10

R

G

FE Fan Coil or 
Variable Speed Furnace

A07114

Fig. 26 -- G Input Wiring for Blower Operation

R

G

FE Fan Coil or 
Variable Speed Furnace

A07115

Fig. 27 -- G Input Wiring for System Shutdown

with Infinity

t

Control (Contact type selectable;

Normally Closed (default) or Normally Open)

High Stage Timer

Minimum amount of time low stage must operate before high stage

is activated. Ten to 60 minutes. 10 = default
A demand of 5

_

F (3

_

C) or more will override the staging timer.

Furnace Airflow (Capacity) Limiting

The following settings allow the installer to restrict the furnace

within certain minimum and maximum airflows. These airflows are
converted to capacities. The Min and Max limits are determined by

the equipment size. These settings are not the same as the zoning

airflow limits.
Min CFM (only appears with modulating furnaces)
Minimum CFM to run a modulating furnace. This will increase the
minimum operating capacity of the furnace. Default value is the

furnace air flow for the lowest heat capacity.
Maximum CFM (only appears with modulating furnaces)
Maximum CFM to run a modulating furnace. This will reduce the

operating capacity of the furnace. Default value is the furnace air
flow for the highest heat capacity.

Off Delay

S

90 seconds

S

120 seconds (default)

S

150 seconds

S

180 seconds

Amount of time the blower will continue to run after heating has

shut off.

Dehum Drain

Turns off the continuous fan at the end of cooling for five minutes

in order to drain the indoor coil of water. The fan will only be
turned off if a dehumidify demand existed at the start of or during

the cooling cycle. Default is enabled.

Altitude

S

US

0 -- 2000 (default)

S

US 2001 -- 3000

S

CA 2001 -- 4500 (for Canada only)

S

US 3001 -- 4000

S

US 4001 -- 5000

S

US 5001 -- 6000

S

US 6001 -- 7000

S

US 7001 -- 8000

S

US 8001 -- 9000

S

US 9001 -- 10000

This setting will adjust the furnace’s airflow to compensate for

altitude. Altitude adjustment is not available with older furnaces.

Please see furnace instructions for further details.

Setup -- Fan Coil

Heat Pump Heating:

S

COMFORT (default) Heat Pump airflow is varied depending on
outdoor temperature to maximize comfort.

S

EFF 325 -- Fixed airflow used to achieve specified ratings . This
is nominally 325 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

EFF 350 -- Fixed airflow used to achieve specified ratings . This
is nominally 350 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

MAXIMUM -- 400 CFM/ton.

Heat Pump Cooling Airflow:

S

COMFORT (default) Cooling airflow is varied depending on
humidity and temperature demand settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When

COMFORT

is not selected, the unit will not run

reduced airflows for dehumidification. Heat Pump airflow is
varied depending on outdoor temperature to maximize comfort.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.

S

QUIET-- minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.

Dehum Airflow:

S

NORMAL (factory default) -- When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.

S

HIGH -- Minimum airflow during the dehumidify mode is
increased to reduce duct and register sweating. Also increases
minimum airflow during normal cooling operation to reduce
duct sweating.

UID

01

--

V

Содержание Infinity SYSTXCCUID01-V

Страница 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Страница 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Страница 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Страница 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Страница 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Страница 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Страница 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Страница 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Страница 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Страница 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Страница 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Страница 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Страница 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Страница 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Страница 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Страница 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Страница 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Страница 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Отзывы: