SYSTEM MALFUNCTION SCREEN

OUTSIDE: 84

_

| FAN: AUTO

71

_

HVAC SERVICE

1---800---555---1212

SYSTEM MALFUNCTION

CALL TECHNICIAON

A07036

Fig. 34 -- System Malfunction Screen

Fan Coil

The code number represents flash code on circuit board of fan coil.
Certain faults will generate a system malfunction message on the

main screen. When this occurs, a technician should proceed to the

Last 10 System Events screen in the Service Menu to determine
which fault has caused the message.
Below is a list of which faults will result in a System Malfunction
event:
Code 37 -- Heater output sensed On when not energized
Code 41 -- Blower Motor Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 44 -- Motor Communication Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 45 -- Control failure

Furnace

The code number represents flash code on circuit board of furnace.
Code 13 -- Limit Circuit Lockout
Code 14 -- Ignition Lockout
Code 15 -- Blower Motor Lockout (ventilator, humidifier,

dehumidifier, outdoor unit will be turned off)
Code 21 -- Gas Heating Lockout
Code 22 -- Abnormal Flame Proving Signal
Code 23 -- Pressure Switch Did Not Open
Code 24 -- Secondary Voltage Fuse Open
Code 33 -- Limit Circuit Fault AND high heat only is active
Code 41 -- Blower Motor Fault (cooling mode only) (ventilator,

humidifier, dehumidifier, outdoor unit will be turned off)
Code 45 -- Control Circuitry Lockout

NOTE

: For codes 13, 14 and 21, the system will use heat pump

heating exclusively if available. When the error code is cleared or
disappears, furnace heating will resume if still requested.

Service Tool Mode

The --V model of user interface software version 21 can be used as

a service tool on any Infinity system. Attach the --V model user
interface anywhere on the ABCD wiring (e.g. at the indoor or

outdoor unit). When the user interface powers up, it will ask the

user if they wish to enter service mode. Selecting “Yes” will allow
the --V model user interface to take over as the system controller,

putting the regular system user interface to sleep. The screen on the
regular user interface will display “IN SERVICE MODE”. The --V

model user interface will then learn all equipment and function as
the system controller. While in service mode, the --V model user

interface will not transfer any settings or information to or from the
regular user interface----it only takes over control of the system.

After removing the --V model user interface from the ABCD

wiring, the regular user interface will take over the system after two
minutes.

Outdoor Unit

The code number represents flash code on circuit board of outdoor
unit.
Code 25 -- Invalid model plug
Code 45 -- Control Failure
Code 47 -- No 230V at unit
Code 48 -- Loss of inverter communications
Code 69 -- Inverter internal fault
Code 73 -- Contactor shorted
Code 74 -- No high voltage at compressor
Code 76 -- Low stage didn’t start three times
Code 78 -- High stage didn’t start three times
Code 81 -- Thermal lockout in low stage -- 4 hrs.
Code 82 -- Thermal lockout in high stage -- 4 hrs.
Code 83 -- Low Pressure Lockout -- 4 hrs.
Code 84 -- High Pressure Lockout -- 4 hrs.
Code 85 -- Low contactor open
Code 86 -- Low contactor shorted
Code 87 -- High contactor open
Code 88 -- Inverter Temp Lockout or High Contactor Shorted
Code 96 -- VDC under voltage lockout
Code 97-- VDC over voltage lockout
Code 99 -- High torque lockout

User Interface

S

Temp sensor failed, loss of communication with smart sensor,
smart sensor fault. “NO SENSOR DATA” shown

S

Indoor unit communication fault

S

Outdoor unit communication fault

S

Packaged product communication fault

S

NIM communication fault

S

SAM communication fault

S

Possible Frozen Coil

S

High Room Temp Alert, when 100

_

F exists for at least 10

minutes, and removed when less than or equal to 98

_

F exists

S

Low Room Temp Alert, when 38

_

F exists for at least 10

minutes, and removed when greater than or equal to 40

_

F exists

S

High Humidity Alert, when 80% Rh exists for 30 minutes, and
removed when less than or equal to 78% Rh exists

The user can press the right side button to dismiss the notice. The

regular run mode screen will then appear except “SYSTEM

MALFUNCTION” will appear in place of the day/time. If the error
has not disappeared within 24 hours, the above display will return.

If the error code disappears, “SYSTEM MALFUNCTION” will
disappear and the day/time will reappear.

Copyright 2011 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Printed in China

Edition Date: 11/11

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: UID01---06SI

Replaces: UID01--- 5SI

UID

01

--

V

Содержание Infinity SYSTXCCUID01-V

Страница 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Страница 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Страница 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Страница 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Страница 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Страница 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Страница 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Страница 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Страница 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Страница 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Страница 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Страница 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Страница 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Страница 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Страница 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Страница 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Страница 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Отзывы: