal 24VAC in order to

energize upon a switch or contact closure. For this application, a
24VAC N.O. Isolation Relay (DPST)

MUST

be used to prevent

mixing the internal humidifier power with the indoor equipment
transformer. Applying 24VAC isolation relay coil to furnace or fan

coil HUM and COM terminals will allow the Infinity Control to

automatically energize the HUM output during a call for
humidification. The N.O. relay contacts will be used to energize the

humidifier. See fan powered humidifier installation instructions for
more details.

EQUIPMENT HAZARD

Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal

power supply) direct to indoor unit HUM and COM terminals.

CAUTION

!

INITIAL POWER--UP

NOTE

: Refer to Functional Overview (see Fig. 15) to become

familiar with key function buttons such as “System On/Off,”
“Fan,” “Left--Side” and “Right--Side” buttons, etc. These function
buttons will be used frequently during setup.

HOLD

COOL

HEAT

SCHEDULE

VACATION

PROGRAM

SCROLL

BASIC

ADVANCED

SETUPS

Schedule

to program

temperature

schedule

Vacation

to start/end

vacation

Basic

to set time,

humidity

Advanced

for all other

settings

Scroll

up & down

Fan Button

Display Screen

(LCD)

Right-Side

Button

Heat Button

Cool Button

Temperature

(+/-) Button

System

On/Off Button
Basic & Advanced

Setup Buttons

Flip Down

Door

Left-Side

Button

Humidity/OAT

Button

Hold

Button

Time (+/-)

Button

Schedule & Vacation

Program Buttons

Up/Down

Scroll Buttons

A03194

Fig. 15 -- Functional Overview

Power Up Sequence

This section addresses initial power up (or commissioning) of a

new Infinity Control. The User Interface will communicate and
identify all Infinity components in the system. The following is a

typical example for a communicating Variable--Speed Furnace /
Fan Coil with a 2--stage Air Conditioner / Heat Pump (including

Hybrid Heat).
The User Interface display will light up and indicate that it is now

“ESTABLISHING COMMUNICATIONS WITH EQUIPMENT

PLEASE WAIT”. The User Interface will automatically continue
by

“SEARCHING

FOR

EQUIPMENT”,

followed

by

“SEARCHING FOR OUTDOOR EQUIPMENT” (see Fig. 16).
Once the indoor and outdoor equipment has been found, the

Installer will be asked to select Accessories. Packaged Products

will be automatically identified and the Installer will be asked to
select Accessories. Proceed to Selecting Accessories.

ESTABLISHING

COMMUNICATIONS

WITH EQUIPMENT

PLEASE WAIT

SOFTWARE

VERSION

INDOOR UNIT

SEARCHING FOR

INDOOR EQUIPMENT

WORKING

OUTDOOR UNIT

SEARCHING FOR

OUTDOOR EQUIPMENT

WORKING

A03195

Fig. 16 -- Power Up Sequence

UID

01

--

V

Содержание Infinity SYSTXCCUID01-V

Страница 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Страница 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Страница 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Страница 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Страница 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Страница 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Страница 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Страница 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Страница 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Страница 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Страница 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Страница 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Страница 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Страница 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Страница 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Страница 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Страница 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Отзывы: