11
4.4.2.
Damper Control Module (zoning systems only)
All wiring is run back to the Damper Control Module. Select a location near the
furnace or fan coil where wiring from the control, each Remote Room Sensor or
Smart Sensor, each damper actuator, and the equipment itself can come together
easily. The Damper Control Module is approved for indoor use only and should
never be installed with any of its components exposed to the elements. The Damper
Control Module (and zone dampers) may be installed in any area where the
temperature remains between --4
_
F to 158
_
F (--20
_
C to 70
_
C), and there is no
condensation. The cover must be installed to prevent damage from other sources.
Do not locate where it will be accessible to children. It may be mounted in either
vertical or horizontal position. Remember that wiring access is likely the most
important consideration.
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
To prevent possible damage to the Damper Control Module,
DO NOT mount on plenum, ductwork, or flush against
furnace or fan coil.
CAUTION
!
4.5.
Mounting
First become familiar with all plastic assembly pieces shown on the following page.
The Infinity Touch Control will snap together with the backplate. A backplate is
supplied. Attach backplate using only a small hole in the wall allowing a four wire
connection to pass through. Mount the assembly to the backplate.