5
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Improper wiring of the ABCD connector will cause the
Infinity System to operate improperly. Check to make sure all
wiring is correct before proceeding with installation or turning
on power.
CAUTION
!
9. Push any excess wire into the wall. Seal hole in wall to pre-
vent any air leaks. Leaks can affect operation.
10. Attach Infinity Control to the mounting plastic by lining up
the plastic guides on the back of the control with the open-
ing on the mounting plastic and push on.
11. Perform installation of all other system equipment (i.e.
dampers, humidifier, ventilator, UV lights, etc.).
12. Turn on power to equipment.
See wiring diagram, Fig. 11, which includes an indoor
communicating furnace or FE fan coil, with a communicating
outdoor unit. No additional OAT (outdoor air temperature) sensor
is required because the Infinity Control will use the temperature
sensor inside the outdoor unit.
See wiring diagram, Fig. 12, for connecting an indoor
communicating furnace or FE fan coil with a 1--stage air
conditioning unit (non--communicating outdoor). An Outdoor Air
Temperature (OAT) sensor may be installed (but is not required) at
the indoor furnace or fan coil OAT terminals. When OAT sensor is
applied, the Infinity System will provide enhanced system features
and benefits.
See wiring diagram, Fig. 13, for connecting an FE fan coil with a
1--stage heat pump (non--communicating outdoor unit). When
OAT is applied, the Infinity System will provide enhanced system
features and benefits.
In a hybrid heat installation with a non--communicating heat pump,
an OAT sensor must be installed, or the heat pump with not run.
NOTE
: For other applications not listed, refer to the Network
Interface Module (NIM) Installation Instructions.
Humidifier Connection
A 24VAC bypass or fan powered humidifier may be installed.
NOTE
:
Do Not Use
a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Infinity Control
operate humidifier.
Bypass Humidifiers
A bypass humidifier should be wired directly to the furnace or fan
coil HUM and 24VAC COM terminals. The Infinity Control will
automatically energize the HUM output during a call for
humidification.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in order to
energize upon a switch or contact closure. For this application, a
24VAC N.O. Isolation Relay (DPST)
MUST
be used to prevent
mixing the internal humidifier power with the indoor equipment
transformer. Applying 24VAC isolation relay coil to furnace or fan
coil HUM and COM terminals will allow the Infinity Control to
automatically energize the HUM output during a call for
humidification. The N.O. relay contacts will be used to energize the
humidifier. See fan powered humidifier installation instructions for
more details.
EQUIPMENT HAZARD
Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal
power supply) direct to indoor unit HUM and COM terminals.
CAUTION
!
INITIAL POWER--UP
NOTE
: Refer to Functional Overview (see Fig. 15) to become
familiar with key function buttons such as “System On/Off,”
“Fan,” “Left--Side” and “Right--Side” buttons, etc. These function
buttons will be used frequently during setup.
HOLD
COOL
HEAT
SCHEDULE
VACATION
PROGRAM
SCROLL
BASIC
ADVANCED
SETUPS
Schedule
to program
temperature
schedule
Vacation
to start/end
vacation
Basic
to set time,
humidity
Advanced
for all other
settings
Scroll
up & down
Fan Button
Display Screen
(LCD)
Right-Side
Button
Heat Button
Cool Button
Temperature
(+/-) Button
System
On/Off Button
Basic & Advanced
Setup Buttons
Flip Down
Door
Left-Side
Button
Humidity/OAT
Button
Hold
Button
Time (+/-)
Button
Schedule & Vacation
Program Buttons
Up/Down
Scroll Buttons
A03194
Fig. 15 -- Functional Overview
Power Up Sequence
This section addresses initial power up (or commissioning) of a
new Infinity Control. The User Interface will communicate and
identify all Infinity components in the system. The following is a
typical example for a communicating Variable--Speed Furnace /
Fan Coil with a 2--stage Air Conditioner / Heat Pump (including
Hybrid Heat).
The User Interface display will light up and indicate that it is now
“ESTABLISHING COMMUNICATIONS WITH EQUIPMENT
PLEASE WAIT”. The User Interface will automatically continue
by
“SEARCHING
FOR
EQUIPMENT”,
followed
by
“SEARCHING FOR OUTDOOR EQUIPMENT” (see Fig. 16).
Once the indoor and outdoor equipment has been found, the
Installer will be asked to select Accessories. Packaged Products
will be automatically identified and the Installer will be asked to
select Accessories. Proceed to Selecting Accessories.
ESTABLISHING
COMMUNICATIONS
WITH EQUIPMENT
PLEASE WAIT
SOFTWARE
VERSION
INDOOR UNIT
SEARCHING FOR
INDOOR EQUIPMENT
WORKING
OUTDOOR UNIT
SEARCHING FOR
OUTDOOR EQUIPMENT
WORKING
A03195
Fig. 16 -- Power Up Sequence
UID
01
--
V