44
S
Airflow:
Selectable between Off to Max in 50 CFM increments
d
Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
d
Default = Off
S
Blower On Delay:
Selectable from 0 to 240 seconds
d
Default = 30 seconds
S
Blower Off Delay:
Selectable from 0 to 240 seconds
d
Default = 0 seconds
6.4.
Check out
Touch
CHECKOUT
to view the equipment installed in the system. Perform
checkout test to make sure each piece of equipment is operating properly.
A13122
6.4.1.
Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to
be exercised. With self--identifying electric heaters, three stages of electric heat are
available to be exercised in any combination. Non--identifying heaters will only
provide one stage of heat. After the selections are made, touch
START
.
S
Low Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes